Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: DP20-0138
Parcel: 13316037K

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP20-0138
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2020 SBEASLE1 START PLANS SUBMITTED Completed
07/09/2020 SBEASLE1 ENGINEERING REVIEW Reqs Change (Reviewed during the OK to Submit)

1. Clarify the nature of the proposed work. The plan shows the drive thru as existing. The previously approved plans do not show the drive thru.

2. Show the proposed window location and stacking.

Loren Makus
Loren.Makus@TucsonAz.gov
07/09/2020 SBEASLE1 ZONING REVIEW Reqs Change (Reviewed during the OK to Submit).

CDRC TRANSMITTAL
TO: Development Services Department Plans Coordination Office FROM: Steve Shields, Site Section Manager
PROJECT: Nico's @ 6540 E Tanque Verde Rd - Drive-Thru Addition
Development Package (1st Review), DP20-0138

TRANSMITTAL DATE: July 8, 2020
DUE DATE: OK to Submit

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

The review comments include the applicable Administrative Manual section number and the following paragraph is the actual comment related to the specific item that must be addressed. If you need to review the sections listed below click on the link or copy it in the address bar of your internet program. http://www.amlegal.com/nxt/gateway.dll/Arizona/tucson_az_udc/administrativemanual?f=templates$fn=default.htm$3.0$vid=amlegal:tucson_udc_az

This link will take you directly to the section used for the standards review. The UDC & TSM requirements are in the Unified Development Code and can be viewed at the same web link as above

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is June 08, 2021.

2-06.3.0 FORMAT REQUIREMENTS

1. 2-06.3.2 - All mapped data shall be drawn at an engineering scale, provide the scale of the drawing.

2. 2-06.3.8 - Provide a north arrow on the plan.

2-06.4.0 CONTENT REQUIREMENTS

3. 2-06.4.1 - Provide the email addresses, and phone number of the primary property owner of the site

4. 2-06.4.3 - Provide the Development Package case number, DP20-0138, adjacent to the title block on all sheets.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

5. 2-06.4.7.A.6.a - Provide a general note on the cover sheet stating "THIS PROJECT IS DESIGNED TO MEET THE OVERLAY ZONE(S) CRITERIA, UDC ARTICLE 5.4 MAJOR STREETS AND ROUTES SETBACK ZONE (MS&R)."

2-06.4.7.A.8 - For development package documents provide:

6. 2-06.4.7.A.8.a - Clarify why the total square footage listed in the Parking Calculation on you plan is different from the total square footage listed on the cover sheet of T17CM07169.

7. 2-06.4.7.A.8.b - Remove the Lot Coverage calculation as it is not applicable, see UDC TABLE 6.3-4.A: DIMENSIONAL STANDARDS FOR THE C-1, C-2, C-3, OCR-1, & OCR-2 ZONES.

8. 2-06.4.7.A.8.c - Remove the building expansion calculation from the plan as it is not applicable.

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

9. 2-06.4.8.A - Provide site boundary information, including bearing in degrees, minutes, and seconds, together with distances in feet, to hundredths of a foot, or other functional reference system.

10. 2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

11. 2-06.4.9.F - All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined.

12. 2-06.4.9.H.5 - You list the drive thru as "EXIST." when appears that it is new. Based on current Google and Aerial photos there is curbing at the north end and fencing at the south.

13. 2-06.4.9.H.5 - Provide a width dimension for the proposed drive-thru.

14. 2-06.4.9.H.5 - Show the required 1' setback to the building to the east of the drive-thru and to the fence to the west of the drive-thru, see UDC Article 7.4.6.F.2.a.(2).

If you can provide an approved site plan showing the drive-thru the above 3 comments would not apply.

15. 2-06.4.9.H.5.a - As it appears that you are using the Shopping Center allowance for your required vehicle parking spaces you must demonstrate that you are meeting the definition of a Shopping Center, see UDC Article 11.3.9.C.3.

If you have any questions about this transmittal, please contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
07/13/2020 GDAURIA1 FIRE REVIEW Completed
07/13/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change RETURNED FOR CORRECTIONS NOTICE
Your Next Step: Resubmittal of documents

DESCRIPTION: SITE - Nico's Mexican Food, tenant improvement.
PERMIT/ACTIVITY: DP20-0138
FEE BALANCE: $0 (zero) Thank you for the payment.

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on blue icon to the right of each document

YOUR NEXT STEP:
Submit documents to the Filedrop
https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Name the 2nd submittal documents starting with the
submittal number, for example: 2_Plan_Set

FOR FASTER PROCESSING:
When on the Filedrop page, select the box
"Development Package or Land Division". This applies to all
DP submittals, DP resubmittals, and DP revisions - and all Land Splits.
(For Building Permits, continue to select "Resubmittals/Revisions...".)

Thank you.

Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/13/2020 SBEASLE1 OUT TO CUSTOMER Completed