Permit Number: DP20-0016
Parcel: 129091430

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP20-0016
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2020 SBEASLE1 START PLANS SUBMITTED Completed
02/06/2020 IMONSHI1 ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office
FROM: Iman Monshizadeh
PDSD Zoning Review Section
PROJECT: Southwest Strings PV System
Development Package (1st Review) 1721 S Cherrybell
DP20-0016 - I-1 Zoning

CHECKLIST FOR MINOR DEVELOPMENT CHANGES TO EXISTING COMMERCIAL/INDUSTRIAL SITES

Purpose
This standard has been prepared for the purpose of informing applicants of the submittal and review requirements for minor changes to existing commercial sites to assure proper and adequate information is presented in a consistent manner, thereby providing the basis for an efficient and timely review. The minor revisions to existing commercial sites are prepared in support of applications for building permits and related reviews.

The information that is requested establishes the basis upon which the project will be approved and could affect what is required of the property in the future, should there be a proposal for expansion or for a different use of the property. This standard does not waive any applicable city regulations or codes.

Applicability
This standard shall be used for minor changes to existing commercial sites such as but not limited to; expansions less than 25% in square footage of land area, floor area, lot coverage, or vehicular use area, modification to accessible vehicle parking, parking area restripe, etc. Applicability to be determined by Zoning and/or Engineering review staff via email or at PDSD review counter.

APPLICATION SUBMITTAL REQUIREMENTS

Development Package applications are available from PDSD. Completed applications and accompanying materials shall be submitted to PDSD. Incomplete or inaccurate applications will not be accepted. The types of documents and the specific number of copies required of each of the documents are on the PDSD website or may be obtained from PDSD. Resubmittals of development packages require a comment response letter that details how all previous comments have been addressed. Provide the same number of copies of the comment response letter as plans provided.
CONTENT REQUIREMENTS

1. The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines.

COMMENT: Provide an email address and all other relevant information for both the developer and owner of the site as noted by the standard above

2. The title block shall include the following information and be provided on each sheet: The proposed name of the project, or if there is no name, the proposed tenant's name. A brief legal description is to be provided. The page number and the total number of pages in the package (i.e., sheet xx of xx). The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

COMMENT: Provide the Development package number DP20-0016 adjacent to the title block on the next submittal

COMMENT: provide the legal description within the title block on the next submittal

GENERAL NOTES
The following general notes are required. Additional notes specific to each plan are required where applicable.

1. List the gross area of the site by square footage and acreage.

COMMENT: Pima County Assessors Shows Parcel 129-09-002A as being approximately 60,000sf instead of approximately 90,000sf. Confirm if the current square footage shown is more accurate, if not revise the square footage for that parcel and the combined square footage.

2. Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses. Clarify what the warehousing is used as, is it commercial storage?

COMMENT: revise the zoning data to show the UDC classified use of the property. Which specific use is the site within the Industrial and retail use group?

COMMENT: Provide the Square footage of each use for parking calculations

EXISTING SITE CONDITIONS:
1. The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.

COMMENT: Provide the information as noted by the standard above for Cherrybell Sv and Silverlake Rd

INFORMATION OF PROPOSED DEVELOPMENT:
The following information on the proposed project shall be shown on the drawing or added as notes.


1. Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.


COMMENT: Show the entire parking area for both the existing and the new parking config on the next submittal to confirm the correct number of spaces. A previously approved site plan shows 25 spaces instead of 12 and 10 on the existing parking spaces located in the center of the parking lot, revise the existing parking config to show the same number of parking that is shown on the previously approved site plan. Parking calculations will be reevaluated by zoning on the next submittal once the ALL parking spaces are shown on plan and the specific UDC uses and their square footage are provided.


COMMENT: Clarify if the two 10'-3" access lanes are not used as a fire lane. If they are to be used as a fire lane they must be 20' wide.


If you have any questions about this transmittal, Contact Iman Monshizadeh at (520) 837-4082 or email Iman.Monshizadeh@tucsonaz.gov or contact Steve Shields at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
02/18/2020 MARTIN BROWN COT NON-DSD FIRE Approved
02/19/2020 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

The Development Package will contain the following identification in the lower right corner of each sheet:

Any relevant case numbers for reviews or modifications that affect the site.

Provide the development package case number, DP20-0016.

Ensure that all Zoning and Engineering comments and concerns are addressed.

Additional comments may apply.
02/25/2020 LOREN MAKUS ENGINEERING REVIEW Passed
02/26/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
Your Next Steps: Resubmittal with a Comment Response Letter

DESCRIPTION: SITE - Southwest Strings, solar PV system on one steel canopy.

PERMIT: DP20-0016
For faster service, please enter this number in the Filedrop's "Project Description" field and on correspondence.

FEE BALANCE: $0 (zero)
SEE REVIEWER'S COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, left side, Activity Search, enter the Activity Number
- Permits section, click on blue tab
- Documents section, click on blue icon to the right of each document
- Reviews section, click on Review Details

YOUR NEXT STEPS: Submit the following items to the Filedrop - https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter (your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set)
3) Any other documents requested by review staff
- Filedrop: In the Project Description field, enter the Activity/Permit Number
- Name your 2nd submittal documents to start with the submittal number, for example: 2_Plan_Set

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
Attn: Permit Counter/Payments
201 N. Stone Avenue, 2nd Floor
Tucson, AZ 85701
email: COTDSDPermits@TucsonAz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
02/26/2020 SBEASLE1 OUT TO CUSTOMER Completed