Permit Number: DP20-0003
Parcel: 10119001F

Review Status: Completed

Review Details: DEV PKG - OK TO SUBMIT

Permit Number - DP20-0003
Review Name: DEV PKG - OK TO SUBMIT
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2020 SBEASLE1 START PLANS SUBMITTED Completed
01/06/2020 SBEASLE1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Needs Review This project does require review by Pima County Addressing.
Thank you
Nicholas Jordan, Addressing Specialist
Pima County Development Services Department
201 N Stone AV – 1st Floor, Tucson, AZ 85701, (520) 724-9623
01/07/2020 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Denied
01/07/2020 JOHN VAN WINKLE ENGINEERING REVIEW Denied DP20-0003 (ok to submit)

This project proposes a new structure within the erosion hazard set back of the Santa Cruz River. Placement of a permanent occupied structure is not permitted according to City Code. The City of Tucson Standards Manual for Drainage Design, section 7.6 gives criteria to reduce an erosion hazard setback.
1. A detailed sediment-transport analysis, prepared by an Arizona Registered Professional Civil Engineer or,
2. The Allowable-Velocity Approach, Tractive-Stress Approach, or Tractive-Power Approach, any or all of which must indicate that the channel banks are not erosive for the flow conditions associated with the runoff events up to and including a 100-year flood on the affected watercourse
The drainage report needs to be expanded to use one of the above methods to determine if the 1220' erosion hazard setback may be reduced prior to the plans being accepted for review

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
01/07/2020 STEVE SHIELDS ZONING REVIEW Needs Review