Permit Number: DP20-0045
Parcel: 132130660

Address:
1002 E 36TH ST

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - DP20-0045
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2022 AWARNER1 LANDSCAPE REVIEW Approved
01/06/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the site utility drawings to indicate that backwater valves will be required for lots 47, 48, 50 and 51 because the rim elevation of the next upstream sanitary manhole is less than 12" below the proposed first floor elevations. Reference: Section 714.1, IPC 2018, as amended by the City of Tucson.
01/10/2022 JPEELDA1 FIRE REVIEW Approved Approved w/o fire sprinklers per Glenn D'Auria
02/03/2022 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change Email from: COTDSDPermits
to: lisa bowers
Thu 2/3/2022 4:15 PM

REVISION REVIEW NOTICE
Returned for corrections, DP20-0045

DESCRIPTION: SITE/GRADING/SWPPP - Brioso at The Bridges, new multi-family residential

REVISION FEES DUE: $ 82.50
ONLINE PAYMENTS
https://www.tucsonaz.gov/pdsd/fees
If amount doesn't match "Fees Due", check back in a few hours after it is updated.
1- Click on: Pay Planning & Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click the blue tab: Continue
5-Under the Pay column, check the boxes you want to pay
6- Click Continue, then enter your credit card info

VIEW the review comments and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

YOUR NEXT STEPS: Submit documents to the Filedrop
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application"
1) Comment Response Letter (your response to
the reviewer's Requires changes comments)
2) Plan Set (or individual sheets)
3) Any other items/documents requested by review staff

Sharon Beasley, Building Permit Specialist

City of Tucson, Planning and Development Services
Email: COTDSDpermits@TucsonAz.gov
02/03/2022 SBEASLE1 COT NON-DSD TRAFFIC Approved Email from: David Stiffey
To: CDRC
Thu 2/3/2022 12:03 PM

There are several notes on these plans that all of the civil/ ROW work is to be done under another DP (DP21-0078) Therefore, I have no comments.

David Stiffey
City of Tucson
Dept. of Transportation and Mobility
12/08/2021 SBEASLE1 ENGINEERING REVIEW Approved Engineering was approved by Loren Makus during the recent OK to Submit.
12/31/2021 STEVE SHIELDS ZONING REVIEW Approved