Permit Number: DP20-0001
Parcel: 115151080

Address:
511 W PLATA ST

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP20-0001
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2020 SBEASLE1 START PLANS SUBMITTED Completed
01/28/2020 LSHAMIS1 ZONING REVIEW Reqs Change CDRC TRANSMITTAL
TO: Development Services Department
Plans Coordination Office
FROM: Loran Shamis
PDSD Zoning Review Section
PROJECT: Silver Street Warehouse Building Addition
525 W Plata St.
Development Package (1st Review)
DP20-0001
TRANSMITTAL DATE: January 28, 2020
DUE DATE: February 4, 2020
COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.
Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is January 2, 2020.
SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
CONTENT REQUIREMENTS
1. 2-06.4.2.B - Revise the legal description of the project within the title block - the project site appears to encompass lots 1, 2, 3, 4, 5, and 6 of block 11 based on the subdivision map.
2. 2-06.4.3 - Provide the development package case number, DP20-0001, adjacent to the title block on each sheet.
3. 2-06.4.4.B - Revise the location map to include the regional watercourses (Santa Cruz River) within the square mile of the subject property.
GENERAL NOTES (2-06.4.7)
Zoning and Land Use Notes
4. 2-06.4.7.A.4 - The proposed use of the property is Commercial Storage. Include in the note subject to UDC Sections 4.9.10.A and 4.9.13.Q.
5. 2-06.4.7.A.6.a - Indicate the Tenant Improvement and Temp Certificate of Occupancy case numbers, T19CM04511 and T19CM04512. (the structure on the east parcel must be reviewed and approved prior to demolition through an HPZ review)
6. 2-06.4.7.A.6.b - Pima County Parcel Tax Combo prior DP approval in order to build one structure on both parcels.
For Development Package Documents Provide (2-06.4.7.A.8)
7. 2-06.4.7.A.8.c - Include the percentage of building and vehicular use area expansion.
Existing Site Conditions (2-06.4.8)
8. 2-06.4.8.B - Demonstrate all easements on the plan if applicable, including recordation information, location, width, and purpose of all easements.
Information on Proposed Development (2-06.4.9)
9. 2-06.4.9.H.5 - The backup spur does not comply with Section 7.4.6, Motor Vehicle Use Area Design Criteria of the UDC; The backup spur needs to be redesigned per this section
10. 2-06.4.9.H.5.a - The bottom of the physically-disabled parking space van-accessible sign must be a minimum of 7 feet above the ground. The proposed plans demonstrate the bottom of the van-accessible sign is below the stated 84" (7'). Show the location of the sign for the handicap sign.
11. 2-06.4.9.H.5.d - Indicate where the long-term bicycle parking will be located. Clarify that the long-term bicycle parking is weather protected, the signage and lighting plan per UDC Section 7.4.9.D, Long-term Bicycle Parking.
12. 2-06.4.9.L - If applicable, add general note indicating location of any proposed easements.
13. 2-06.4.9.O - Provide setback dimension from Plata Street, the setback is based on the 21' or the height of the of the proposed exterior building wall, whichever greater, from the nearest edge of travel lane.
14. 2-06.4.9.Q - Provide the dimensional length, square footage and the height of each structure and the specific use proposed (Commercial Storage) within the footprint of the buildings.
15. 2-06.4.9.Q - Revise the maximum allowable height for I-1 to 75', per UDC, Section 6.3-5.A, Dimensional Standards for the P-1, I-1, and I-2 Zones.
16. 2-06.4.9.T - Provide location of refuse collection areas, including locations of dumpsters, screening locations and materials, and vehicle maneuverability, fully dimensioned, and access route. If dumpster service is not proposed, indicate the type of service.
17. 2-06.4.9.V - Indicate where mail will be delivered.
18. 2-06.4.9.W - Add note indicating the location and types of proposed signs, will be permitted under separate permit application.
***For additional information on the any standard presented in this memo, please refer to the City of Tucson "Unified Development Code" - Administrative Manual Section 2-06 or Technical Standards noted in the comments. https://www.tucsonaz.gov/pdsd/all-codes-plans-determinations
If you have any questions about this transmittal, Contact Loran Shamis by email Loran.Shamis@tucsonaz.gov or contact Steve Shields at (520) 837-4956 or email Steve.Shields@tucsonaz.gov
RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
01/29/2020 LSHAMIS1 ZONING HC REVIEW Reqs Change See zoning review comments.
01/30/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify the FFE values for the existing and proposed buildings - they appear to be about 100-feet below the street level.
2. If the rim elevation of the upstream cleanout (9460*40) in the public sewer is less than 12" below the FFE of the proposed building, provide a note on the plans requiring the installation of a backwater valve when future plumbing activities take place. Reference: Section 714.1, IPC 2018, as amended by the City of Tucson.
02/03/2020 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS

4.1 Identification and Descriptive Data
All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

The Development Package will contain the following identification in the lower right corner of each sheet:

Any relevant case numbers for reviews or modifications that affect the site.

