Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2021 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

4.1 Identification and Descriptive Data

All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

The Development Package will contain the following identification in the lower right corner of each sheet:

Any other relevant case number for reviews or modifications that affect the site.

Add case number and DP20-0242 on each sheet.

Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.

Additional comment may apply
01/12/2021 NICHOLAS ROSS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Nick Ross
Lead Planner

PROJECT:
Development Package (1st Review)
DP20-0242

TRANSMITTAL DATE: January 5, 2021

DUE DATE: January 12, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is January 5 , 2021.


1. 2-06.4.2 - The title block shall include the following information and be provided on each sheet:

COMMENT: Please include "DP20-0242"

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

2. 2-06.4.9.A - Draw in all proposed lot lines with approximate distances and measurements.
COMMENT: This proposal incorporates several adjacent parcels. A lot combination will be required prior to approval.

3. 2-06.4.9.H.5 - If utilizing parking area access lanes (PAALs), they shall be designed in accordance with Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.
COMMENT: Indicate at minimum a 1ft clearance from proposed parking canopies from adjacent PAALs.

4. 2-06.4.9.H.5.c - Show all loading zones, vehicle maneuverability fully dimensioned, and access route. Provide as a note the number of loading spaces required, the number provided, whether the loading space is a Type A or B as provided in UDC Section 7.5.4.
COMMENT: General Manufacturing Use must comply with Use Specific Standards 4.9.5.C and 4.9.13.Q. In the case of 4.9.5.C.5 - "All work and activity in connection with, and accessory to, a manufacturing use, such as loading and unloading areas, docks, and platforms, shall be located entirely within a building or an area on the lot that shall be enclosed on all sides by a solid wall or fence six feet in height. Such loading and unloading areas, docks, and platforms shall be located as far from any surrounding residential uses or zones as is reasonably possible."

5. 2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided.
COMMENT: Indicate location of long term bicycle parking.

6. 2-06.4.9.O - All applicable building setback lines, such as erosion hazard, floodplain detention/retention basins, and zoning, including sight visibility triangles, will be shown.
COMMENT: Provide proposed building setback information.

7. 2-06.4.9.R - Show on-site pedestrian circulation and refuge utilizing location and the design criteria in Section 7-01.0.0, Pedestrian Access, of the Technical Standards Manual.
COMMENT: Show accessible path connecting both buildings on site and connection to the sidewalk in the right-of-way along Old Vail Rd.

If you have any questions about this transmittal, please contact me at Nicholas.Ross@tucsonaz.gov or (520) 837-4029.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
01/15/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Clearly show pedestrian circulation from each building to Old Vail Road. Show slopes and cross-slopes to demonstrate ADA accessibility.
2. A floodplain use permit is required for this project. Use the online permit portal to submit a FUP application.
01/18/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change DATE: January 18, 2021

Returned for Corrections / Request for Resubmittal

PERMIT/ACTIVITY: DP20-0242

DESCRIPTION: Site/Grading/Swppp - TuSimple Expansion. 9538 E OLD VAIL RD

FEES DUE: $ 5,177.50 Thank you for the partial payment. A payment is required before your resubmittal.

ONLINE PAYMENT
https://www.tucsonaz.gov/pdsd/fees

PLEASE READ: If information is not available or amount isn't correct, check back in a few hours after data is updated.

(Visa, MC, Discover, American Express, or pay from bank account)
1- Click on: Pay Planning & Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click the blue tab: Continue
5- Under the Pay column, check the boxes you want to pay
6- Click Continue, then enter your credit card info
7- If any issues, try using the browser Internet Explorer

RESUBMITTAL OF UPDATED/CORRECTED DOCUMENTS
Submit documents to NEW FILEDROP:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp

1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Title the documents for your 2nd submittal starting with the
submittal number, for example: 2_Plan_Set

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

FYI - For all NEW development package submittals in the future (not resubmittals) on the Filedrop page, select the box: "SITE REVIEW...".

Thank you.

City of Tucson
Attn: Sharon Beasley, Permit Specialist
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov
12/04/2020 SBEASLE1 START PLANS SUBMITTED Completed
12/21/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
12/30/2020 JPEELDA1 FIRE REVIEW Approved