Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP20-0265
Parcel: 13612004H

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP20-0265
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2021 SBEASLE1 START PLANS SUBMITTED Completed
04/27/2021 SSHIELD1 LANDSCAPE REVIEW Approved
04/27/2021 STEVE SHIELDS ZONING REVIEW Reqs Change FROM: Development Services Department Zoning Review

PROJECT: Rauscher Reservoir & ‘D’ – ‘E’ Zone Booster SCADA Upgrade
Development Package (2nd Review)
DP20-0265

TRANSMITTAL DATE: April 27, 2021

DUE DATE: April 29, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is December 28, 2021.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

1. The Special Exception case number should be listed as T20SE00017. 2-06.4.7.A.6.a – As a Special Exception process is required once approved provide the case number adjacent to the title block on all sheets and provide a general note stating the case number, type of process, date approved and if applicable any conditions of approval. Zoning cannot approve the DP until the Special Exception has been approved.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

2. 2-06.4.9.H.5.a – This comment was not addressed correctly. Per TABLE 7.4.4-1: MINIMUM NUMBER OF MOTOR VEHICLE SPACES REQUIRED, UTILITIES USE GROUP, 1 space per 500 sq. ft. GFA, with a minimum of 2 spaces per facility. Provide a vehicle parking space calculation on the plan. This calculation shall provide the number require and provided.

If you have any questions about this transmittal, please contact Elisa Hamblin, (520) 837-4966 or Elisa.Hamblin @tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
05/07/2021 LOREN MAKUS ENGINEERING REVIEW Approved
05/10/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Email sent from: COTDSDPermits
To: Ryan Stucki
Mon 5/10/2021 8:37 AM

Returned for Corrections Notice

PERMIT/ACTIVITY: DP20-0265
DESCRIPTION: SITE/Special Exception - Tucson Water, Rauscher Reservoir and 'D' - 'E' Zone Booster SCADA upgrade. 2727 S HARRISON RD

FEE BALANCE: $0 (zero) Thank you for the payment.

INCLUDE IN YOUR RESUBMITTAL
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

Please title your 3rd submittal documents according to this example:
3_Comment Response Letter, 01.01.21

FILEDROP
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
(Select "Existing Application", then the permit number)

SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on “View”


Sharon Beasley, Permit Specialist

City of Tucson, Planning and Development Services
email: COTDSDPermits@TucsonAz.gov