Permit Number: DP20-0240
Parcel: 132130770

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP20-0240
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2021 JPEELDA1 COT NON-DSD FIRE Reqs Change IFC 2018, 507.5.1.1 Hydrant for Standpipe system. Buildings equipped with a standpipe system installed in accordance with Section 905 shall have a fire hydrant within 100 feet of the fire department connections
IFC 2018, Section D105:
D105.1 Where required. Where the vertical distance between the grade plane and the highest roof surface exceeds 30 feet, approved aerial fire apparatus access roads shall be approved.
D105.3 Proximity to the building. One or more of the required access routes meeting this condition shall be located not less than 15 feet and not greater than 30 feet from the building, and shall be positioned parallel to one entire side of the building.
Please show these areas on your drawings.
01/06/2021 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Denied 01/06/21

Applicant needs to provide a letter of approval from the Bridges Design Review Committee.

John Beall
John.Beall@TucsonAz.gov
(520) 791-5550
01/14/2021 ALEXANDRA HINES ZONING REVIEW Reqs Change 1. Add "DP20-0240" to the bottom right-hand corner of every sheet.

Alexandra Hines
alexandra.hines@tucsonaz.gov
01/26/2021 SBLOOD1 ENGINEERING REVIEW Approved
01/28/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change DATE: January 28, 2021
Returned for Corrections / Request for Resubmittal

PERMIT/ACTIVITY: DP20-0240
DESCRIPTION: Site/Grading/SWPPP - Springhill Suites, new hotel.
FEE BALANCE: $0 (zero) Thank you for the payment.

RESUBMITTAL OF UPDATED/CORRECTED DOCUMENTS
Submit documents to NEW FILEDROP:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application", then the permit number

1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Title the documents for your 2nd submittal starting with the
submittal number, for example: 2_Plan_Set

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

FYI - For all NEW development package submittals in the future (not resubmittals) on the Filedrop page, select the box: "SITE REVIEW...".

Thank you.

City of Tucson
Attn: Sharon Beasley, Permit Specialist
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov
11/27/2020 SBEASLE1 UTILITIES SOUTHWEST GAS Passed
11/27/2020 SBEASLE1 OTHER AGENCIES PIMA ASSN OF GOVTS Passed
11/27/2020 SBEASLE1 START PLANS SUBMITTED Completed
11/27/2020 SBEASLE1 OTHER AGENCIES U. S. POST OFFICE Passed
12/04/2020 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved 12/04/20
ADOT South Central District Office and ADOT Southern Regional Traffic have reviewed the request and have no comments on this development; and support its acceptance. The development will have no direct impacts to ADOT facilities because of the location. Thank you

Richard La Pierre, Permits Supervisor, South Central District
1221 South Second Ave, Tucson, Arizona 85713
520.388.4234 (office), 520.307.5893 (cell)
RLaPierre@azdot.gov
12/16/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
12/16/2020 SBEASLE1 UTILITIES TUCSON ELECTRIC POWER Approved (The TEP FACILITIES MAP mentioned below can be viewed online: www.TucsonAz.gov/Pro. See the Documents section.)

December 11, 2020

SUBJECT: Springhill Suites, DP20-0240

Tucson Electric Power Company (TEP) has reviewed and approved the development plan submitted December 1, 2020. There do not appear to be any conflicts.
Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer.
In order to apply for electric service, call the New Construction Department at (520) 918-8300.
Submit a final set of plans including approved site, electrical load, paving off-site improvements and irrigation plans, if available include a CD with the AutoCAD version of the plans.
If easements are required, they will be secured by separate instrument. Your final plans should
be sent to:
Tucson Electric Power Company
Attn: Ms. Bianca Maubach
New Business Project Manager
P. O. Box 711 (OH 204)
Tucson, AZ 85702
520-307-3864

Should you have any technical questions, please contact the area Designer Martin Rodriguez, at (520) 991-5495

Sincerely,
Conor Mahoney, Office Support Assistant
Design/Build
12/17/2020 SBEASLE1 COT NON-DSD PARKS & RECREATION Approved 12/17/20
The Tucson Parks and Recreation Department has no issues or concerns regarding this development as shown on the submitted plans.

