Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP20-0045
Parcel: 132130660

Address:
1002 E 36TH ST

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP20-0045
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2020 SBEASLE1 START PLANS SUBMITTED Completed
05/29/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/04/2020 ANDREW CONNOR LANDSCAPE REVIEW Approved
06/10/2020 STEVE SHIELDS ZONING REVIEW Approved
06/15/2020 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Correct the bike parking description on sheet 1. Plan says "*BICYCLE HANGER WITHIN THE RESIDENTIAL UNITS (1 IN EACH 2-BED UNIT, 2 IN EACH 2-BED UNIT). SEE DETAIL L, SHEET 14." Please clarify.

Loren Makus, EIT

Loren.makus@tucsonaz.gov
06/18/2020 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved Per page 108 of PAD-15, each subsequent developmentplan or subdivision plat shall be brought before the Design Review Committee (DRC) for its formal consideration, together with proposed conceptual building elevations and architectural renderings, sufficient toallow the Committee to judge the proposed Project for conformance with the pertinent adopted design guidelines.
Prior to the submittalof any development plan or subdivision plat to the City of Tucson, the Developer must procure a letter of recommendation from the DRC for submittal to the City. This letter, and a record copy (for the City's archives) of the materials recommended by the DRC,must accompany any City submittal in order to allow review of same by the City of Tucson Planning & Development Services Department.
The second submittal response comments state that letter is to be provided. Provide the letter in next resubmittal.
06/18/2020 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved March 31, 2020
ACTIVITY NUMBER: DP20-0045
PROJECT NAME: Brioso at the Bridges
PROJECT ADDRESS: 1002 E 36th Street
PROJECT REVIEWER: Zelin Canchola TDOT

A private improvement agreement (PIA) will be required for offsite work.
06/19/2020 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Reqs Change Brioso at the Bridges, DP20-0045, 2nd submittal, is Conditionally Approved by Pima County Addressing subject to eliminating the word “UNIT” as these will all be Building Numbers and correcting the numbering in the area shown below as discussed with the Fire Department and Pima County Addressing.
Please let me know if you have any questions.

Thank you,

Robin Freiman, Addressing Official
Pima County Development Services Department
(520) 724-7570
06/23/2020 SBEASLE1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Reqs Change June 22, 2020
RE: DP20-0045 / Brioso at The Bridges, 2nd submittal, Received May 22, 2020

Thank you for the opportunity to comment on DP20-0045, Brioso at The Bridges; 2nd Submittal, a development package application for an approximately 10.2 acre site, located southeast of the intersection of South Park Avenue and East 37th Street. The property is zoned Planned Area Development 15 (PAD-15), with the proposed development being a multi-family residential development.

This site is within the Tucson International Airport avigation easement requirements and public disclosure area, FAA traffic pattern airspace, and FAA Part 77 airspace.

The Tucson Airport Authority previously commented on the Major Change to PAD-15, comment letter is dated March 9th, 2018, with this comment letter being adopted on Page B7-B8 of City of Tucson Ordinance 11552. This proposed project area is contained within the areas identified by this City of Tucson Ordinance.

The Tucson Airport Authority conditionally approves the subject request contingent upon the following conditions of approval, as noted below. These conditions shall be identified in the general notes of the revised development plan.

The applicant’s comment response letter for the first submittal of this project made reference to these notes but these notes were not present in the 2nd submittal of the project.

Conditions of approval:

1. According to the Federal Aviation Administration (FAA) Notice Criteria Tool, this project area is located in proximity to a navigation facility and could impact navigation signal reception. The applicant shall file FAA Form 7460 with the FAA at least 45 days before construction activities begin unless FAA staff, with the Obstruction Evaluation / Airport Airspace Analysis (OE/AAA), provides the project applicant with written communication that filing FAA Form 7460 is not required. It is highly recommended that the applicant file earlier than 45 days to provide the applicant with sufficient time to respond to any concerns which are identified by the FAA. Any cranes which are used must also be identified with Form 7460. Please file Form 7460 at https://oeaaa.faa.gov/oeaaa/external/portal.jsp”

2. That prior to the City's approval of any construction permit for a permanent building, the property owner shall record the Avigation Easement which discloses the existence, and operational characteristics of the Tucson International Airport to future owners or tenants of the property and further conveys the right to the public to lawfully use the airspace above the property. The Avigation Easement shall be recorded in a manner with the Pima County recorder which shall document it as having title liability. The content of such documents shall be according to the form and instructions provided.

