Permit Number: DP20-0173
Parcel: 14042022A

Address:
2830 E MEDINA RD

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - DP20-0173
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2022 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: TAC2 – New Shell Building
Development Package (2nd Review - Revision #1)
DP20-0173

TRANSMITTAL DATE: June 10, 2022

DUE DATE: July 01, 2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is September 14, 2021.

CONTENT REQUIREMENTS

1. This comment was not fully addressed. The required case number was not provided on sheets 78-95. COMMENT: 2-06.4.3 – Remove the DP21-0322 reference on sheets 55-95 and provide the correct DP20-0173 on the plans.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

2. Until S22-019 is approved Zoning cannot approve this DP. Also provide the land split case number S22-019 shall be provided adjacent to the title block on each sheet. COMMENT: 2-06.4.9.A – As it appears that a lot line reconfiguration is proposed the reconfiguration process must be completed prior to approval of this DP. The reconfiguration can be used to combine all existing parcels. Contact Elisa Hamblin for direction on how to complete this process.

3. COMMENT: 2-06.4.9.A – Sheet 2 Site Plan Keynotes #4 you state “EXISTING PARKING LOT TO BE REMOVED AND RELOCATED TO EXISTING PROPERTY TO THE SOUTH- UNDER SEPARATE PERMIT”. A separate development package meeting the requirements of AM 2-06 will need to be submitted and approved for the relocation of the vehicle parking prior to approval of this plan.

If you have any questions about this transmittal, please contact Nicholas Ross at Nicholas.Ross@tucsonaz.gov.

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
06/21/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
07/11/2022 AWARNER1 LANDSCAPE REVIEW Reqs Change CDRC TRANSMITTAL
TO: Planning and Development Services Department, Plans Coordination
FROM: Anne Warner, RLA
PDSD Landscape/Native Plant Preservation Section

PROJECT: Tucson Airport Center
ACTIVITY NO: DP20-0173, REV 1.2
Address: 2830 E Medina
Zoning: I-1
Existing Use: undisturbed Sonoran Desert
Proposed Use: Warehouse

TRANSMITTAL DATE: July 11, 2022
DUE DATE: July 1, 2022
COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Landscape Review Section comments were addressed.
This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting.

1. This comment was not adequately addressed - Please distinguish between the mitigation/salvage plants and the other required plants on the legend, symbol or any other method that would communicate the information. Please sort the plant inventory by species rather than tag number and provide a summary of total inventoried vs. viable plants.

2. This comment was not adequately addressed - Identify the point of drainage off roof areas, amount of flow, and disposition of flow. UDC section 7.6.6.C requires the use of all runoff to supplement irrigation. Show how this is attained. Also, it is not clear on either of the grading plans or the water harvesting plan for Bldg. A how rainwater is getting to the landscape areas.



RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package

YOUR NEXT STEPS: Submit documents to the Filedrop
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application"
1) Comment Response Letter (your response to
the reviewer's Requires changes comments)
2) Plan Set (or individual sheets)
3) Any other items requested by review staff
07/14/2022 JPEELDA1 FIRE REVIEW Approved
07/14/2022 LOREN MAKUS ENGINEERING REVIEW Approved
07/15/2022 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change email from: COTDSDPermits
To: Jennifer K.
Fri 7/15/2022 10:40 AM

REVISION REVIEW NOTICE
Revision returned for corrections, DP20-0173

Project Description: SITE/GRADING/SWPPP - Tucson Airport Center (TAC 2), new shell building, phases one and two. 6818 S COUNTRY CLUB RD

REVISION FEES DUE: $ 2,033.13
Please pay fees before sending in a resubmittal

ONLINE PAYMENTS
https://www.tucsonaz.gov/pdsd/fees
** If the online amount doesn't match "Revision Fees Due" shown above, check back in a few hours after it is updated **
1- Click on: Pay Planning & Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click the blue tab: Continue
5-Under the Pay column, check the boxes you want to pay
6- Click Continue, then enter your credit card info

VIEW the review comments and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

YOUR NEXT STEPS: Submit documents to the Filedrop
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application"

1) Comment Response Letter (your response to the reviewer's Requires changes comments)
2) Plan Set (or individual sheets)
3) Any other items/documents requested by review staff


Sharon Beasley, Certified Permit Technician

City of Tucson, Planning & Development Services Dept.