Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: DP20-0010
Parcel: 211350170

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP20-0010
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2020 SBEASLE1 START PLANS SUBMITTED Completed
01/21/2020 SBEASLE1 LANDSCAPE REVIEW Approved Approved 01/14/2020 by Andrew Connor (see Okay to Submit).
01/21/2020 SBEASLE1 ZONING REVIEW Approved Approved 01/17/2020 by Steve Shields (see Okay to Submit).
02/13/2020 LOREN MAKUS ENGINEERING REVIEW Reqs Change Provide an approved floodplain use permit from Pima County RFCD for this project.
02/14/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
Your Next Steps: Resubmittal with a Comment Response Letter

NOTE: All City of Tucson offices will be closed on Monday, February 17 (except for emergency services). Planning & Development Services will re-open on Tuesday: https://www.tucsonaz.gov/pdsd/contact-us-hours-service.

DESCRIPTION: SITE - City of Tucson, 3330 S. Sandario, solar ground mount, well, SA-014A.

PERMIT: DP20-0010
For faster service, please include this number in the Filedrop's "Project Description" field.
FEE BALANCE: $0 (zero)
SEE REVIEWER'S COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, left side, Activity Search, enter the Activity Number
- Permits section, click on blue tab
- Documents section, click on blue icon to the right of each document
- Reviews section, click on Review Details

YOUR NEXT STEPS: Submit the following items to the Filedrop - https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter (your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set)
3) Any other documents requested by review staff
- Filedrop: In the Project Description field, enter the Activity/Permit Number
- Name your 2nd submittal documents to start with the submittal number, for example: 2_Plan_Set

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
Attn: Permit Counter/Payments
201 N. Stone Avenue, 2nd Floor
Tucson, AZ 85701
email: COTDSDPermits@TucsonAz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
02/14/2020 SBEASLE1 OUT TO CUSTOMER Completed