Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: DEV PKG
Permit Number - DP19-0298
Review Name: DEV PKG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2020 | IMONSHI1 | ZONING HC | REVIEW | Reqs Change | |
| 01/03/2020 | IMONSHI1 | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Iman Monshizadeh PDSD Zoning Review Section PROJECT: Village Inn Storage - 4245 E Speedway bl. Development Package (1st Review) DP19-0298 - C-2 Zoning TRANSMITTAL DATE: December 30th, 2019 DUE DATE: January 8th, 2019 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is December 3rd, 2020. SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS) COMMENT: If the storage of vehicles is a temporary use, less than two years a temporary use permit (TUP) might be applicable and eliminate the development package requirement. A TUP is good for one (1) year with an allowed one (1) year extension if interested in this process contact Mark Castro at the City of Tucson Department of Planning: Mark.Castro@tucsonaz.gov CONTENT REQUIREMENTS 2-06.4.1 - The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines. 1. COMMENT: 2-06.4.1 - Provide the email address for the architect associated with this project. 2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet. 2. COMMENT: 2-06.4.3 - Provide the development package case number, DP19-0298, adjacent to the title block on each sheet. 2-06.4.7.A.2 - List the gross area of the site/subdivision by square footage and acreage. 3. COMMENT: 2-06.4.7.A.2 - The Pima County Assessors office estimates this site to be around 39,518sf (.91 acres). Revise the square footage on the plan, if the square footage shown on the plan is more accurate ignore this comment . 2-06.4.7.A.4 - Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses . 4. COMMENT: 2-06.4.7.A.4 - Revise the use to "Vehicle Rental and Sales" on the next submittal. 2-06.4.8.B - All easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. Blanket easements should be listed in the notes, together with recordation data and their proposed status. Should an easement not be in use and be proposed for vacation or have been abandoned, so indicate. However, should the easement be in conflict with any proposed building location, vacation of the easement shall occur prior to approval of plan unless written permission from easement holder(s) is provided. 5. COMMENT: 2-06.4.8.B - If applicable, Provide the information noted by the standard above. 2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks. 6. COMMENT: 2-06.4.8.C - Provide the information noted by the standard above for both Columbus and Speedway Blvd. 2-06.4.9.H.4 - Indicate if existing streets are public or private; provide street names, widths, curbs, sidewalks, and utility locations, all fully dimensioned. 7. COMMENT: 2-06.4.9.H.4 - Indicate whether speedway and Columbus are public or private along with all applicable information shown by the standard above. 2-06.4.9.I - Show all right-of-way dedications on or abutting the site and label. If the development package documents have been prepared in conjunction with a subdivision plat or is required as a condition of approval of a review process, such as a rezoning, street dedications in accordance with the Major Streets and Routes (MS&R) Plan may be required by these processes. Projects bounded by streets having only a portion of the right-of-way width dedicated will be required to dedicate right-of-way, up to one-half, to complete the street width. Should there be any proposed street or alley vacation, provide this information. If vacation has occurred, include the recording information. 8. COMMENT: 2-06.4.9.I - Show future ROW dedications for speedway Blvd. 2-06.4.9.W - Indicate the locations and types of proposed signs (wall, free-standing, pedestal) to assure there are no conflicts with other requirements and that minimal locational requirements can be met. Indicate if there are any existing billboards on site. Compliance to the Sign Code, Chapter 3 of the Tucson Code, is required. 9. COMMENT: 2-06.4.9.W - add a general note stating all signs will be approved under a separate permit ***For additional information on the any standard presented in this memo, please refer to the City of Tucson "Unified Development Code" - Administrative Manual Section 2-06 or Technical Standards noted in the comments. https://www.tucsonaz.gov/pdsd/all-codes-plans-determinations If you have any questions about this transmittal, Contact Iman Monshizadeh at (520) 837-4082 or by email Iman.Monshizadeh@tucsonaz.gov or contact Steve Shields at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 01/06/2020 | ANDREW CONNOR | LANDSCAPE | REVIEW | Reqs Change | ADMINISTRATIVE MANUAL SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS 4.1 Identification and Descriptive Data A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan. The development package will contain the following identification in the lower right corner of each sheet: Any relevant case numbers for reviews or modifications that affect the site. Provide Case # DP19-0298 on each sheet. Ensure that Zoning and Engineering comments are addressed prior to landscape section approval. Additional comments may apply |
| 01/09/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 01/10/2020 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | DP19-0298 1) Show on plans the dimension between the western most parking spaces and the new North-South Running fence. Minimum required dimension is 24' 2) The eastern most existing curb along speedway cut just will need to be closed off if it is being abandoned. Reference Tucson City code section 25-43. Please show on details the necessary new curb that will be installed according to PAG standard detail 209 3) Show that the existing trash enclosure is not being used by any surrounding properties, if so indicate how access will continue to be provided 4) Provide onsite service vehicle maneuvering area for the proposed trash enclosure according to TSM section 8 5) Show on plans dimensions for the proposed site visibility triangles John Van Winkle, P.E. John.VanWinkle@tucsonaz.gov 520-837-5007 |
| 01/10/2020 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | PLAN RETURNED FOR CORRECTIONS NOTICE A resubmittal with a Comment Response Letter is required. Description: SITE - Village Inn, storage lot, paving, fencing, landscaping. Permit/Activity Number: DP19-0298 Please include this number on all future correspondence. Fee Balance: $0 (zero) View documents and reviewer's comments on PRO: www.tucsonaz.gov/pro (If information is not available, check back later after data transfers to PRO.) - Home page, left side, Activity Search, enter the Activity Number - Permits section, click on blue tab - Documents section, click on blue icon to the right of each document - Reviews section, click on Review Details YOUR NEXT STEPS: Submit the following items to the Filedrop - https://www.tucsonaz.gov/file-upload-pdsd - In the Project Description field, enter the Activity Number - Name your 2nd submittal documents accordingly, for example: 2_Plan_Set 1) Comment Response Letter (your response to the reviewer's Requires Change comments) 2) Plan Set (all pages, full set) 3) Any other documents requested by review staff Thank you. Sharon Beasley, Permit Specialist City of Tucson Planning and Development Services Attn: Permit Counter/Payments 201 N. Stone Avenue, 2nd Floor Tucson, AZ 85701 email: COTDSDPermits@TucsonAz.gov |
| 12/09/2019 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 12/13/2019 | MASHFOR1 | COT NON-DSD | FIRE | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/10/2020 | SBEASLE1 | OUT TO CUSTOMER | Completed |