Permit Review Detail
Review Status: Completed
Review Details: DEV PKG - RESUBMITTAL
Permit Number - DP20-0222
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/15/2021 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 03/26/2021 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | DP20-0222 1) For the new proposed trash enclosure shown access and maneuvering for the service vehicle and trash enclosure should follow details shown in figure 3A. Reference City of Tucson Technical Standards Section 8. Provide Waste stream calculations showing existing/proposed service is sufficient. 2) Expedited review is available once the above comment is addressed. Please email to contact John Van Winkle, P.E. John.VanWinkle@tucsonaz.gov |
| 04/06/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 04/09/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office PROJECT: 4902 E Pima St – Fire Station #7 Addition Development Package (2nd Review) DP20-0222 TRANSMITTAL DATE: April 9, 2021 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06 as well as compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM). Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is October 28, 2021. Previous comment 2. The DDO needs to be approved prior to approval of this DP. If approved provide a general note stating the DDO case number, T21SA00083, date of approval, what was modified, and if applicable any conditions of approval. Also provide the DDO case number adjacent to the title block on all sheets. 2-06.4.7.A.4 - Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses. Demonstrate compliance with use-specific standard 4.9.13.F. which requires a minimum 5 ft screen wall to the south and east. It appears that portions of the site are enclosed with a chain link fence, which does not meet the requirements of a screen wall per UDC Article 7.6.5. It is possible to modify this requirement through a Design Development Option (DDO), which is an administrative process. The DDO request would be for a substitution of materials to include slatted chain link fencing and vegetation in lieu of a solid wall. Contact Mark.Castro@tucsonaz.gov for more information. Additional comments: 2-06.4.9.H.5.a – Per 2018 IBC Chapter 11 Section 1106.5 Van Spaces, for every six of fraction of six accessible parking spaces, at least one shall be a van-accessible parking space. That said Zoning highly recommends, but it is not required, that the existing accessible space be modified to meet the requirements of ICC A117.1-2009 Section 502.2 for a van-accessible space. If you have any questions about this transmittal, please contact me at Elisa.Hamblin@tucsonaz.gov. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 04/20/2021 | SSHIELD1 | LANDSCAPE | REVIEW | Approved | |
| 04/20/2021 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | Email from: COTDSDPermits To: JPrice Tue 4/20/2021 9:30 AM Returned for Corrections PERMIT/ACTIVITY: DP20-0222 DESCRIPTION: SITE - Addition to Fire Station 7, City of Tucson. 4902 E PIMA ST FEE BALANCE: $0 (zero) Thank you for the payment. RESUBMITTAL - FILEDROP https://docs.tucsonaz.gov/Forms/tucsonpermitapp (Select "Existing Application", then the permit number) 1) Comment Response Letter (your response to the reviewer's Requires Change comments) 2) Plan Set (all pages, full set, even if no changes were made) 3) Any other documents requested by review staff Title your 3rd submittal documents according to this example: 3_Comment Response Letter, 01.01.21 SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro (If information is not available, check back later after data transfers to PRO.) - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab - Reviews - click on Review Details - Documents - click on View to the right of each document Thank you. Sharon Beasley Permit Specialist City of Tucson, Planning and Development Services email: COTDSDPermits@TucsonAz.gov (Disregard any automatic reply you might receive) |