Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP20-0116
Parcel: 14029051C

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP20-0116
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2020 SBEASLE1 START PLANS SUBMITTED Completed
11/05/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The revised plans show that the rim elevation of the next upstream sanitary manhole (3629-02, 2613.6') is less than 12" below the first floor elevation (2614.5'). Provide a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson. Verify that no fixtures located above the rim elevation of the next upstream manhole discharge through the backwater valve
11/06/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change DATE: November 6, 2020

RETURNED FOR CORRECTIONS NOTICE
Your Next Steps: Resubmittal of your updated/corrected documents

IMPORTANT: On the Filedrop page, select the box: "Site Review/CDRC..." when sending your next submittal.

DESCRIPTION: Site/Grading/SWPPP - Hemisphere Loop Spec Building.

PERMIT/ACTIVITY: DP20-0116
FEE BALANCE: $0 (zero) Thank you for the payment.

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

YOUR NEXT STEP:
Submit documents to the Filedrop
https://www.tucsonaz.gov/pdsd-filedrop
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Title the documents for your 4th submittal starting with the
submittal number, for example: 4_Plan_Set

IMPORTANT: On the Filedrop page, select the box: "Site Review/CDRC..." when sending your next submittal.

HOLIDAY:
All City of Tucson offices (except for emergency services) will be closed on
Wednesday, November 11, for Veterans Day.


City of Tucson
Attn: Sharon Beasley, Permit Specialist
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov