Permit Number: DP20-0008
Parcel: 110100400

Address:
5001 E GLENN ST

Review Status: Completed

Review Details: TENTATIVE PLAT REVIEW

Permit Number - DP20-0008
Review Name: TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2020 SBEASLE1 START PLANS SUBMITTED Completed
06/03/2020 SBEASLE1 PIMA COUNTY ADDRESSING Reqs Change (The attached plans mentioned below can be viewed online: www.TucsonAz.gov/Pro. See the Documents section: "PimaCo Addressing review, Plans, 06.30.20")

Pima County Addressing is returning Fort Glenn Homes, DP20-0008, 2nd submittal, for corrections.
Please see the attached plans for comments.

Nicholas Jordan, Addressing Specialist

Pima County Development Services Department
(520) 724-9623
06/08/2020 ANDREW CONNOR LANDSCAPE REVIEW Approved
06/09/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not resolved. [Initial comment: Provide the first floor elevation for the proposed residence on lot #2.]
07/01/2020 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
PDSD Zoning Review Section

PROJECT: Fort Glenn Homes (FLD Subdivision Lots 1 - 7 and CA's A, B, and C)
Development Package (2nd Review) 5001 E Glenn Street
DP20-0008 - R-1 Zoning

TRANSMITTAL DATE: July 1, 2020
DUE DATE: July 1, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is January 9, 2021.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
Section

Previous COMMENT 15. Until the TSMR is approved this DP cannot be approved. If approved provide the TSMR case number adjacent to the title block on all sheets and provide a general note stating the "TSMR case number, date of approval, what was modified and if applicable any conditions of approval. COMMENT: 2-06.4.9.H.4 - Approval of the street cross section as proposed will require approval through a TSMR. The required visitor parking area will also have to be approved as part of the TSMR. Contact Steve Shields for TSMR information.

This comment was not addressed. Label the proposed name for the private street.

This comment was not fully addressed, label the radius for the back-up spur. Label the street width dimensions and the dimension the visitor parking areas, overhang dimension and the back-up spur must be designed to comply with UDC Art 7.4.6.F.4 and figure 7.4.6-B. Revise the back-up spur as noted by the sections noted.

The proposed pedestrian circulation at the back of the entrance turn around area is a safety issue and needs to be addressed. Also provide a detail for the accessible ramp on the south side of the turnaround that clearly shows how this ramp will meet accessible requirements. A back up area is required when providing a gated community and adjacent to an MS&R street. See PDSD Engineering comments.

Previous 16. COMMENT: 2-06.4.9.O - Add a general note for the interior building setbacks as follows. "Perimeter Yards on Interior Lots - The perimeter yard requirements of Section 6.3.4, Dimensional Standards and Exceptions Tables, may be reduced for setbacks along interior lot lines to the extent permitted by the City 's adopted Building Codes."

This comment was not fully addressed. Per UDC Article 6.4.5.C.2.b.(2).(c) The distance between the street pavement edge and the parking structure is eight feet or less. The purpose of this requirement is to discourage motor vehicle tandem parking that would block the pedestrian area or overhang onto the roadway. Provide a dimension for lots 3, 5 & 6 from the face of garage to the edge of pavement. It appears that the 8' setback has been exceeded. The interior street setbacks have not been listed under general note 7. Use developing area setbacks based on the ADT of o to 140. See section 6.4.5.C. See the required setbacks for the Carport/Garage and the dwelling.

Previous COMMENT 17. Until the TSMR is approved this DP cannot be approved. If approved provide the TSMR case number adjacent to the title block on all sheets and provide a general note stating the "TSMR case number, date of approval, what was modified and if applicable any conditions of approval. COMMENT: 2-06.4.9.R - A pedestrian sidewalk along west side of Lot 6 is to be provided. A TSMR must be applied for and approved to eliminate the sidewalk along the west side of lot 6.

2-06.5.0 FLEXIBLE LOT DEVELOPMENT (FLD - ADDITIONAL REQUIREMENTS)

Previous COMMENT 23. This comment has not been addressed see previous comment 16 above. COMMENT: 2-06.5.3.A. - Demonstrate compliance with the required Building and Carport/Garage interior street setbacks.

