Permit Number: DP20-0208
Parcel: 132041330

Address:
3225 E 36TH ST

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP20-0208
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2020 SBEASLE1 START PLANS SUBMITTED Completed
10/29/2020 GDAURIA1 FIRE REVIEW Completed
11/17/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Note: Tucson Water currently allows a 5/8" water meter to serve a demand of 20 GPM but a ¾" schedule 40 PVC service pipe is limited to 13 GPM with at the pipe manufacturer's recommended maximum water velocity of 8 FPS. Reference: Section 303.2, IPC 2018.
2. The maximum distance between cleanouts shall be 100-feet, measured along the developed pipe length. Reference: Section 708.1.1, IPC 2018.
3. Provide a cleanout immediately prior to entering the right of way. Reference: Pima County Standard Detail RWRD 401.
11/20/2020 SSHIELD1 LANDSCAPE REVIEW Approved
11/20/2020 STEVE SHIELDS ZONING REVIEW Approved
12/30/2020 LOREN MAKUS ENGINEERING REVIEW Reqs Change DP20-0208
1. Revise the drainage to clearly address the whole site. Although the proposed development is on just a small portion of the site, the whole site should be included in the description and site analysis.
2. Provide a discussion of the development timelines for the overall parcel. Since the parcel was recently created by combining parcels, It is unclear when prior development has occurred. If the buildings and pavement were completed after September 1984 retention and detention must address these developments.
3. Provide the waste stream calculation figures. Include the uses for the whole site.
4. Delineate areas of pavement, gravel or other surface treatments throughout the site.
5. The fences shown on the site plan seem to indicate potential use of both Lot 14 and Lot 15 as a single use. Clarify the relationship between the operations on the two sites.
6. Provide blocks or curbs to prevent vehicle overhang from partially blocking the sidewalk from the street to the new modular building.
7. Show how water harvesting is maximized in the project.
12/31/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change DATE: December 31, 2020

RETURNED FOR CORRECTIONS NOTICE
Your Next Steps:
1. Online Payment
2. Resubmittal of updated/corrected documents

IMPORTANT - There's a new Filedrop link for your resubmittal:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application"

FYI - For all NEW development package submittals in the future (not this resubmittal) on the new Filedrop page, select the box: "SITE REVIEW..." so it is routed to correct staff member for quicker processing.

PERMIT/ACTIVITY: DP20-0208
DESCRIPTION: Site/Grading - Desert Metals, commercial storage building.

FEES DUE: $ 1,624.50
Please pay the total fees (or at a minimum, the REVIEW Fees). A payment is required before your next submittal.

ONLINE PAYMENT
https://www.tucsonaz.gov/pdsd/fees

PLEASE READ: If information is not available or amount isn't correct, check back later after data is updated.

(Visa, MC, Discover, American Express, or pay from bank account)
1- Click on: Pay Planning & Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click the blue tab: Continue
5- Under the Pay column, check the boxes you want to pay
6- Click Continue, then enter your credit card info
7- If any issues, try using the browser Internet Explorer

RESUBMITTAL OF UPDATED/CORRECTED DOCUMENTS
Submit documents to NEW FILEDROP:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp

1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Title the documents for your 2nd submittal starting with the
submittal number, for example: 2_Plan_Set

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

Thank you.

City of Tucson
Attn: Sharon Beasley, Permit Specialist
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov