Permit Number: DP20-0160
Parcel: 12205046A

Address:
2102 N RALPH AV

Review Status: Completed

Review Details: TENTATIVE PLAT REVIEW

Permit Number - DP20-0160
Review Name: TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2020 SBEASLE1 START PLANS SUBMITTED Completed
08/12/2020 SBEASLE1 UTILITIES SOUTHWEST GAS Passed
08/12/2020 SBEASLE1 OTHER AGENCIES U. S. POST OFFICE Passed
08/12/2020 SBEASLE1 OTHER AGENCIES PIMA ASSN OF GOVTS Passed
08/17/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/18/2020 GDAURIA1 COT NON-DSD FIRE Completed
09/07/2020 SBEASLE1 COT NON-DSD PARKS & RECREATION Approved No existing or proposed Tucson Parks and Recreation facilities are affected by this development.

Howard B. Dutt, RLA, Landscape Architect
Tucson Parks and Recreation
(520) 837-8040
09/09/2020 SBEASLE1 UTILITIES TUCSON ELECTRIC POWER Approved Tucson Electric Power Co., (TEP) has reviewed and approves the Tentative Plat submitted on August 12, 2020. A preliminary electrical drawing for these lots is in progress. A final construction drawing will be prepared with approval of the preliminary drawing and a copy of the Approved Tentative Plat. Easements for TEP facilities will be required to be shown on the Final Plat in order for TEP to approve the plat.

If there are any questions, please contact me at 520-401-9895.

Thank you,
Mary Burke, Senior Right of Way Agent
Tucson Electric Power Co.
Cell - 520-401-9895
mburke@tep.com
09/09/2020 SBEASLE1 PIMA COUNTY ADDRESSING Reqs Change (The “ATTACHED PDF” mentioned below can be viewed online: www.TucsonAz.gov/Pro. See the Documents section.)

Ralph LLC, DP20-0160, 1st submittal, is being Returned for Corrections by Pima County Addressing. The attached pdf contains Addressing’s comments.

Please let me know if you have any questions.
Thank you,
Robin Freiman, Addressing Official

Pima County Development Services Department
(520) 724-7570
09/09/2020 ZELIN CANCHOLA COT NON-DSD TRAFFIC Reqs Change September 9, 2020
ACTIVITY NUMBER: DP20-0160
PROJECT NAME: Tentative Plat
PROJECT ADDRESS: 2102 N Ralph Av
PROJECT REVIEWER: Zelin Canchola Transportation and Mobility

Resubmittal Required: The following items must be revised and added to the Development plan.


1. Offsite improvements are not shown. Show new 5 feet sidewalk along frontage of Ralph Av and Senica St

2. Close any unused driveway curb cuts. Show on plan.

3. Show elevations for new driveways and sidewalk for work in the right of way.

4. Show driveway standard detail PAG Standard detail 206.

If you have any questions, I can be reached at 520 837 6659 or zelin.canchola@tucsonaz.gov
09/10/2020 ANDREW CONNOR ZONING REVIEW Reqs Change ADMINISTRATIVE MANUAL

The development package will contain the following identification in the lower right corner of each sheet:

Any relevant case numbers for reviews or modifications that affect the site.

Provide Case # DP20-0160 on each sheet.
.
Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.

Additional comments may apply
09/11/2020 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL


4.1 Identification and Descriptive Data


The development package will contain the following identification in the lower right corner of each sheet:

Any relevant case numbers for reviews or modifications that affect the site.

Provide Case # DP20-0160 on each sheet.
.
Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.


Additional comments may apply
09/25/2020 SBLOOD1 ENGINEERING REVIEW Reqs Change 1. Add required note from Administrative Manual section 2-06.4.7.C.2 "No structure or vegetation shall be located or maintained so as to interfere with the sight visibility triangles in accordance with Section 10-01.5.0, Sight Visibility, of the Technical Standards Manual."
2. Show on plan sight visibility triangles
3. Update legend to show found and set survey monumentation
4. Need to show and label curb cuts on both E. Seneca St and N. Ralph Ave.
5. Need to show and label (2) 8'X9' Box culverts in both Seneca and Ralph
6. Provide information stated in Administrative manual 2-06.4.8.I and show on plans
7. Clarify extent of grading for this project
8. Show on plans a minimum 5' wide sidewalk along E Seneca St and N Ralph Ave Reference TSM section 10-01.4.1.A.1.a.
9. Show dimension for new proposed driveway aprons
10. Clarify on page 1 of Drainage Statement - Base Flood Elevation doesn't match between elevation certificate
11. Expand the Drainage Statement to show how adequate site drainage will be maintained and show pre vs proposed drainage patterns. Also how the BFE was determined
12. Clarify if site walls will be constructed as part of this project and if not provide a statement saying "will require a separate FUP"

Stephen Blood
stephen.blood@tucsonaz.gov
09/25/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change DATE: Sept. 25, 2020

RETURNED FOR CORRECTIONS NOTICE
Your Next Steps: 1. Payment 2. Resubmittal of your updated/corrected documents

DESCRIPTION: TENTATIVE PLAT/FLOODPLAIN - Ralph LLC, Lots 1-3, residential.

PERMIT/ACTIVITY: DP20-0160

FEES DUE: $ 1,481.50
Please pay the total fees (or at a minimum, the REVIEW Fees).
A payment is required before your next submittal.

ONLINE PAYMENTS **Allow 1-2 days for correct amount to show**
https://www.tucsonaz.gov/pdsd/fees
(Visa, MC, Discover, American Express or pay from checking account)
1- Click on: Pay Planning & Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click the blue tab: Continue
5- Under the Pay column, check the boxes you want to pay
6- Click Continue, then enter your credit card info
7- If any issues, try using the browser Internet Explorer

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

YOUR NEXT STEP:
Submit documents to the Filedrop
https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Name the 2nd submittal documents starting with the
submittal number, for example: 2_Plan_Set

IMPORTANT:
On the Filedrop page, select the box: "Site Review/CDRC..."

Thank you.