Howard B. Dutt, RLA
Landscape Architect
Tucson Parks and Recreation
(520) 837-8040
12/23/2020 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

4.1 Identification and Descriptive Data

All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

The Development Package will contain the following identification in the lower right corner of each sheet:

Any other relevant case number for reviews or modifications that affect the site.

Add case number and DP20-0240 on each sheet.

Indicate graphically, where possible, compliance with conditions of PAD-15 document.

Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.

Additional comment may apply
12/24/2020 SBEASLE1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Reqs Change December 24, 2020

RE: DP20-0240 / Site/Grading/SWPPP - Springhill Suites, new hotel, 1st submittal, Received November 27, 2020

Thank you for the opportunity to comment on DP20-0240, Springhill Suites, new hotel; 1st Submittal, a development package application for an approximately 4 acre site, located northwest of the intersection of East Tucson Marketplace Boulevard and South Kino Parkway. The property is zoned Planned Area Development 15 (PAD-15), with the proposed development being a hotel.

This site is within the Tucson International Airport avigation easement requirements and public disclosure area, FAA traffic pattern airspace, and FAA Part 77 airspace.

The Tucson Airport Authority conditionally approves the subject request contingent upon the following conditions of approval, as noted below. These conditions shall be identified in the general notes of the revised development plan.

Conditions of approval:
1. "According to the Federal Aviation Administration (FAA) Notice Criteria Tool, this project area is located in proximity to a navigation facility and could impact navigation signal reception. The applicant shall file FAA Form 7460 with the FAA at least 45 days before construction activities begin unless FAA staff, with the Obstruction Evaluation / Airport Airspace Analysis (OE/AAA), provides the project applicant with written communication that filing FAA Form 7460 is not required. It is highly recommended that the applicant file earlier than 45 days to provide the applicant with sufficient time to respond to any concerns which are identified by the FAA. Any cranes which are used must also be identified with Form 7460. Please file Form 7460 at https://oeaaa.faa.gov/oeaaa/external/portal.jsp"

Although this project does not propose a change in plan designation or zoning the Tucson Airport Authority highly recommends the applicant add the following note into the general notes of the revised development plan. This project is located approximately 3 miles northwest of Tucson International Airport and is within FAA traffic pattern airspace, an area which would be subject to aircraft overflight and noise due to being in close proximity to Tucson International Airport.

The proposed note would provide a means of assuring that future owners and tenants of the property are aware they are in proximity an airport and further assures the continued right of the City of Tucson, Tucson Airport Authority, and all persons lawfully utilizing the Tucson International Airport the right to utilize the airspace above or near the property. This would be accomplished through the property owner recording the Avigation Easement. The Tucson Airport Authority believes the proposed note helps to support the City of Tucson Airport Environs Overlay Zone and supports Plan Tucson - Regional and Global Positioning policy 4 (RG-4).

1. "That prior to the City's approval of any construction permit for a permanent building, the property owner shall record the Avigation Easement which discloses the existence, and operational characteristics of the Tucson International Airport to future owners or tenants of the property and further conveys the right to the public to lawfully use the airspace above the property. The Avigation Easement shall be recorded in a manner with the Pima County recorder which shall document it as having title liability. The content of such documents shall be according to the form and instructions provided.

The current property owner or person authorized to sign on behalf of the current property owner shall complete, sign, and record the Avigation Easement. Please record the Avigation Easement with the Pima County Recorder's Office. Once the Avigation Easement is recorded please send a complete copy of the recorded easement document to Tucson Airport Authority by either email (send to srobidoux@flytucson.com) or to the mailing address provided below.

Scott Robidoux
Senior Airport Planner
Tucson Airport Authority
7250 South Tucson Boulevard
Suite 300
Tucson, AZ 85756"

Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811.

Respectfully,
Scott Robidoux, C.M., Senior Airport Planner
12/28/2020 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved