Permit Number: DP19-0287
Parcel: 13409018F

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP19-0287
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2020 SBEASLE1 START PLANS SUBMITTED Completed
01/30/2020 IMONSHI1 ZONING REVIEW Approved
01/30/2020 IMONSHI1 ZONING HC REVIEW Approved
02/12/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the site drawing to include the following existing utility information:
a. The location and size of sanitary sewers including the pipe diameter and the invert and rim elevations of all manholes and cleanouts; along with the Pima County Wastewater Management Department (PCWMD) reference number.
b. The first floor elevation for the building
Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2018
02/13/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE - See Plumbing comments
Your Next Steps: Resubmittal with a Comment Response Letter

NOTE: All City of Tucson offices will be closed on Monday, February 17 (except for emergency services). Planning & Development Services will re-open on Tuesday: https://www.tucsonaz.gov/pdsd/contact-us-hours-service.

DESCRIPTION: SITE - Watermill Express, replace un-manned ice kiosk.

PERMIT: DP19-0287
For faster service, please include this number in the Filedrop's "Project Description" field.
FEE BALANCE: $0 (zero)
SEE PLUMBING REVIEWER'S COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, left side, Activity Search, enter the Activity Number
- Permits section, click on blue tab
- Documents section, click on blue icon to the right of each document
- Reviews section, click on Review Details

YOUR NEXT STEPS: Submit the following items to the Filedrop - https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter (your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set)
3) Any other documents requested by review staff
- Filedrop: In the Project Description field, enter the Activity/Permit Number
- Name your 3rd submittal documents to start with the submittal number, for example: 3_Plan_Set

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
Attn: Permit Counter/Payments
201 N. Stone Avenue, 2nd Floor
Tucson, AZ 85701
email: COTDSDPermits@TucsonAz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
02/13/2020 SBEASLE1 OUT TO CUSTOMER Completed