Permit Number: DP20-0075
Parcel: 14117680A

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP20-0075
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2020 SBEASLE1 START PLANS SUBMITTED Completed
04/27/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/28/2020 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS

4.1 Identification and Descriptive Data

A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

The development package will contain the following identification in the lower right corner of each sheet:

Any relevant case numbers for reviews or modifications that affect the site.

Provide Case # DP20-0075 on each sheet.

Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.


Additional comments may apply
04/29/2020 GDAURIA1 FIRE REVIEW Completed * Fire Sprinklers are a deferred submittal to TFD.
05/04/2020 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Section Manager

PROJECT: ACE Hardware - Building Expansion - 7451 S. Houghton Rd.
Development Package (1st Review)
DP20-0075

TRANSMITTAL DATE: May 4, 2020

DUE DATE: May 6, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is April 07, 2021.

2-06.3.0 FORMAT REQUIREMENTS

1. 2-06.3.9 - The plan drawing shall be oriented with north toward the top of the sheet. If it is not practical to orient north to the top of the sheet, the plan drawing shall be oriented with north to the left side of the sheet.

CONTENT REQUIREMENTS

2. 2-06.4.3 - Provide the development package case number, DP20-0075, adjacent to the title block on all sheets.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

3. 2-06.4.7.A.4 - Revise general note 3 to reflect the correct Use Specific Standards. Per UDC TABLE 4.8-5: PERMITTED USES - INDUSTRIAL ZONES, Retail Trade Land Use Group With Land Use Class/Type: General Merchandise Sales: Excluding Large Retail Establishments, the Use Specific Standards should only be 4.9.13.Q

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

4. 2-06.4.9.H.5 - Per UDC Article 7.4.6.H.1 Barriers, such as post barricades or wheel stop curbing, are required in a vehicular use area to prevent vehicles from extending beyond the property lines, to prevent cars from damaging adjacent landscaping, walls, or buildings, overhanging adjacent sidewalk areas, and/or driving onto unimproved portions of the site. That said some type of barrier is required along the north and south ends of the vehicle parking shown to the of the proposed building and along the east side of the proposed expansion.

5. 2-06.4.9.H.5.d - The 2 bike racks called out under keynote 19 near the northwest corner of the proposed building meet the requirement for 4 bikes where are the other 2/

6. 2-06.4.9.H.5.d - Keynote 20 calls out "NEW LONG-TERM BIKE PARKING AREA IN BUILDING." But there is a keynote 20 near the southwest corner of the existing building that is pointing to what appears to be bike lockers outside the building.

7. 2-06.4.9.H.5.d - The short-term bicycle calculation shows 1 space per 6,000 but it should be 5,000.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
05/04/2020 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Provide dimension for the drive behind the proposed building. Show the width is sufficient for a one-way access route.
2. Show roof drainage patterns. Ensure sidewalks are maintained flood-free for up to a 10-year event.
05/05/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change RETURNED FOR CORRECTIONS NOTICE
Your Next Step: Resubmittal of documents

DESCRIPTION: SITE/GRADING - Ace Hardware, building expansion.

PERMIT/ACTIVITY: DP20-0075
FEE BALANCE: $0 (zero)

SEE REVIEWER'S COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, left side, Activity Search, enter the Activity Number
- Permits section, click on blue tab
- Reviews section, click on Review Details
- Documents section, click on blue icon to the right of each document

YOUR NEXT STEPS: Submit to the Filedrop - https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter (your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Name the 2nd submittal documents starting with the submittal number, for example: 2_Plan_Set

NOTE: The City of Tucson's Permit Counter at 201 N. Stone Avenue (the physical office) is closed to the public until further notice. Our staff is working remotely. All communications are by telephone or email.


CONTACT US Monday-Friday, 8:00 am to 12:00 noon
https://www.tucsonaz.gov/pdsd/virtual-service-counter
To request information or an over-the-counter review,
sign in to the Virtual Service Counter and we will give you a call.

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
05/05/2020 SBEASLE1 OUT TO CUSTOMER Completed