Permit Number: DP20-0093
Parcel: 14010029A

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP20-0093
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2020 SBEASLE1 START PLANS SUBMITTED Completed
08/11/2020 GDAURIA1 FIRE REVIEW Reqs Change * Additional hydrant required at SW entry ot property.
* Clearly show all hydrants on DP
08/17/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/28/2020 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Site Section Manager

PROJECT: Door Church - Worship Center Addition
Development Package (2nd Review)
DP20-0093

TRANSMITTAL DATE: August 28, 2020

DUE DATE: August 31, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is May 01, 2021.

CONTENT REQUIREMENTS

1. This comment was not fully addressed. The case number was not provided on sheets 7-10. 2-06.4.3 - Provide the development package case number, DP20-0093, adjacent to the title block on each sheet.

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

2. 2-06.4.8.B - There is an existing "10' SEWER EASEMENT" shown running under the proposed building. This easement will need to be abandoned prior to approval of the DP.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

3. This comment was not fully corrected. The calculation shows "REQUIRED = 9, PROVDIED = 12 (13 + 2 VAN ACCESSIBLE). If it is 13 + 2 it should be 15 total but only 12 are provided. 2-06.4.9.H.5.a - The accessible vehicle parking space calculation is not correct. Per 2018 IBC Chapter 11 Table 1106.1 401 to 500 only requires 9 spaces. Also based on 15 accessible space provided 3 must be van accessible.

4. 2-06.4.9.H.5.d - Detail 2 sheet C-5 provide a dimension from the rack to the building to the north. This dimension must me 2'-6", see UDC Article 7.4.9.B2.g.

5. This comment was not fully addressed. The street perimeter yard setback for both Irvington and Country Club is 21' or the Height of the exterior wall, greater of the two, measured from the back of future curb. Revise General Not 4. 2-06.4.9.O - The street perimeter yard setbacks shown under General Note 4.C are not correct. Per UDC Article 11.4.6 definition of Established Area Setback streets designated as a major street to not qualify for established area setbacks. Per UDC Article 6.4.5.C.2 and Table 6.4.5.C-1 the required street perimeter yard for a street with an ADT of 1,000 or greater is 21' or the height of the proposed exterior building wall, greater of the two, measured from the back of future curb.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
08/28/2020 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS

4.1 Identification and Descriptive Data

A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

The development package will contain the following identification in the lower right corner of each sheet:

Any relevant case numbers for reviews or modifications that affect the site.

Provide Case # DP20-0093 on each sheet.

Remove the word Preliminary from Landscape Plans.

It doesn't appear that the following comments were addressed. Please submit a separate landscape response letter.

7.6.4. LANDSCAPE STANDARDS

Oasis Allowance
An oasis is an area where non-drought tolerant landscaping designs are permitted. Plants not listed on the Arizona Department of Water Resource's Low Water Use/Drought Tolerant Plant List may be used in an oasis if the plants are grouped in separately programmed irrigation areas according to their water requirements. The location and maximum area on a site that may be used for oasis areas, including those located in a street landscape border, is determined as follows.
(2) All Other Uses
Equal to, but not more than, 2.5% of the site.
(3) Locational Standards
The following factors should be considered when determining the location of the oasis area.
(a) Providing optimum exposure for site users by selecting areas near main buildings, pedestrian facilities, and active use areas; and,
(b) Selecting areas that incorporate outdoor seating or assembly spaces.
Provide Oasis calculation for Turf area

Located on Site

Street landscape borders must be located entirely on site, except that, if approved by the City Engineer or designee, up to five feet of the required ten foot width may be placed within the adjacent right-of-way area or within the Major Streets and Routes (MS&R) right-of-way area on MS&R streets.
Portions of the landscape area have more than 5' in ROW along Irvington Rd. Revise paln as necessary or obtain a variance to reduce street landscape area width.

Use of the Public Right-of-Way

Nonrequired landscaping may be placed in the public right-of-way, if the following standards are met:
1. The landscaping is approved by the City Engineer or designee and complies with the City Engineer's standards on construction, irrigation, location, and plant type;
2. All vegetation complies with the standards of Section 7.6.4, Landscaping Standards; and,
3. The landscaping does not interfere with the use of the sidewalk.

Obtain permission for use of ROW for non-required landscaping.

The landscape plan shall include the following:
Irrigation Plan
1. Type of water conserving irrigation systems proposed and differentiation between systems for the different water use zones on the site;
2. Source of irrigation water;
3. System specifications and system design and layout (Section 4-01.4.2, Irrigation Standards, of the Technical Standards Manual);
4. Extent of supplementary irrigation in each planting area, provided by water harvesting methods;
5. Point of drainage off roof areas, amount of flow, and disposition of flow;
6. The extent to which systems are proposed within the public right-of-way.

Include irrigation plan with next submittal

Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.

Additional comments may apply
09/17/2020 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. As previously commented, per COT Unified Development Code (UDC) section 7.4.6.H, provide a barrier to prevent vehicles from driving of the proposed drive along the east side of the new building. Clearly show either curb or some other barrier on both sides of the drive.
2. Where spot grades are shown for landscape areas, show grades for surrounding ground or pavement to substantiate depression of the landscape areas.
09/18/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change DATE: Sept. 18, 2020

RETURNED FOR CORRECTIONS NOTICE
Your Next Steps: Resubmittal of your updated/corrected documents

DESCRIPTION: SITE/GRADING - Door Church, worship center addition.

PERMIT/ACTIVITY: DP20-0093

FEES DUE: $ 619.63 (These can be paid at a later date if you choose since they are permit fees,
not review fees.) Thank you for your past payments of review fees.

ONLINE PAYMENTS
https://www.tucsonaz.gov/pdsd/fees
(Visa, MC, Discover, American Express or pay from checking account)
1- Click on: Pay Planning & Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click the blue tab: Continue
5- Under the Pay column, check the boxes you want to pay
6- Click Continue, then enter your credit card info
7- If any issues, try using the browser Internet Explorer

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

YOUR NEXT STEP:
Submit documents to the Filedrop
https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Name the 3rd submittal documents starting with the
submittal number, for example: 3_Plan_Set

IMPORTANT:
On the Filedrop page, select the box: "Site Review/CDRC..."

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
09/18/2020 SBEASLE1 OUT TO CUSTOMER Completed