| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/12/2021 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 03/15/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The location of the sanitary building drain as it exits the building is very different from the plumbing design. The plumbing design shows the sanitary drain exiting the building about 3-feet east of and parallel to the grease waste. Coordinate the relative location of the sanitary building drain with the plumbing design. Locating a backwater valve upstream of a grease interceptor could lead to maintenance issues and will not protect the grease interceptor from backwater events. A single backwater valve could be installed downstream of the junction of the grease waste and the sanitary waste lines. Coordinate with the plumbing design or simply note that a backwater valve is required and refer to the plumbing drawings. [Second comment: The sanitary building drain connects with the grease waste drain downstream of the grease interceptor; both need to be protected by a backwater valve. Coordinate the location of the backwater valve with the plumbing design or simply note that a backwater valve is required and refer to the plumbing drawings.] [Initial comment: Provide the rim elevation of the next upstream sanitary manhole and the first-floor elevation. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.] |
| 03/15/2021 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 03/15/2021 | ZELIN CANCHOLA | COT NON-DSD | TRAFFIC | Approved | |
| 03/16/2021 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | DATE: March 16, 2021 Returned for Corrections PERMIT/ACTIVITY: DP20-0184 DESCRIPTION: SITE/GRADING - Salad and Go, drive-thru restaurant. FEE BALANCE: $0 (zero) Thank you for the payment. RESUBMITTAL Submit the following documents to: https://docs.tucsonaz.gov/Forms/tucsonpermitapp (Select "Existing Application", then the permit number) 1) Comment Response Letter (your response to the reviewer's Requires Change comments) 2) Plan Set (all pages, full set, even if no changes were made) 3) Any other documents requested by review staff - Title the documents for your 4th submittal starting with the submittal number, for example: 4_Plan_Set SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro (If information is not available, check back later after data transfers to PRO.) - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab - Reviews - click on Review Details - Documents - click on View to the right of each document For all NEW development package submittals on the Filedrop page, select the box: "SITE REVIEW...". Thank you. City of Tucson Attn: Sharon Beasley, Permit Specialist Planning and Development Services email: COTDSDPermits@TucsonAz.gov (Disregard the automatic reply you will receive: "This email account is not...") |