Permit Number: DP20-0024
Parcel: 107130670

Address:
2729 N STONE AV

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP20-0024
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2020 SBEASLE1 START PLANS SUBMITTED Completed
02/19/2020 IMONSHI1 ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Iman Monshizadeh
PDSD Zoning Review Section

PROJECT: Stone Auto Group - 2729 N Stone
Development Package (1st Review)
DP20-0024 - C-2 Zoning
TRANSMITTAL DATE: February 19th, 2020
DUE DATE: February 25th, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is January 23rd, 2020.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)


2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

1. COMMENT: 2-06.4.3 - Provide the development package case number, DP20-0024, adjacent to the title block on each sheet.

2-06.4.7.A.8.b - Percentage and area in square feet of building and accessory building coverage;

2. COMMENT: 2-06.4.7.A.8.b - Demo permit must be approved and all structures must be cleared off of parcel prior to approval of DP. Include the approved documents for the lot combo on the next submittal.

Provide a general note stating what the use for the existing slab will be. If the slab is to be kept as is state that as so.


2-06.4.9.E - Proposed land splits or existing lot lines shall be drawn on the plan with dimensions and the identification number and approximate square footage of each lot. (Please be aware that, if land division occurs and the number of lots falls within the definition of subdivision, a subdivision plat is required.) Land splits require a separate permit and review.

3. COMMENT: 2-06.4.9.E - This site consists of 2 existing parcels. List both parcel numbers under general notes. A lot combination must be processed before the DP can be approved.

Revise the case number provided for the demo permit, this case number seems to be for a violation


2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

4. COMMENT: 2-06.4.9.H.5.a - Define clearly where the vehicle display area will be on the site. Is there any areas designated for vehicle repair within the site? If there are clarify where and show the square footage.


2-06.4.9.H.5.c - Show all loading zones, vehicle maneuverability fully dimensioned, and access route. Provide as a note the number of loading spaces required, the number provided, whether the loading space is a Type A or B as provided in UDC Section 7.5.4.

5. COMMENT: 2-06.4.9.H.5.c - Add a general note stating that access gate is open during business hours.

2-06.4.9.W - Indicate the locations and types of proposed signs (wall, free-standing, pedestal) to assure there are no conflicts with other requirements and that minimal locational requirements can be met. Indicate if there are any existing billboards on site. Compliance to the Sign Code, Chapter 3 of the Tucson Code, is required.

6. COMMENT: 2-06.4.9.W - Provide a general note stating that all signs will be approved under a separate permit.

***For additional information on the any standard presented in this memo, please refer to the City of Tucson "Unified Development Code" - Administrative Manual Section 2-06 or Technical Standards noted in the comments. https://www.tucsonaz.gov/pdsd/all-codes-plans-determinations


If you have any questions about this transmittal, Contact Iman Monshizadeh at (520) 837-4082 or by email Iman.Monshizadeh@tucsonaz.gov or contact Steve Shields at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
02/26/2020 MARTIN BROWN FIRE REVIEW Approved
03/02/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The rim elevation of the next upstream sanitary manhole (#9812-23, 2367.22') is higher than the first floor elevation (2365.92). Provide a note on the plans requiring the installation of a backwater valve when future plumbing activities take place. Reference: Section 714.1, IPC 2018, as amended by the City of Tucson.
2. Revise the site drawing to include the location of the fire hydrants. Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2018.
03/03/2020 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS

4.1 Identification and Descriptive Data

A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

The development package will contain the following identification in the lower right corner of each sheet:

Any relevant case numbers for reviews or modifications that affect the site.

Provide Case # DP20-0024 on each sheet.

7.6. LANDSCAPING AND SCREENING

7.6.2. APPLICABILITY

The provisions of this section apply to the following:

A. All new development.

Minimum Width
Street landscape borders must be a minimum of ten feet wide as measured from the street property line.

A street landscape border is an area running the full length of the street property line bounding the site except for points of ingress-egress.


7.6.5. SCREENING STANDARDS

Screening for individual land uses and zones must be provided as determined in Table 7.6.4-1 and in addition to the required landscape borders. Screening is not required between similar uses in accordance with Table 7.6.4-1.

Show compliance with landscaping and screening requirements by locations, material descriptions, and dimensions. Specific plant or hardscape material shall be detailed on a landscape plan. A detailed landscape plan is required. In accordance with Section 2-10.0.0, Landscape Plan Requirements.

7.6.6. USE OF WATER
Water Conservation Design
Landscape plans shall incorporate water-conserving designs. A water-conserving design must take into account soil and drainage factors and microclimates, includes grouping of plants with similar water standards and use of efficient irrigation systems, and attempts to preserve on-site vegetation.

Provide Irrigation plan.


Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.


Additional comments may apply
03/10/2020 PCAMARE1 ENGINEERING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department

Plans Coordination Office



FROM: Paul Camarena

PDSD Engineering Review Section



PROJECT: Stone Auto Group

Development Package (1st Review) 2729 N. Stone Ave

DP20-0024



TRANSMITTAL DATE: March 10, 2020



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Engineering Review Section comments were addressed.



1. Clarify the existing conditions on site. It appears that there is not an existing sidewalk on Stone Ave and that the site is not fully paved.



2. A 6' concrete sidewalk will be required along Stone Ave. Draw and label the proposed driveway apron.



3. Label the proposed area to be paved.



4. Provide the existing and proposed contour lines. ( Water is to be routed to landscape border the maximum amount possible)



If you have any questions about this transmittal, Contact Paul Camarena at Paul.Camarena@tucsonaz.gov





RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package and structural plans
03/11/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change RETURNED FOR CORRECTIONS NOTICE
Your Next Steps: 1. Payment 2. Resubmittal with a Comment Response Letter

DESCRIPTION: SITE - Stone Auto Group. Change of use from upholstery shop toauto sales facility.

PERMIT: DP20-0024
Due to high volume, please enter this number at the beginning on Filedrop's "ProjectDescription" field and all correspondence. It will allow our staff to quickly identify which office to forward it to for processing.

FEES DUE: $ 1,206.50
Note: A payment is required before we can accept your resubmittal.
PAYMENT OPTIONS Please pay the total fees (or Review Fees at a minimum)
1. Online Payment
2. In person at the City Permit Counter (Mon-Fri, 8:00 AM to 2:00 PM)
3. By mail - a check payable to the City of Tucson (address is below), include the Activity Number

Online Payment
https://www.tucsonaz.gov/pdsd/online-resources-fees-maps-records

1. NOTE: It may take 1-2 days for complete permit information to be available online
2. Visa, MC, Discover, American Express or pay by checking account
3. Not case-sensitive but a hyphen is needed, for example: dp19-2000
4. Enter your Permit Nbr
5. Business/Individual Name: Leave blank
6. Click the blue Continue tab
7. If any issues, try using the browser Internet Explorer

SEE REVIEWER'S COMMENTS and your submitted documentson PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, left side, Activity Search, enter the Activity Number
- Permits section, click on blue tab
- Reviews section, click on Review Details
- Documents section, click on blue icon to the right of each document

YOUR NEXT STEPS: Submit the following items to the Filedrop- https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter (your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set)
3) Any other documents requested by review staff
- Filedrop: In the Project Description field, enter the Activity/Permit Number
- Name your 2nd submittal documents to start with the submittal number, for example: 2_Plan_Set

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
Attn: Permit Counter/Payments
201 N. Stone Avenue, 2nd Floor
Tucson, AZ 85701
email: COTDSDPermits@TucsonAz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
03/11/2020 SBEASLE1 OUT TO CUSTOMER Completed