| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/16/2020 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 09/29/2020 | GDAURIA1 | FIRE | REVIEW | Reqs Change | * A hydrant is required within 600' of any exterior portion of the building. * A hydrant must be located within 100' of the FDC (can be the same hydrant). |
| 10/14/2020 | ANDREW CONNOR | LANDSCAPE | REVIEW | Reqs Change | ADMINISTRATIVE MANUAL 4.1 Identification and Descriptive Data All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan. The Development Package will contain the following identification in the lower right corner of each sheet: Any relevant case numbers for reviews or modifications that affect the site. Provide Case # DP20-0183 on each sheet. Ensure that Zoning comments are addressed prior to landscape section approval. Additional comments may apply |
| 10/14/2020 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Steve Shields Section Manager PROJECT: Development Package (1st Review) DP20-0183 TRANSMITTAL DATE: October 14, 2020 DUE DATE: October 14, 2020 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM). Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is September 15, 2021. CONTENT REQUIREMENTS 1. 2-06.4.3 – Provide the development package case number, DP20-0183 and case number T20SA00251, adjacent to the title block on all sheets. 2-06.4.7 - General Notes The following general notes are required. Additional notes specific to each plan are required where applicable. 2-06.4.7.A - Zoning and Land Use Notes 2. 2-06.4.7.A.4 – For the existing and proposed uses provide the Use Specific Standards as listed on TABLE 4.8-4: PERMITTED USES - COMMERCIAL AND MIXED USE ZONES, Retail Trade Use Group With Land Use Class/Type: Medical Marijuana Dispensary 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes. 3. 2-06.4.9.H.2 – As the existing curb along Benson Hwy is not at future location show the future curb and sidewalk and provide future SVTs on the plan. 4. 2-06.4.9.H.5 – Dimension the radius on both backup spurs, see UDC Article 7.4.6.F.4. 5. 2-06.4.9.H.5.d – Provide details for both the short – and long – term bicycle parking. These details need to demonstrate compliance with UDC Articles 7.4.9.B.1, .2, 7.4.9.C & 7.4.9.D. 6. 2-06.4.9.O – The street perimeter yard setback listed under “PROJECT DATA” is not correct. Based on the Definition of Established Area Setback this site is considered Developing Area. Per UDC Article 6.4.5.C.2, Table 6.4.5C-1 the required street perimeter yard setback is 21’ or the height of the proposed exterior building wall, greater of the two measured from the back of future curb along Benson Hwy. Provide setback dimensions on the plan. 7. 2-06.4.9.Q – Provide the square footage, height and the specific use proposed within the footprint of the building on the plan. 8. 2-06.4.9.R – Provide a width dimension for the sidewalk that runs out to Benson Hwy. 9. Revise Zoning & Land Use Note 14 to reflect the 2018 IBC and ICC A117.1-2009. If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 10/20/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 10/27/2020 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | 1. Provide on plans waste stream calculations per City of Tucson (COT) Technical Standards Manual (TSM) section 8-01.8.0 2. Show on plans roof drain locations, And ensure that the roof drains scupper underneath sidewalks as needed. Reference COT Technical Standards Manual (TSM) section 7-01.4.1.e. Stephen Blood stephen.blood@tucsonaz.gov |
| 10/28/2020 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | DATE: Oct. 28, 2020 RETURNED FOR CORRECTIONS NOTICE Your Next Steps: 1. Payment 2. Resubmittal of your updated/corrected documents IMPORTANT: On the Filedrop page, select the box: "Site Review/CDRC..." when sending your next submittal. DESCRIPTION: SITE/GRADING/SWPPP - Earth's Healing. PERMIT/ACTIVITY: DP20-0183 FEES DUE: $ 2,472.35 Please pay the total fees (or at a minimum, the REVIEW Fees). A payment is required before your next submittal. ONLINE PAYMENTS **Allow 1-2 days for correct amount to show** https://www.tucsonaz.gov/pdsd/fees (Visa, MC, Discover, American Express or pay from checking account) 1- Click on: Pay Planning & Permit Fees 2- Enter your Permit Nbr, example: dp20-0000 (not case-sensitive but a hyphen-dash- is needed) 3- Business/Individual Name: Leave blank 4- Click the blue tab: Continue 5- Under the Pay column, check the boxes you want to pay 6- Click Continue, then enter your credit card info 7- If any issues, try using the browser Internet Explorer SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro (If information is not available, check back later after data transfers to PRO.) - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab - Reviews - click on Review Details - Documents - click on View to the right of each document YOUR NEXT STEP: Submit documents to the Filedrop https://www.tucsonaz.gov/pdsd-filedrop 1) Comment Response Letter (your response to the reviewer's Requires Change comments) 2) Plan Set (all pages, full set, even if no changes were made) 3) Any other documents requested by review staff - Name the 2nd submittal documents starting with the submittal number, for example: 2_Plan_Set IMPORTANT: On the Filedrop page, select the box: "Site Review/CDRC..." when sending your next submittal. Thank you. Sharon Beasley, Permit Specialist City of Tucson Planning and Development Services email: COTDSDPermits@TucsonAz.gov |