Permit Number: DP20-0274
Parcel: 122172730

Address:
3408 E CODY ST

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP20-0274
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2021 SBEASLE1 START PLANS SUBMITTED Completed
01/12/2021 JVINCEN1 COT NON-DSD FIRE Approved
01/28/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/03/2021 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

4.1 Identification and Descriptive Data

All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

The Development Package will may be needed and should contain the following identification in the lower right corner of each sheet:

Any other relevant case number for reviews or modifications that affect the site.

Add case number DP20-0274 on each sheet.

Ensure that Zoning, Engineering comments and concerns are addressed prior to landscape section approval.

Additional comments may apply
02/03/2021 ZELIN CANCHOLA COT NON-DSD TRAFFIC Reqs Change DP20-0274
February 3, 2021
Zelin Canchola
Transportation and Mobility Engineering

The following requires change. Show on development plan.

25 feet curb return radius is required along arterial streets. Change 18 feet to 25.

Show pag standard pedestrian ramps at the driveway if required to tie in to existing sidewalk due to elevation change.

Close unused driveway/curb opening. Remove unused concrete from old driveway. show on plan.

Show existing light pole and new location of required.
02/16/2021 SBEASLE1 COT NON-DSD REVIEW Approved 02/16/21
For this specific development, we have no comments; it will not impact transit services.
Thank you,
Christopher Blue
Transit Services Coordinator | Transit Services Division
Department of Transportation & Mobility
C: 520.260.9558
02/18/2021 STEVE SHIELDS ZONING REVIEW Reqs Change FROM: Development Services Department Zoning Review

PROJECT: 3427 & 3435 E Speedway Blvd
Development Package (1st Review)
DP20-0274

TRANSMITTAL DATE: February 18, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is January 07, 2022.

CONTENT REQUIREMENTS

1. COMMENT: 2-06.4.3 – Provide the development package case number, DP20-0274, adjacent to the title block on all sheets.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

2. COMMENT: 2-06.4.9.E – It appears that some type of lot reconfiguration is proposed, this process must be completer prior to approval of this DP. Provide the applicable case number adjacent to the title block on all sheets of the DP.

3. COMMENT: 2-06.4.9.H.5 – Per UDC Article 7.4.6.F.2.a.(2) show the required 1’-0” setback from the building to the drive-through lane for both proposed buildings.

4. COMMENT: 2-06.4.9.H.5.d – The short-term bicycle parking for the eastern building does not meet the requirements of UDC Article 7.4.9. C.2.c.

5. COMMENT: 2-06.4.9.H.5.d – Demonstrate on the plan or detail how the short-term bicycle parking meets the requirements of UDC Articles 7.4.9.C.1.e, 7.4.9.B.2.f & .g are met

6. COMMENT: 2-06.4.9.H.5.d – Show the required long-term bicycle parking on the plan and demonstrate how the requires of UDC Articles UDC Articles 7.4.9.C.1.e and 7.4.9.D are met.

If you have any questions about this transmittal, please contact Elisa Hamblin, (520) 837-4966 or Elisa.Hamblin @tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
02/19/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change DATE: February 19, 2021
Returned for Corrections

PERMIT/ACTIVITY: DP20-0274
DESCRIPTION: SITE/GRADING - Dunkin Donuts, new development.

FEES DUE: $ 2,305.70
Please pay the total fees (or at a minimum, the REVIEW Fees). A payment is required before your resubmittal.

ONLINE PAYMENT
https://www.tucsonaz.gov/pdsd/fees
If information is not available or amount isn't correct, check back in a few hours after data is updated.
(Visa, MC, Discover, American Express, or pay from bank account)
1- Click on: Pay Planning & Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click the blue tab: Continue
5- Under the Pay column, check the boxes you want to pay
6- Click Continue, then enter your credit card info

RESUBMITTAL
Submit the following documents to:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
(Select "Existing Application", then the permit number)

1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Title the documents for your 2nd submittal starting with the
submittal number, for example: 2_Plan_Set

SEE COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

For all NEW development package submittals on the new Filedrop page, select the box: "SITE REVIEW..." for quicker processing.

Thank you.

City of Tucson
Attn: Sharon Beasley, Permit Specialist
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov
02/19/2021 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP20-0274

DP20-0274
1) This project will require a pre-construction meeting prior to issuance of the development package permit. Project will require EOR certification prior to final inspection
2) Provide a trash enclosure detail to meet TSM section 8-01.9.0
3) Provide a minimum of 40' of clear space in front of the proposed trash enclosure per TSM section 8
4) Provide a complete pedestrian circulation path according to TSM section 7. This includes a path to the new proposed trash enclosure. Pedestrian pathway cannot run behind parking spaces or turn in the PAAL
5) Provide a complete pedestrian circulation path according to TSM section 7, this includes a pedestrian circulation connection to E Cody st
6) Sheet 3, Keynote 3 on the northside of the southwestern PAAL. The referenced detail on sheet 6 does not exist. Pathway is not correct and appears to direct into the wing/transition of the curb access ramp. Provide a detail and adjust as needed
7) Sheet 6, Detail A. Vehicle overhang reduces pedestrian pathway width for access ramp. Adjust as needed to provide a minimum 4' path
8) Sheet 3, keynote 3 does not exist on sheet 6. Update as needed
9) For the driveway entrance on speedway, provide curb access ramps according to PAG standard detail 207. Provide spot grades for the ramps and crossing to ensure ADA compliance
10) Ensure that roof drains, from the new building, scupper underneath sidewalks as needed. Reference COT Technical Standards Manual (TSM) section 7-01.4.1.e. Show on plans location of roof drains and scuppers
11) Per City of Tucson (COT) Technical Standards Manual (TSM) section 10-01.4.1. Provide a minimum 5' along E Cody Street
12) The City of Tucson uses the Stormwater Detention/Retention Manual found in the following link. https://www.tucsonaz.gov/files/pdsd/codes/Stormwater_detention-retention_manual.pdf Section 1.4 requires 5 year threshold retention be provided. Please update as needed to reference this design manual. Provide calculations or confirm that this minimum volume is being provided
13) Update drainage statement to show existing and proposed watersheds to show that existing drainage outfall locations will be maintained. At the outfall location, which appears to be along Cody street a sidewalk scupper may be needed
14) Provide spot grades in all depressed landscaped areas and at the upstream and downstream of each inlet. Spot grades to consider the depth of ground cover proposed
15) For volumes of rainwater harvesting basins. Take into account side slopes and constructed condition of basin and check volumes provided
16) Sheet 10. Rainwater harvesting calcs indicate a avg basin depth of 4". 4" of depth does not provide the volumes stated in the grading/site plan. Please double check depths to volumes
17) Show on plans that the existing aprons along E Cody St and E Speedway Bl will be closed off and replaced with new vertical curb
18) Per (TSM) section 10-01.3.2.C. At the intersections of streets with other streets or collector or arterial streets with PAALs/Driveways, the curb lines will be connected with a curve having the minimum radius shown in Figure 6, measured at the face of the curb. Update the driveway entrance/exit one to E Speedway Bl to show a 25' radius instead of the 18' as shown

John Van Winkle, P.E.