Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP20-0050
Parcel: 13213089A

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP20-0050
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2020 SBEASLE1 START PLANS SUBMITTED Completed
03/10/2020 SBEASLE1 UTILITIES SOUTHWEST GAS Passed Review not required. This agency was notified for their information only.
03/10/2020 SBEASLE1 OTHER AGENCIES PIMA ASSN OF GOVTS Passed Review not required. This agency was notified for their information only.
03/10/2020 SBEASLE1 OTHER AGENCIES U. S. POST OFFICE Passed Review not required. This agency was notified for their information only.
03/25/2020 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Reqs Change Per page 108 of PAD-15, each subsequent developmentplan or subdivision plat shall be brought before the Design Review Committee (DRC) for its formal consideration, together with proposed conceptual building elevations and architectural renderings, sufficient toallow the Committee to judge the proposed Project for conformance with the pertinent adopted design guidelines.
Prior to the submittalof any development plan or subdivision plat to the City of Tucson, the Developer must procure a letter of recommendation from the DRC for submittal to the City. This letter, and a record copy (for the City's archives) of the materials recommended by the DRC,must accompany any City submittal in order to allow review of same by the City of Tucson Planning & Development Services Department.
Provide the letter in a resubmittal.

Alexandra Hines, Lead Planner
Alexandra.Hines@tucsonaz.gov
City of Tucson
03/26/2020 SBEASLE1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Approved March 23, 2020

RE: DP20-0050 Taco Bell at Tucson Marketplace / 1st Submittal, Received March 10, 2020

Thank you for the opportunity to comment on DP20-0050, Taco Bell at Tucson Marketplace; 1st Submittal, a development package application for an approximately 1 acre site, located southeast of the intersection of East Tucson Marketplace Boulevard and South Park Avenue. The property is zoned Planned Area Development 15 (PAD-15), with the proposed development being a commercial use which would contain a restaurant.
This site is within the Tucson International Airport avigation easement requirements and public disclosure area, FAA traffic pattern airspace, and FAA Part 77 airspace.
The Tucson Airport Authority approves the 1st submittal of this project and has no additional comments to provide.

Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811.
Respectfully, Scott Robidoux, Senior Airport Planner
03/31/2020 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
04/01/2020 SBEASLE1 COT NON-DSD PARKS & RECREATION Approved No existing or proposed Tucson Parks and Recreation facilities are affected by this development.

Howard B. Dutt, RLA, Landscape Architect
Tucson Parks and Recreation, (520) 837-8040
04/03/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/06/2020 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS

4.1 Identification and Descriptive Data

The development package will contain the following identification in the lower right corner of each sheet:

Any relevant case numbers for reviews or modifications that affect the site.

Provide Case # DP20-0050 on each sheet.

Indicate graphically, where possible, compliance with conditions of PAD-15 Document. https://www.tucsonaz.gov/files/pdsd/plans/Bridges_PAD_Amendment-MayorCouncil-May_2018.pdf

C.2 LAND USE REGULATIONS Page 50

Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.


Additional comments may apply
04/08/2020 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Show drainage patterns throughout the site. Show how water harvesting will be maximized by directing runoff to water harvesting areas to the maximum extent practicable.
2. Provide references to the typical water harvesting island on the grading plan as applicable.
3. Check the callout references to ensure the correct details are listed.
4. Revise the solid waste enclosure to meet the requirements of Technical Standard 8-01.9.0 Figure 3A.
04/09/2020 DJELLEN1 ZONING REVIEW Reqs Change CDRC TRANSMITTAL



TO: Development Services Department

Plans Coordination Office



FROM: David Jellen

PDSD Zoning Review Section



PROJECT: Taco Bell at Tucson Marketplace

Development Package (1st Review)

DP20-0050



TRANSMITTAL DATE: April 9, 2020



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.



Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is March 6, 2021.



SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)



CONTENT REQUIREMENTS



2-06.4.1 - The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines.



COMMENT: 2-06.4.1 - Include the email addresses for the developer and the architect.





2-06.4.2 - The title block shall include the following information and be provided on each sheet:



2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.



COMMENT: 2-06.4.3 - Provide the development package case number, DP20-0050, adjacent to the title block on each sheet.





2-06.4.4.C - Section, township, and range; section corners; north arrow; and the scale will be labeled.



COMMENT: 2-06.4.4.C - Solely provide the number for each section on the location map and do so for each corner of each section shown.





2-06.4.7 - General Notes

The following general notes are required. Additional notes specific to each plan are required where applicable.



Zoning and Land Use Notes



2-06.4.7.A.4 - Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses.



COMMENT: 2-06.4.7.A.4 - Indicate the existing use of the property in General Note 19 as noted by the standard above. The proposed use is Food and Beverage Sales, which is part of the Retail Use Group, and is permitted in Sub-Areas A and F in PAD-15.





2-06.4.8 - Existing Site Conditions

The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.



2-06.4.8.A - Provide site boundary/subdivision perimeter information, including bearing in degrees, minutes, and seconds, with basis for bearing noted, together with distances in feet, to hundredths of a foot, or other functional reference system.



COMMENT: 2-06.4.8.A - Provide the site boundary perimeter information as noted by the standard above.