Applicants requesting a perimeter yard reduction must indicate what the required and reduced perimeter yards are and their locations. Applicants requesting a reduced street perimeter yard must provide a written description of how the reduced yard will enhance the architectural design or the vehicular circulation in the FLD and submit a transportation statement, or if required by the Department of Transportation, a traffic impact analysis;

Previous COMMENT 25. This comment was not fully addressed. As there are amenities planned for the FOS accessibility requirements must be met. Demonstrate how the requirements of 2018 IBC Chapter 11 and the ICC A117.1-2009 for access to the amenities. COMMENT: 2-06.5.3.C - It does not appear that the proposed FOS area meets the intent of the FOS requirements. The FOS is placed in the middle of a turnabout street with no specific use. The proposed FOS is unacceptable.

Include in general note 10 the word "Functional" (Functional Open Space).

Additional comments:

There is a keynote 27 pointing to the center of the round-about that references vehicle overhang that does not appear to be correct.

***For additional information on the any standard presented in this memo, please refer to the City of Tucson "Unified Development Code" - Administrative Manual Section 2-06 or Technical Standards noted in the comments. https://www.tucsonaz.gov/pdsd/all-codes-plans-determinations

If you have any questions about this transmittal, Contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
07/07/2020 ALEXANDRA HINES DESIGN PROFESSIONAL REVIEW Reqs Change Comment from 1st review not addressed.
1. Provide architectural variation per UDC 8.7.3.M.1 since single-family detached units are abutting a collector (Glenn) street.

For UDC 8.7.3.M.2, transition edge treatment and privacy mitigation do not apply to dettached single story residences.

Alexandra Hines
alexandra.hines@tucsonaz.gov
8376975
07/07/2020 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Reqs Change The Applicant is responsible for obtaining a Water Availability Letter from Tucson Water (or Ray Water Company, if applicable). Provide the Letter in the next resubmittal. Mayor & Council cannot approve until water is assured.
07/07/2020 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP20-0008

1) Sheet 2. Keynote 27 is pointing towards the center of the traffic circle. This appears to be incorrect
2) Show the finished floor and finished grade elevation for lot 2
3) Previous comment 6. Access to the detention basin must be from onsite or from a Right of Way. If access for maintenance will be provided from offsite, provide a copy of the maintenance/access easement from the adjacent property to ensure access will be provided
4) Previous comment 10. Please add the applicable notes found in paragraph 2 of section 14.3
5) Previous comment 12. Please show the cross slope within the pedestrian crossing between the two curb access ramps. As shown the cross slope is outside of the pedestrian ADA path. Provide additional spot grades at the curb access ramps to show ADA compliance
6) Provide a curb access ramp on the southside of the onsite vehicle turnaround to provide a continuous pathway to the northside curb access ramp
7) Show on plans any subsurface drainage features necessary for the construction of the retaining wall system
8) Per TSM section 2-01.4.1.C, provide a copy of the project soils engineering report upon next submittal

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
07/08/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change RETURNED FOR CORRECTIONS NOTICE
Your Next Step: Resubmittal of documents

DESCRIPTION:
Tentative Plat / FLD - Fort Glenn Homes, Lots 1-6. Private street "A" (ingress, egress, open space, public utility), CA "B" (detention basin), CA "C" (landsc buffer).

PERMIT/ACTIVITY: DP20-0008
FEE BALANCE: $0 (zero) Thank you for the payment.

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on blue icon to the right of each document

YOUR NEXT STEP: Submit documents to the Filedrop
https://www.tucsonaz.gov/file-upload-pdsd

FOR FASTER PROCESSING, when on the Filedrop page, select the box
"Development Package or Land Division". This applies to all
DP submittals, DP resubmittals, and DP revisions - and all Land Splits.
(For Building Permits, continue to select "Resubmittals/Revisions...".)

1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Name the 3rd submittal documents starting with the
submittal number, for example: 3_Plan_Set

Thank you.
Sharon Beasley, Permit Specialist
City of Tucson
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/08/2020 SBEASLE1 OUT TO CUSTOMER Completed