Add Case # DP20-0001.

ARTICLE 7: DEVELOPMENT STANDARDS
7.6. LANDSCAPING AND SCREENING

7.6.2. APPLICABILITY
The provisions of this section apply to the following:
A. All new development; and,
B. Expansion of existing development, as provided below:
1. Buildings Greater Than 10,000 Square Feet

If the expansion is 25% or greater or if expansions as of February 15, 1991, cumulatively result in a 25% or greater expansion in land area, floor area, lot coverage, or vehicular use area, the standards of this section apply to the entire site.

Show compliance with landscaping and screening requirements by locations, material descriptions, and dimensions for the entire site.

Street Landscape Borders

Minimum Width

Street landscape borders must be a minimum of ten feet wide as measured from the street property line. On streets designated as Major Streets and Routes (MS&R), the street landscape border must be measured from the future MS&R right-of-way line as determined by Section 5.4.4

Provide permission for use of ROW

Ensure that all Zoning and Engineering comments and concerns are addressed.

Additional comments may apply.
02/05/2020 SBEASLE1 PIMA COUNTY ADDRESSING Approved DP20-0001 / Silver Street Whse., 1st submittal is Approved by Pima County Addressing.
The proposed new building will retain the address 511 W Plata St.
Thank you,
Robin Freiman, Addressing Official
Pima County Development Services Department
201 N Stone AV – 1st Floor Tucson, AZ 85701, (520) 724-7570
02/05/2020 JVINCEN1 COT NON-DSD FIRE Approved
02/10/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
Your Next Steps: 1. Payment 2. Resubmittal with a Comment Response Letter

DESCRIPTION: SITE/GRADING - Silver St. Whse. building addition.

PERMIT: DP20-0001
Please include this number in the Filedrop's "Project Description" field.

FEES DUE: $ 1,697.10
Note: A payment is required before we can accept your resubmittal.
PAYMENT OPTIONS Please pay the total fees (or Review Fees at a minimum):
1. Online Payment
2. In person at the City Permit Counter (Mon-Fri, 8:00 AM to 2:00 PM)
3. By mail - a check payable to the City of Tucson (address is below), include the Activity Number

Online Payment
https://www.tucsonaz.gov/pdsd/online-resources-fees-maps-records
1. NOTE: It may take 1-2 days for complete permit information to be available online
2. Visa, MC, Discover, American Express
3. Not case-sensitive but a hyphen is needed, for example: dp19-2000
4. Enter your Permit Nbr. and click the Continue tab
5. Business/Individual Name: Leave blank
6. If any issues, try using the browser Internet Explorer

VIEW REVIEWER'S COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, left side, Activity Search, enter the Activity Number
- Permits section, click on blue tab
- Documents section, click on blue icon to the right of each document
- Reviews section, click on Review Details

YOUR NEXT STEPS: Submit the following items to the Filedrop - https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter (your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set)
3) Any other documents requested by review staff
- Filedrop: In the Project Description field, enter the Activity/Permit Number
- Name your 2nd submittal documents to start with the submittal number, for example: 2_Plan_Set

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
Attn: Permit Counter/Payments
201 N. Stone Avenue, 2nd Floor
Tucson, AZ 85701
email: COTDSDPermits@TucsonAz.gov

NOTE: All City of Tucson offices will be closed on Monday, February 17 (except for emergency services). Planning & Development Services will re-open on Tuesday: https://www.tucsonaz.gov/pdsd/contact-us-hours-service.
02/10/2020 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Show the dimension of the existing sidewalk along the frontage of the existing buildings.
2. Where the new sidewalk meets the existing, provide a transition of three longitudinal to one lateral. (TS 10-01.3.3.D.1.d)
3. Show storage and service locations for solid waste containers.
4. Explain how roof drainage between the existing building and the proposed building will be directed to the ground.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/10/2020 SBEASLE1 OUT TO CUSTOMER Completed