2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.



COMMENT: 2-06.4.8.C - Provide all information regarding existing private or public right-of-way adjacent to or within the site as noted by the standard above.





2-06.4.9 - Information on Proposed Development

The following information on the proposed project shall be shown on the drawing or added as notes.



2-06.4.9.F - All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined. If the property is being rezoned, use those boundaries and classifications. The basis for this requirement is that some zoning requirements on a project are based on the zoning classification of adjacent property. Also, in some instances, each zone has to be taken into consideration on property that is split by two or more zoning classifications, as each may have different requirements.



COMMENT: 2-06.4.9.F - Indicate all existing zoning classification on and adjacent to the project as noted by the standard above.





2-06.4.9.H.4 - Indicate if existing streets are public or private; provide street names, widths, curbs, sidewalks, and utility locations, all fully dimensioned.



COMMENT: 2-06.4.9.H.4 - Dimension widths, curbs, sidewalks, and utility locations as noted by the standard above. See related comment 6.





2-06.4.9.O - All applicable building setback lines, such as erosion hazard, floodplain detention/retention basins, and zoning, including sight visibility triangles, will be shown.



COMMENT: 2-06.4.9.O - Provide the applicable building setback lines to the north, south, and west of the building.





2-06.4.9.Q - Provide the square footage and the height of each commercial, industrial, or business structure and the specific use proposed within the footprint of the building(s).



COMMENT: 2-06.4.9.Q - Indicate the height of the building within the footprint of the building on the site plan.





2-06.4.9.T - Show refuse collection areas, including locations of dumpsters, screening location and materials, and vehicle maneuverability, fully dimensioned, and access route. If dumpster service is not proposed, indicate type of service. For specific information on refuse collection, refer to Section 8-01.0.0, Solid Waste and Recycle Disposal, Collection, and Storage, of the Technical Standards Manual. Refuse collection on all projects shall be designed based on that section, even if collection is to be contracted to a private firm.



COMMENT: 2-06.4.9.T - It appears that the gate of the dumpster, when open, will interfere with the drive-through. Show that the dumpster will not interfere with vehicles exiting the drive-through area.





***For additional information on the any standard presented in this memo, please refer to the City of Tucson “Unified Development Code” – Administrative Manual Section 2-06 or Technical Standards noted in the comments. https://www.tucsonaz.gov/pdsd/all-codes-plans-determinations





If you have any questions about this transmittal, Contact David Jellen at (520) 837-4082 or by email David.Jellen@tucsonaz.gov.



RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
04/16/2020 GDAURIA1 COT NON-DSD FIRE Completed
04/27/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change RETURNED FOR CORRECTIONS NOTICE
Your Next Steps: Resubmittal with a Comment Response Letter

DESCRIPTION: SITE/GRADING/SWPPP/FUP - Taco Bell at Tucson Marketplace.
PERMIT: DP20-0050
FEE BALANCE: $0 (zero)

SEE REVIEWER'S COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, left side, Activity Search, enter the Activity Number
- Permits section, click on blue tab
- Reviews section, click on Review Details
- Documents section, click on blue icon to the right of each document

YOUR NEXT STEPS: Submit the following items to the Filedrop - https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter (your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Name your 2nd submittal documents to start with the submittal number, for example: 2_Plan_Set

NOTE: The City of Tucson's Permit Counter at 201 N. Stone Avenue (the physical office) is closed to the public until further notice. In the meantime, our staff is working remotely from home. All communications are by telephone or email.

CONTACT US INFO: To speak with a staff member on the telephone, please sign into the Virtual Zoning Counter:
https://www.tucsonaz.gov/pdsd/virtual-service-counter
The queue is open from 8:00 am -12:00 noon, Monday-Friday.
It’s better to sign in closer to 8 than 12 noon.
This is similar to the City’s in-person counter but instead over the phone.

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov
04/27/2020 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Needs Review
04/29/2020 SBEASLE1 UTILITIES TUCSON ELECTRIC POWER Approved (The TEP Facilities Map mentioned below can be viewed online: www.TucsonAz.gov/Pro. See the Documents section.)

WR# 6309863
April 29, 2020
SUBJECT: TACO BELL AT TUCSON MARKETPLACE
DP20-0050

Tucson Electric Power Company (TEP) has reviewed and approved the development plan submitted March 10 2020. It appears that there are no conflicts with existing facilities.

Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer.

In order to apply for electric service, call the New Construction Department at (520) 918-8300.
Submit a final set of plans including approved site, electrical load, paving off-site improvements and irrigation plans, if available include a CD with the AutoCAD version of the plans.
If easements are required, they will be secured by separate instrument. Your final plans should be sent to:
Tucson Electric Power Company
Attn: Mr. Richard Harrington
New Business Project Manager
P. O. Box 711 (OH 204)
Tucson, AZ 85702
520-917-8726

Should you have any technical questions, please contact the area Designer Martin Rodriguez, at (520) 991-5495
Sincerely,
Conor Mahoney
Office Support Assistant, Design/Build

Final Status

Task End Date Reviewer's Name Type of Review Description
04/27/2020 SBEASLE1 OUT TO CUSTOMER Completed