Permit Number: DP19-0289
Parcel: 14047006F

Review Status: Completed

Review Details: GRADING

Permit Number - DP19-0289
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/09/2019 ALEXANDRA HINES OTHER AGENCIES TUCSON AIRPORT AUTHORITY Passed
12/11/2019 DAVID RIVERA ZONING REVIEW Reqs Change TO: Development Services Department
Plans Coordination Office

FROM: David Rivera
PDSD Zoning Review Section

PROJECT: Stockpile - Grading plan for TAA Aerospace Parkway
Development Package (1st Review) 9385 S Country Club Road
DP19-0289 - I-2 Zoning

TRANSMITTAL DATE: December 11, 2019
DUE DATE: December 27, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is November 21, 2020.



1. COMMENT: 2-06.4.1 - List on the cover sheet the owner's contact name and email address.


2. COMMENT: 2-06.4.3 - Provide the development package case number, DP19-0289, adjacent to the title block on each sheet.

List the administrative address next to the title block of all plan sheets.

3. COMMENT: Zoning will approve the grading plan once it is approved by the PDSD Engineering and Landscape reviewers.

***For additional information on the any standard presented in this memo, please refer to the City of Tucson "Unified Development Code" - Administrative Manual Section 2-06 or Technical Standards noted in the comments. https://www.tucsonaz.gov/pdsd/all-codes-plans-determinations


If you have any questions about this transmittal, Contact David Rivera on Tuesday, or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Corrected DP package as noted above for zoning
12/24/2019 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS

4.1 Identification and Descriptive Data

All improvements and site information, such as adjacent rights-of-way and property lines, shown on the NPP/ Landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

The development package will contain the following identification in the lower right corner of each sheet:

Any relevant case numbers for reviews or modifications that affect the site.

Provide Case # DP19-0289 on each sheet.

Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.


Additional comments may apply.
12/31/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP19-0289

1) Include all standard applicable notes found in the COT Administrative Manual (AM) section 2-06, including but not limited to the hold harmless note in AM 2-06.4.7 and Drainage will remain in its natural state note
2) There is an "UNKOWN WASH" which appears to be impacted by the fill area. It flows in a northwesterly direction. Please clarify if this is a regulatory flow (100 cfs) or greater. If the wash is regulatory show the 100 year floodplain boundary
3) There are two areas that appear to not maintain existing drainage patterns. As shown on sheet 3, the flow arrow at the south-east corner, and the flow arrow at the northeast corner, will be blocked by the proposed fill pad
4) Sheet 1. Please adjust general note 22 to reflect the correct COT standards
5) Sheet 1. Remove general note 29. Reseeding bonds are no longer being supported
6) This project will require a pre-construction meeting prior to issuance of the development package permit. Project will require EOR certification prior to final inspection


John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
12/31/2019 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
NOTE: A resubmittal with a Comment Response Letter is required.

Permit/Activity Number: DP19-0289
Include this number on all future correspondence.

Project Description: GRADING/SWPPP - TAA 550 acres, Tucson Airport Authority, aerospace parkway. Onsite mass grading and stockpile.
Project Managers (City): John.VanWinkle@TucsonAz.gov and Loren.Makus@TucsonAz.gov

Fee Balance: $0 (zero)
View the documents and the reviewer's comments online: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, left side, Activity Search, enter the Activity Number
- Permits section, click on blue tab
- Documents section, click on blue icon to the right of each document
- Reviews section, click on "Review Details"

Submit the following items to the Filedrop.
In the Project Description field, enter the Activity Number.
PDSD Filedrop: https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter (your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set)
3) Any other documents requested by review staff
4) Name your 2nd submittal documents accordingly, for example: 2_Plan_Set

Thank you.
Sharon Beasley, Permit Specialist

NOTE: All City of Tucson offices will be closed on Wednesday, January 1 (except for emergency services). Planning & Development Services will be open normal business hours on Thursday and Friday: https://www.tucsonaz.gov/pdsd/contact-us-hours-service.

City of Tucson
Planning and Development Services
Attn: Permit Counter/Payments
201 N. Stone Avenue, 2nd Floor
Tucson, AZ 85701
email: COTDSDPermits@TucsonAz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
12/31/2019 SBEASLE1 OUT TO CUSTOMER Completed