The current property owner or person authorized to sign on behalf of the current property owner shall complete, sign, and record the Avigation Easement. Please record the Avigation Easement with the Pima County Recorder’s Office. Once the Avigation Easement is recorded please send a complete copy of the recorded easement document to Tucson Airport Authority by either email (send to srobidoux@flytucson.com) or to the mailing address provided below.
Scott Robidoux, Senior Airport Planner
Tucson Airport Authority
7250 South Tucson Boulevard, Suite 300
Tucson, AZ 85756

3. For only residential uses - The developer shall provide the Airport Disclosure Statement form, at time of sale, to the new property owners with new unit purchases. In the event the development of any residential uses does not involve the sale of new units, but is instead offering rental residential units to the public, the new tenant of the rental unit shall be provided a copy of the Airport Disclosure Statement form. The intent of the Airport Disclosure Statement form is to educate and notify the new residents that they are living near an airport. The content of such documents shall be according to the form and instructions provided.

The new property owner or new tenant shall forward a signed copy of the Airport Disclosure Statement form to the Tucson Airport Authority, using the mailing address provided below.

Scott Robidoux, Senior Airport Planner
Tucson Airport Authority
7250 South Tucson Boulevard, Suite 300
Tucson, AZ 85756

Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811.

Respectfully,
Scott Robidoux, C.M., Senior Airport Planner
06/26/2020 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Reqs Change Per page 108 of PAD-15, each subsequent developmentplan or subdivision plat shall be brought before the Design Review Committee (DRC) for its formal consideration, together with proposed conceptual building elevations and architectural renderings, sufficient toallow the Committee to judge the proposed Project for conformance with the pertinent adopted design guidelines.
Prior to the submittalof any development plan or subdivision plat to the City of Tucson, the Developer must procure a letter of recommendation from the DRC for submittal to the City. This letter, and a record copy (for the City's archives) of the materials recommended by the DRC,must accompany any City submittal in order to allow review of same by the City of Tucson Planning & Development Services Department.
The second submittal response comments state that letter is to be provided. Provide the letter in next resubmittal.
07/14/2020 SBEASLE1 UTILITIES TUCSON ELECTRIC POWER Reqs Change (The TEP FACILITY MAP mentioned below can be viewed online: www.TucsonAz.gov/Pro. See the Documents section.)

WR#6309820
July 14, 2020
SUBJECT: Brioso at the Bridges
DP20-0045, 2nd Submittal

Tucson Electric Power Company (TEP) has reviewed the development plan submitted June 30, 2019. TEP is unable to approve the plan at this time.

There are primary voltage lines and facilities along Park Ave right of way that are not depicted on the submitted
plans. Cannot approve plans as we cannot determine if there are conflicts with TEP facilities. In order for TEP to approve the plan, our facilities and easements must be depicted on the plans.

Enclosed is a copy of a TEP facility map showing the approximate location of the existing facilities. All costs associated with the relocation of the facilities in conflict will be billable to the developer.

Please resubmit a revised blueline to the City of Tucson for TEP’s review. Should you have any technical questions, please contact the area Designer, Martin Rodriguez, at
(520) 991-5495 should you have any questions.
Sincerely,
Conor Mahoney, Office Support Assistant
Design/Build
07/14/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change RETURNED FOR CORRECTIONS NOTICE
Your Next Steps: 1. Payment 2. Resubmittal of documents

DESCRIPTION: SITE/GRADING/SWPPP - Brioso at The Bridges, new multi-family residential.

PERMIT/ACTIVITY: DP20-0045

FEES DUE: $ 5,966.44
Please pay the total fees (or at a minimum, the REVIEW Fees). A payment is required before your next submittal.

ONLINE PAYMENTS
https://www.tucsonaz.gov/pdsd
NOTE: It may take 1-2 days for the full fee amount to show online.
Wait for full amount before paying.
Visa, MC, Discover, American Express or pay by checking account
1- Click blue tab: Pay Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click the blue tab: Continue
5- If any issues, try using the browser Internet Explorer

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on blue icon to the right of each document

YOUR NEXT STEP:
Submit documents to the Filedrop
https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Name the 3rd submittal documents starting with the
submittal number, for example: 3_Plan_Set

FOR FASTER PROCESSING:
When on the Filedrop page, select the box
"Development Package or Land Division". This applies to all
DP submittals, DP resubmittals, and DP revisions - and all Land Splits.
(For Building Permits, continue to select "Resubmittals/Revisions...".)

Thank you.

Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/14/2020 SBEASLE1 OUT TO CUSTOMER Completed