Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: DP20-0243
Parcel: 14041133A

Address:
3550 E CORONA RD

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP20-0243
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/08/2020 SBEASLE1 START PLANS SUBMITTED Completed
12/08/2020 SBEASLE1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Reqs Change December 2, 2020

RE: DP20-0243 Site/Grading/SWPPP/Floodplain - Project Merlin, commercial storage - 1st Submittal, Received November 3, 2020

Thank you for the opportunity to comment on DP20-0243, Project Merlin; 1st Submittal, a development package application for an approximately 46.73 acre site, located northwest of the intersection of South Alvernon Way and East Los Reales. The property is zoned Light Industrial Zone (I-1), with the proposed development being a commercial storage use for a warehouse.

This site is within the Tucson International Airport avigation easement requirements and public disclosure area, FAA traffic pattern airspace, and FAA Part 77 airspace.

The Tucson Airport Authority (TAA) is unable to approve the 1st submittal of this project. The applicant shall revise the Traffic Impact Analysis document and Development Package to respond to TAA’s comments.

TAA Comments:

1. The applicant shall revise the Traffic Impact Analysis document for this project. This report incorrectly represents Los Reales Road, between Country Club Road and Alvernon Way, as being an undivided roadway with a speed limit of 35 MPH. Los Reales Road is classified as an Arterial Roadway and has a posted speed limit of 50 MPH.

2. Revise page 21 of 75 of the development package, the Q100 doesn't show a value at the TAA property boundary.

3. Revise page 21 of 75 of the development package, the existing grade at sta: 10+00 to 10+30 looks to be a low point (1/2') from the rip rap edge. TAA does not want standing water at the property boundary.

Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811.

Respectfully,
Scott Robidoux, C.M., Senior Airport Planner
12/09/2020 ANDREW CONNOR LANDSCAPE REVIEW Approved
12/09/2020 SBEASLE1 UTILITIES TUCSON ELECTRIC POWER Passed
12/09/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. A separate permit is required for the installation of a private sewer collection system with manholes and will require a review of the system design by the Pima County Department of Environmental Quality. Reference Title 18, R18-9-E302, 4.02 General Permit, Arizona Administrative Code.
2. An approved development plan is not to be used for construction or modification of on-site utilities (e.g. water service to buildings, building sewers, site lighting, electrical service to buildings, etc.). The construction of the on-site utilities may be included with the permit for constructing the building or as a separate permit.
3. The maximum distance between cleanouts shall be 100-feet, measured along the developed pipe length (see sheets 37, 38, and 40). Reference: Section 708.1.1, IPC 2018.
12/09/2020 SBEASLE1 OTHER AGENCIES U. S. POST OFFICE Passed
12/09/2020 GDAURIA1 COT NON-DSD FIRE Approv-Cond * Concrete skirts at NW and SW corners of building to have a rolled curb, bollards and must support 75,000 pounds for aerial access to those corners.
12/09/2020 STEVE SHIELDS ZONING REVIEW Approved
12/09/2020 SBEASLE1 COT NON-DSD PARKS & RECREATION Approved 12/09/20

The Tucson Parks and Recreation Department has no issues or concerns regarding this development as shown on the submitted plans.

Howard B. Dutt, RLA, Landscape Architect
Tucson Parks and Recreation, (520) 837-8040
12/09/2020 SBEASLE1 OTHER AGENCIES PIMA ASSN OF GOVTS Passed
12/09/2020 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Approved
12/09/2020 SBEASLE1 UTILITIES SOUTHWEST GAS Passed
12/10/2020 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved December 10, 2020
DP20-0243
Zelin Canchola

The offsite improvments are acceptable according to the traffic impact analysis. The work will require a private improvement agreement (PIA) with the department if Transportation and Mobility Engineering.
12/18/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change DATE: December 18, 2020

PERMIT/ACTIVITY: DP20-0243
DESCRIPTION: Site/Grading/Swppp/Floodplain - Project Merlin.

RETURNED FOR CORRECTIONS NOTICE
Your Next Steps:
1. Online Payment
2. Resubmittal of updated/corrected documents

IMPORTANT - NEW FILEDROP for your resubmittal:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application"

FYI - For all NEW development package submittals in the future (not this resubmittal) on the new Filedrop page, select the box: "SITE REVIEW..." so it is routed to correct staff member for quicker processing.

FEES DUE: $ 12,923.25 (see image at end of this email, disregard the blue highlighted row)
Please pay the total fees (or at a minimum, the REVIEW Fees).

ONLINE PAYMENT
https://www.tucsonaz.gov/pdsd/fees
IMPORTANT: If information is not available or amount isn't correct, check back later after data is updated.
(Visa, MC, Discover, American Express, or pay from bank account)

1- Click on: Pay Planning & Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click the blue tab: Continue
5- Under the Pay column, check the boxes you want to pay
6- Click Continue, then enter your credit card info
7- If any issues, try using the browser Internet Explorer

RESUBMITTAL OF UPDATED/CORRECTED DOCUMENTS
Submit documents to NEW FILEDROP:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp

1) Comment Response Letter (your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Title the documents for your 2nd submittal starting with the
submittal number, for example: 2_Plan_Set

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

Thank you.

City of Tucson
Attn: Sharon Beasley, Permit Specialist
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov
12/18/2020 SBLOOD1 ENGINEERING REVIEW Approved