Permit Number: DP20-0153
Parcel: 122173090

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - DP20-0153
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2021 SBEASLE1 ZONING REVIEW Approved Approved by Elisa Hamblin during the recent OK to Submit, 09/22/21.
10/11/2021 SBEASLE1 ENGINEERING REVIEW Approved Approved by Loren Makus during the recent OK to Submit, 10/08/21.
10/25/2021 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change Email from: COTDSDPermits
To: Erin Harris
Mon 10/25/2021 1:02 PM

REVISION PLAN
Returned for corrections: DP20-0153

DESCRIPTION: SITE/GRADING - Cornerstone Homes on Bellevue, multi-family, 26 units. 3139 E BELLEVUE ST

REVISION FEES DUE: $ 264.00

ONLINE PAYMENTS
https://www.tucsonaz.gov/pdsd/fees
If amount doesn't match "Fees Due", check back in a few hours after it is updated.
1- Click on: Pay Planning & Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click the blue tab: Continue
5-Under the Pay column, check the boxes you want to pay
6- Click Continue, then enter your credit card info

VIEW the review comments and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

YOUR NEXT STEPS: Submit documents to the Filedrop
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application"

1) Comment Response Letter (your response to
the reviewer's Requires changes comments)
2) Plan Set (or individual sheets)
3) Any other items requested by review staff

Thank you.
Sharon Beasley, Building Permit Specialist

City of Tucson, Planning and Development Services
Email: COTDSDpermits@TucsonAz.gov
(disregard the email response that will be sent automatically)
10/25/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change An approved two-way cleanout fitting is a listed single fitting and is located at the junction of the building drain and the building sewer. The junction of the building sewer is defined as being 30-inches in developed length beyond the exterior wall of a structure. To my knowledge, no two-way cleanout fitting is manufactured for use at a 90-degree, or 45-degree junction as shown for building #1 and CO#3 for building #2. Additionally, nothing in the plumbing code requires the installation of a two-way cleanout. Reference: Sections 202, 708.1.3, and 708.1.8, IPC 2018.