Permit Number: DP20-0148
Parcel: 117170050

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP20-0148
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2020 SBEASLE1 START PLANS SUBMITTED Completed
09/24/2020 NICHOLAS ROSS ZONING REVIEW Approved
09/24/2020 NROSS1 DESIGN PROFESSIONAL REVIEW Approved
10/05/2020 ANDREW CONNOR LANDSCAPE REVIEW Approved
10/07/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/09/2020 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP20-0148

1) Previous Comment 1. This comment was partially addressed. Capacity of proposed pumps is shown, however no information about the volume of water the pumps will be required to handle, or if the drain system can function adequately with a clogging factor of 2
2) Previous Comment 7. This comment was not addressed. The area being drained by the sump is a detention basin. Please add notes a,b,c and d found in paragraph 2 in section 14.3 of the standards manual for drainage design.

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
10/12/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change DATE: Oct. 12, 2020

RETURNED FOR CORRECTIONS NOTICE
Your Next Steps: Resubmittal of your updated/corrected documents

IMPORTANT: On the Filedrop page, select the box: "Site Review/CDRC..." when sending your next submittal.

DESCRIPTION: SITE/GRADING - 124 East Broadway Blvd

PERMIT/ACTIVITY: DP20-0148

FEE BALANCE: $0 (zero) Thank you for the payment.

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

YOUR NEXT STEP:
Submit documents to the Filedrop
https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Name the 3rd submittal documents starting with the
submittal number, for example: 3_Plan_Set

IMPORTANT: On the Filedrop page, select the box: "Site Review/CDRC..." when sending your next submittal.

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov
10/12/2020 SBEASLE1 ENV SVCS REVIEW Reqs Change 10/12/20

Provide a detail of trash room area to include all dimensions, wall protection, and door/gate opening where containers are to be rolled out/in from to Arizona Ave. Must demonstrate sufficient area to support two 4yd containers and maneuver out/in from/to building.

Thanks.
Andy Vera
City of Tucson -Environmental Services
Accounts Representative Supervisor
(520) 837-3798
email: Andy.Vera@TucsonAz.gov
10/13/2020 SBEASLE1 COT NON-DSD REAL ESTATE Approved 10/07/20
The applicant has submitted an application for a new Temporary Revocable Easement for the new patio that will encroach into the City's right of way. RES 2021-040

Should any ground or aerial encroachments into City right-of-way come to be included, applicant is requested to contact the Real Estate Division to apply for easements. Any development in public streets that cannot be addressed by a PIA should be directed to Real Estate as well.

Michael Hollar, Senior Property Agent

Real Estate Division
Department of Transportation & Mobility
Main 520-791-4181, Direct 520-837-6784