Permit Number: DP19-0308
Parcel: 11623144A

Address:
1007 S FREEWAY

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - DP19-0308
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2020 SBEASLE1 ZONING REVIEW Approved Approved by Steve Shields, 05/08/20 (see Okay to Submit).
05/11/2020 SBEASLE1 ENGINEERING REVIEW Reqs Change (These are review comments from Okay to Submit, 05/08/20.)

DP19-0308

1) Please confirm that the drawdown time will be less than 12 hrs, not 24 hrs as stated. Reference COT Stormwater Detention/Retention manual, section 3.5. Update the revision letter and plans accordingly
2) Confirm that the proposed construction does not impact any utilities.

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
05/11/2020 SBEASLE1 OUT TO CUSTOMER Completed