Permit Number: DP20-0008
Parcel: 110100400

Address:
5001 E GLENN ST

Review Status: Completed

Review Details: TENTATIVE PLAT REVIEW

Permit Number - DP20-0008
Review Name: TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2020 SBEASLE1 START PLANS SUBMITTED Completed
08/12/2020 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Passed Tucson Water approval not needed until final plat phase.
08/17/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/24/2020 SBEASLE1 DESIGN PROFESSIONAL REVIEW Approved Date: August 23, 2020

From: Rick Gonzalez, Architect, City of Tucson On-call Design Professional

Re: Design Professional review comments for Flexible Lot Development Review DP20-0008 Fort Glen FLD Subdivision.

After review, based upon Unified Development Code (UDC) Section 8.7.3.M.1 - 4, of the required development plan documents submitted to PDSD (Revision #3 documents in PRO), I recommend approval of this project, as noted in Italics below:

M. Design Criteria
1. Architectural Variation
c. Requirements
(1) The same architectural elevation shall not be repeated more often than every fourth lot.

Complies (italics)

(2) Architectural variation may be accomplished by incorporating a minimum of two of the following design features into the affected elevations: different building orientation, building elevation, garage placement, roof type, ornamentation, or architectural style. The applicant shall work with the City's Design Professional to ensure that adequate variation is achieved.

Complies (italics)

(3) Garage Placement. For FLD projects with over 20 or more single-family detached residential units, no more than 50% of detached residential units throughout the FLD shall be designed with garages that protrude from or are flush with the front wall of the living area or front porch of the house.
1.
Complies (italics)

END OF DP REVIEW
09/08/2020 SBEASLE1 PIMA COUNTY ADDRESSING Reqs Change (The "ATTACHED PDF" mentioned below can be viewed online: www.TucsonAz.gov/Pro. See the Documents section.)

Sept. 8, 2020
Fort Glenn Homes, DP20-0008, 3rd submittal, is being Returned for Corrections by Pima County Addressing.
The attached pdf contains Addressing’s comments.

Please let me know if you have any questions.
Thank you,
Robin Freiman, Addressing Official

Pima County Development Services Department
201 N Stone AV – 1st Floor
Tucson, AZ 85701
(520) 724-7570
09/09/2020 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
PDSD Zoning Review Section

PROJECT: Fort Glenn Homes (FLD Subdivision Lots 1 - 7 and CA's A, B, and C)
Development Package (3rd Review) 5001 E Glenn Street
DP20-0008 - R-1 Zoning

TRANSMITTAL DATE: September 9, 2020
DUE DATE: September 8, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

2-06.5.0 FLEXIBLE LOT DEVELOPMENT (FLD - ADDITIONAL REQUIREMENTS)

Previous COMMENT 25. This comment was not addressed, provide an accessible route to the amenities shown within the FOS,. As there are amenities planned for the FOS accessibility requirements must be met. Demonstrate how the requirements of 2018 IBC Chapter 11 and the ICC A117.1-2009 for access to the amenities. COMMENT: 2-06.5.3.C - It does not appear that the proposed FOS area meets the intent of the FOS requirements. The FOS is placed in the middle of a turnabout street with no specific use. The proposed FOS is unacceptable.

If you have any questions about this transmittal, Contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
09/25/2020 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change Engineering Approval pending Zoning Approval
09/28/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change DATE: Sept. 28, 2020

RETURNED FOR CORRECTIONS NOTICE
Your Next Steps: Resubmittal of your updated/corrected documents

DESCRIPTION: Tentative Plat / FLD - Fort Glenn Homes
PERMIT/ACTIVITY: DP20-0008
FEE BALANCE: $0 (zero) Thank you for the payment.

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

YOUR NEXT STEP:
Submit documents to the Filedrop
https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Name the 4th submittal documents starting with the
submittal number, for example: 4_Plan_Set

IMPORTANT:
On the Filedrop page, select the box: "Site Review/CDRC..."

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
09/28/2020 SBEASLE1 OUT TO CUSTOMER Completed