Permit Number: DP20-0167
Parcel: 141366940

Address:
6601 E BENSON HY

Review Status: Completed

Review Details: GRADING

Permit Number - DP20-0167
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2020 ANDREW CONNOR NPPO REVIEW Reqs Change ADMINISTRATIVE MANUAL

The development package will contain the following identification in the lower right corner of each sheet:

Any relevant case numbers for reviews or modifications that affect the site.

Provide Case # DP20-0167 on each sheet.

Indicate graphically, where possible, compliance with conditions of PAD-7 document.

Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.


Additional comments may apply
10/13/2020 NMARTEL1 ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Nicholas Martell; Planner

PROJECT:
Development Package (1st Review)
DP20-0167

TRANSMITTAL DATE: 10/12/20

DUE DATE: 10/12/20

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is August 21, 2021.


1. 2-06.3.4 - A title block shall be provided in the lower right quadrant of each sheet.

Comment: Provide consistent title blocks and numbering on every page of the development package.


2. 2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

Comment: Provide the Development Package number DP20-0167 adjacent to the title block on each sheet.


3. 2-06.4.7.A.6.b - If there is more than one lot within the site, the note should specify which lots are affected by the additional applications or overlay zones.

Comment: Specify which lots are affected by the additional applications or overlay zone

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.


4. 2-06.4.8.B - All easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. Blanket easements should be listed in the notes, together with recordation data and their proposed status. Should an easement not be in use and be proposed for vacation or have been abandoned, so indicate. However, should the easement be in conflict with any proposed building location, vacation of the easement shall occur prior to approval of plan unless written permission from easement holder(s) is provided.

Verify all existing easements are in the plans.

5. 2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.

Verify all existing or proposed easements are illustrated and aligned with DP19-0313 and S19-012





If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
10/20/2020 SBLOOD1 ENGINEERING REVIEW Reqs Change 1. Note: *Basin Table on sheet 03, sheet 3 doesn’t have a basin table. Please update plans as needed

2. Page Numbers aren’t adding up and sheet index doesn’t correspond. Please update

3. Sections on page 21 of 43 don’t seem to correspond to anything in the plan set. Please clarify where these sections apply

Stephen Blood
stephen.blood@tucsonaz.gov
10/22/2020 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change DATE: Oct. 22, 2020

RETURNED FOR CORRECTIONS NOTICE
Your Next Steps: Resubmittal of your updated/corrected documents

IMPORTANT: On the Filedrop page, select the box: "Site Review/CDRC..." when sending your next submittal.

DESCRIPTION: GRADING - La Estancia, Phase 2, Parcel 1. Lots 1-193 and common areas A-1 through J-1.

PERMIT/ACTIVITY: DP20-0167
FEE BALANCE: $0 (zero) Thank you for the payment.

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

YOUR NEXT STEP:
Submit documents to the Filedrop
https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Name the 2nd submittal documents starting with the
submittal number, for example: 2_Plan_Set

IMPORTANT: On the Filedrop page, select the box: "Site Review/CDRC..." when sending your next submittal.

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov