Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP20-0173
Parcel: 14042022A

Address:
2830 E MEDINA RD

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP20-0173
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP can't be approved until the TSMR is approved and issued.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
01/21/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change DATE: January 21, 2021

Returned for Corrections / Request for Resubmittal

PERMIT/ACTIVITY: DP20-0173

DESCRIPTION: SITE/GRADING/SWPPP - Tucson Airport Center (TAC 2), new shell building.
6818 S COUNTRY CLUB RD

FEE BALANCE: $0 (zero) Thank you for the payment.

RESUBMITTAL OF UPDATED/CORRECTED DOCUMENTS
Submit documents to NEW FILEDROP:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application", then the permit number

1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Title the documents for your 3rd submittal starting with the
submittal number, for example: 3_Plan_Set

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

FYI - For all NEW development package submittals in the future (not resubmittals) on the Filedrop page, select the box: "SITE REVIEW...".

Thank you.

City of Tucson
Attn: Sharon Beasley, Permit Specialist
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov
11/13/2020 SBEASLE1 START PLANS SUBMITTED Completed
11/27/2020 GDAURIA1 FIRE REVIEW Completed
12/01/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Utility note #12 on sheet C2.0 is OK but utility plans C2.2 and C2.3 still show 100' between cleanouts, not a developed length of 100' between cleanouts. [Initial comment: Clarify the cleanout locations for the building sewer. Provide cleanouts in the building sewer at intervals not exceeding 100 feet measured from the cleanout rim, along the developed pipe length to the next drainage fitting providing access for cleaning. Reference Section 708.1.2, IPC 2018.]
2. The engineer's seal not signed or dated. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that in addition to signing the seal, the registrant shall include the date the document was sealed
12/10/2020 ANDREW CONNOR LANDSCAPE REVIEW Approved
12/31/2020 STEVE SHIELDS ZONING REVIEW Approved