Permit Number: DP20-0208
Parcel: 132041330

Address:
3225 E 36TH ST

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP20-0208
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2021 SBEASLE1 START PLANS SUBMITTED Completed
02/18/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The developed pipe length between cleanouts includes the vertical distance from the cleanout rim to the pipe invert and the horizontal distance to the next cleanout. For example, with a cleanout rim elevation of 2523.92' and an invert of 2518.07', the maximum horizontal distance to the next cleanout is approximately 94 feet. [Initial comment: The maximum distance between cleanouts shall be 100-feet, measured along the developed pipe length. Reference: Section 708.1.1, IPC 2018.]

Robert Sherry
email: Robert.Sherry@TucsonAz.gov
03/10/2021 LOREN MAKUS ENGINEERING REVIEW Approved
03/11/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change DATE: March 11, 2021 Returned for Corrections

PERMIT/ACTIVITY: DP20-0208
DESCRIPTION: Site/Grading - Desert Metals, commercial storage building.

FEE BALANCE: $0 (zero) Thank you for the payment.

RESUBMITTAL
Submit the following documents to:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
(Select "Existing Application", then the permit number)
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Title the documents for your 3rd submittal starting with the
submittal number, for example: 3_Plan_Set

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

For all NEW development package submittals on the Filedrop page, select the box: "SITE REVIEW...".

Thank you.

City of Tucson
Attn: Sharon Beasley, Permit Specialist
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov
(Disregard the automatic reply you will receive: "This email account is not...".)