Permit Review Detail
Review Status: Completed
Review Details: DEV PKG
Permit Number - DP20-0042
Review Name: DEV PKG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/23/2020 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 03/23/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 03/23/2020 | ANDREW CONNOR | LANDSCAPE | REVIEW | Approved | |
| 03/23/2020 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Please show all existing, proposed, and relocated fire hydrants. |
| 03/31/2020 | SBEASLE1 | ENGINEERING | REVIEW | Reqs Change | 1. Clearly indicate by note or graphically that all landscape islands capable of receiving runoff will be provided with curb openings. |
| 04/02/2020 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | Show the location of the accessible signage on the plan. |
| 04/06/2020 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | RETURNED FOR CORRECTIONS NOTICE Your Next Steps: 1. Payment 2. Resubmittal with a Comment Response Letter DESCRIPTION: SITE - Grant Rd. & 1st Avenue, parking. PERMIT: DP20-0042 FEES DUE: $ 4,023.30 Note: A payment is required before we can accept your resubmittal. PAYMENT OPTIONS Please pay the total fees (or Review Fees at a minimum) 1. Online Payment Online Payment https://www.tucsonaz.gov/pdsd/online-resources-fees-maps-records 1. NOTE: It may take 1-2 days for complete permit information to be available online 2. Visa, MC, Discover, American Express or pay by checking account 3. Not case-sensitive but a hyphen is needed, for example: dp19-2000 4. Enter your Permit Nbr 5. Business/Individual Name: Leave blank 6. Click the blue Continue tab 7. If any issues, try using the browser Internet Explorer SEE REVIEWER'S COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro (If information is not available, check back in a few days as we have recently implemented updated computer software.) - Home page, left side, Activity Search, enter the Activity Number - Permits section, click on blue tab - Reviews section, click on Review Details - Documents section, click on blue icon to the right of each document YOUR NEXT STEPS: Submit the following items to the Filedrop - https://www.tucsonaz.gov/file-upload-pdsd 1) Comment Response Letter (your response to the reviewer's Requires Change comments) 2) Plan Set (all pages, full set) 3) Any other documents requested by review staff - Name your 2nd submittal documents to start with the submittal number, for example: 2_Plan_Set Thank you. Sharon Beasley, Permit Specialist City of Tucson Planning and Development Services email: COTDSDPermits@TucsonAz.gov NOTE: The City of Tucson's Permit Counter at 201 N. Stone Avenue (the physical office) is closed to the public until further notice. In the meantime, our office is still fully staffed but all communications are by telephone or email. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/06/2020 | SBEASLE1 | OUT TO CUSTOMER | Completed |