Permit Number - DP19-0293
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2020 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved Regional Traffic Engineering has no comments on this submittal and supports this submittal. The proposed development location will have no impact to any nearby ADOT facilities. Thank you.
Tom J. Martinez
ADOT
TMartinez@Azdot.gov
01/06/2020 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP19-0293
1) Sheet 1: Please remove the site location image/information for the TARP WTP. This project is only for WELL SITE R-127A
2) Sheet C02. Show the width of the proposed sidewalk. If the sidewalk is new, the minimum width is 5'.
3) Sheet C02. PAG detail 206 calls for 3' between the back of curb and the proposed sidewalk. Current position of sidewalk and curb provides about 1.5' between back of curb and sidewalk. Please show on plans a dimension's driveway apron, per PAG 206. This might require repositioning of the sidewalk so that it is further away from the curb

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
01/06/2020 SBEASLE1 UTILITIES TUCSON ELECTRIC POWER Approved (The "TEP facilities map" mentioned below can be viewed online: www.TucsonAz.gov/Pro. See the "Documents" section.)

WR#6299792 January 2, 2020
SUBJECT:TARP 4965 S 13TH AVE, DP19-0293

Tucson Electric Power Company (TEP) has reviewed and approved the development plan submitted March 12/10/19. It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development.

Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, electrical load, paving off-site improvements and irrigation plans, if available include a CD with the AutoCAD version of the plans.
If easements are required, they will be secured by separate instrument. Your final plans should be sent to:
Tucson Electric Power Company
Attn: Mr. Richard Harrington
New Business Project Manager
P. O. Box 711 (OH 204)
Tucson, AZ 85702
520-917-8726
Should you have any technical questions, please contact the area Designer, Fred Quintero, at (520) 918-8758
Sincerely,
Conor Mahoney, Office Support Assistant, Design/Build
(520) 918-8388, CMahoney@SWEnergySolutions.com

cc: DSD_CDRC@tucsonaz.gov, City of Tucson (email)
F. QuinteroTucson Electric Power
01/06/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
NOTE: A resubmittal with a Comment Response Letter is required.
Permit/Activity Number: DP19-0293
Include this number on all future correspondence.

Project Description: SITE/GRADING - TARP-13th Ave, Tucson Intl Airport Area Groundwtr Remediation.

Fee Balance: $0 (zero)
View the documents and the reviewer's comments on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, left side, Activity Search, enter the Activity Number
- Permits section, click on blue tab
- Documents section, click on blue icon to the right of each document
- Reviews section, click on Review Details

Your next step: Submit the following items to the Filedrop- https://www.tucsonaz.gov/file-upload-pdsd
(In the Project Description field, enter the Activity Number.)
1) Comment Response Letter (your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set)
3) Any other documents requested by review staff
4) Name your 2nd submittal documents accordingly, for example: 2_Plan_Set

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
Attn: Permit Counter/Payments
201 N. Stone Avenue, 2nd Floor
Tucson, AZ 85701
email: COTDSDPermits@TucsonAz.gov
11/29/2019 SBEASLE1 START PLANS SUBMITTED Completed
12/05/2019 SBEASLE1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Reqs Change December 5, 2019

RE: DP19-0293 TARP 13th Ave / 1st Submittal, Received November 29, 2019

Thank you for the opportunity to comment on DP19-0293 TARP 13th Ave, 1st Submittal, a development package application for an approximately 0.19 acre site, located 600 feet northeast of the intersection of West Iowa Street and South 13th Avenue. The zoning for this site is Office Zone 3 (O-3), with the proposed use being a new Tucson Water well (which is classified as a utility distribution use). The Tucson Airport Authority provided previous comments as part of an earlier submittal of the project through the Special Exception Procedure, SE-19-20.

This site is within FAA Part 77 airspace.

The Tucson Airport Authority conditionally approves the subject request contingent upon the following conditions of approval, as noted below. These conditions shall be identified in the general notes of the revised development plan.
Conditions of approval:
1. "According to the Federal Aviation Administration (FAA) Notice Criteria Tool, this project area is located in proximity to a navigation facility and could impact navigation signal reception. The project applicant shall file FAA Form 7460 with the FAA at least 45 days before construction activities begin unless FAA staff, with the Obstruction Evaluation / Airport Airspace Analysis (OE/AAA), provides the project applicant with written communication that filing FAA Form 7460 is not required. It is highly recommended that the applicant file earlier than 45 days to provide the applicant with sufficient time to respond to any concerns which are identified by the FAA. Any cranes which are used must also be identified with Form 7460. Please file Form 7460 at https://oeaaa.faa.gov/oeaaa/external/portal.jsp"

Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811.
Respectfully, Scott Robidoux, Senior Airport Planner

cc: Mike Sanders
12/06/2019 SBEASLE1 UTILITIES SOUTHWEST GAS Passed Review not required. This agency was notified for their information only.
12/06/2019 SBEASLE1 OTHER AGENCIES U. S. POST OFFICE Passed Review not required. This agency was notified for their information only.
12/06/2019 SBEASLE1 OTHER AGENCIES PIMA ASSN OF GOVTS Passed Review not required. This agency was notified for their information only.
12/11/2019 SBEASLE1 COT NON-DSD PARKS & RECREATION Approved No existing or proposed Tucson Parks and Recreation facilities are affected by this development.
Howard B. Dutt, RLA
Landscape Architect
Tucson Parks & Recreation, (520) 837-8040
Howard.Dutt@tucsonaz.gov
12/12/2019 MASHFOR1 COT NON-DSD FIRE Approved
12/17/2019 IMONSHI1 ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office
FROM: Iman Monshizadeh
PDSD Zoning Review Section
PROJECT: TARP Additional Remediation Well
Development Package (1st Review) - O-3 Zoning
DP19-0293 - 4965 S 13TH AV

CHECKLIST FOR MINOR DEVELOPMENT CHANGES TO EXISTING COMMERCIAL/INDUSTRIAL SITES

Purpose
This standard has been prepared for the purpose of informing applicants of the submittal and review requirements for minor changes to existing commercial sites to assure proper and adequate information is presented in a consistent manner, thereby providing the basis for an efficient and timely review. The minor revisions to existing commercial sites are prepared in support of applications for building permits and related reviews.

The information that is requested establishes the basis upon which the project will be approved and could affect what is required of the property in the future, should there be a proposal for expansion or for a different use of the property. This standard does not waive any applicable city regulations or codes.

Applicability
This standard shall be used for minor changes to existing commercial sites such as but not limited to; expansions less than 25% in square footage of land area, floor area, lot coverage, or vehicular use area, modification to accessible vehicle parking, parking area restripe, etc. Applicability to be determined by Zoning and/or Engineering review staff via email or at PDSD review counter.

APPLICATION SUBMITTAL REQUIREMENTS

Development Package applications are available from PDSD. Completed applications and accompanying materials shall be submitted to PDSD. Incomplete or inaccurate applications will not be accepted. The types of documents and the specific number of copies required of each of the documents are on the PDSD website or may be obtained from PDSD. Resubmittals of development packages require a comment response letter that details how all previous comments have been addressed. Provide the same number of copies of the comment response letter as plans provided.
FORMAT REQUIREMENTS

1. A title block shall be provided in the lower right quadrant of each sheet.

COMMENT: Correct the sheet number on sheet 1 to read sheet 1 of 36 on the next submittal

COMMENT: Remove all PDSD approval stamps from the Development Package

2. A small, project-location map shall be provided in the upper right corner of the cover sheet. This map shall cover approximately one square mile, be drawn at a minimum scale of three inch equals one mile, and provide the following information;

COMMENT: Revise the location maps on the cover page and provide one drawn location map showing the information noted above.

a. Show the subject property approximately centered within the one square mile area. Identify major streets within the square mile area and all streets that abut the subject property. Section, township, and range, north arrow, and the scale will be labeled.

COMMENT: Provide the information noted by the standard above on the revised location map.

3. An index of sheets in the development package shall be provided on the first sheet.

COMMENT: revise the sheet index to match the new page numbers and remove all pages not included in the development package


GENERAL NOTES
The following general notes are required. Additional notes specific to each plan are required where applicable.

4. Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses.

COMMENT: revise general note 1, C-2 is not a proposed use. The use for this site is Pollution Remediation Facilities

INFORMATION OF PROPOSED DEVELOPMENT:
The following information on the proposed project shall be shown on the drawing or added as notes.

5. All proposed easements (utility, sewer, drainage, access, etc.) are to be dimensioned and labeled as to their purposes and whether they will be public or private. The easements may have to be recorded and the recordation information added to the development package prior to approval.

COMMENT: if applicable provide the information noted by the standard above.

COMMENT: Archeological Review required for this site prior to zoning approval. Contact Allison Diehl for further information at Allison.Diehl@tucsonaz.gov

If you have any questions about this transmittal, Contact Iman Monshizadeh at (520) 837-4082 or at Iman.Monshizadeh@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
12/17/2019 IMONSHI1 ZONING HC REVIEW Reqs Change
12/18/2019 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Passed
12/23/2019 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved Change referance to work in the right of way to PAG standards not COT/Pima county.
12/26/2019 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS

4.1 Identification and Descriptive Data

All improvements and site information, such as adjacent rights-of-way and property lines, shown on the NPP/ Landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

The development package will contain the following identification in the lower right corner of each sheet:

Any relevant case numbers for reviews or modifications that affect the site.

Provide Case #'s DP19-0289 & Special Exception: T19SE00020 and SE-19-20. on each sheet.

7.6.4. LANDSCAPE STANDARDS

Landscape Borders

Located on Site

Street landscape borders must be located entirely on site, except that, if approved by the City Engineer or designee, up to five feet of the required ten foot width may be placed within the adjacent right-of-way area or within the Major Streets and Routes (MS&R) right-of-way area on MS&R streets.

Obtain permission for use of ROW.

Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.


Additional comments may apply.
12/31/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
01/06/2020 SBEASLE1 OUT TO CUSTOMER Completed