Permit Review Detail
Review Status: Completed
Review Details: DEV PKG - RESUBMITTAL
Permit Number - DP20-0184
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/20/2021 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 02/04/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The sanitary building drain connects with the grease waste drain downstream of the grease interceptor; both need to be protected by a backwater valve. Coordinate the location of the backwater valve with the plumbing design or simply note that a backwater valve is required and refer to the plumbing drawings. [Initial comment: Provide the rim elevation of the next upstream sanitary manhole and the first-floor elevation. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.] |
| 02/16/2021 | ZELIN CANCHOLA | COT NON-DSD | TRAFFIC | Reqs Change | DP20-0184 February 16, 2021 Zelin Canchola Transportation and Mobilty The plan requires change 1. The dumpster location on site is unacceptable. Too close to driveway, may cause conflict with baking up onto right of way and incoming vehicles from street. A right in right out is required from Country Club driveway due to the proximity of existing left turn lane. A pork chop type of island at the driveway is required. |
| 02/16/2021 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | 1. Please show circulation path to dumpster enclosure as per Technical Standards Manual (TSM) section 7-01.3.3. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |
| 02/18/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/23/2021 | ANDREW CONNOR | LANDSCAPE | REVIEW | Approved | |
| 02/26/2021 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | DATE: February 26, 2021 Returned for Corrections PERMIT/ACTIVITY: DP20-0184 DESCRIPTION: SITE/GRADING - Salad and Go, drive-thru restaurant. FEE BALANCE: $0 (zero) Thank you for the payment. RESUBMITTAL Submit the following documents to: https://docs.tucsonaz.gov/Forms/tucsonpermitapp (Select "Existing Application", then the permit number) 1) Comment Response Letter (your response to the reviewer's Requires Change comments) 2) Plan Set (all pages, full set, even if no changes were made) 3) Any other documents requested by review staff - Title the documents for your 3rd submittal starting with the submittal number, for example: 3_Plan_Set SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro (If information is not available, check back later after data transfers to PRO.) - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab - Reviews - click on Review Details - Documents - click on View to the right of each document For all NEW development package submittals on the new Filedrop page, select the box: "SITE REVIEW..." for quicker processing. Thank you. City of Tucson Attn: Sharon Beasley, Permit Specialist Planning and Development Services email: COTDSDPermits@TucsonAz.gov |