Permit Number: DP19-0287
Parcel: 13409018F

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP19-0287
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
NOTE: A resubmittal with a Comment Response Letter is required.
Permit/Activity Number: DP19-0287
Include this number on all future correspondence.

Project Description: SITE - Watermill Express, replace un-manned ice kiosk.

Fee Balance: $0 (zero)
View the documents and the reviewer's comments on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, left side, Activity Search, enter the Activity Number
- Permits section, click on blue tab
- Documents section, click on blue icon to the right of each document
- Reviews section, click on Review Details

Submit the following items to the Filedrop.
In the Project Description field, enter the Activity Number.
PDSD Filedrop: https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter (your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set)
3) Any other documents requested by review staff
4) Name your 2nd submittal documents accordingly, for example: 2_Plan_Set

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
Attn: Permit Counter/Payments
201 N. Stone Avenue, 2nd Floor
Tucson, AZ 85701
email: COTDSDPermits@TucsonAz.gov
11/27/2019 SBEASLE1 START PLANS SUBMITTED Completed
12/10/2019 SAMUEL ROGERS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office
FROM: Samuel Rogers - Planner
PDSD Zoning Review Section
PROJECT: Watermill Express Kiosk Replacement - 8588 E. Broadway Blvd.
Development Package (1st Review)
DP19-0287

CHECKLIST FOR MINOR DEVELOPMENT CHANGES TO EXISTING COMMERCIAL/INDUSTRIAL SITES

Purpose
This standard has been prepared for the purpose of informing applicants of the submittal and review requirements for minor changes to existing commercial sites to assure proper and adequate information is presented in a consistent manner, thereby providing the basis for an efficient and timely review. The minor revisions to existing commercial sites are prepared in support of applications for building permits and related reviews.

The information that is requested establishes the basis upon which the project will be approved and could affect what is required of the property in the future, should there be a proposal for expansion or for a different use of the property. This standard does not waive any applicable city regulations or codes.

Applicability
This standard shall be used for minor changes to existing commercial sites such as but not limited to; expansions less than 25% in square footage of land area, floor area, lot coverage, or vehicular use area, modification to accessible vehicle parking, parking area restripe, etc. Applicability to be determined by Zoning and/or Engineering review staff via email or at PDSD review counter.

APPLICATION SUBMITTAL REQUIREMENTS

Development Package applications are available from PDSD. Completed applications and accompanying materials shall be submitted to PDSD. Incomplete or inaccurate applications will not be accepted. The types of documents and the specific number of copies required of each of the documents are on the PDSD website or may be obtained from PDSD. Resubmittals of development packages require a comment response letter that details how all previous comments have been addressed. Provide the same number of copies of the comment response letter as plans provided.
FORMAT REQUIREMENTS


4. A title block shall be provided in the lower right quadrant of each sheet.

COMMENT: Strike out and add correct Page # of #. Add page


9. An index of sheets in the development package shall be provided on the first sheet.

COMMENT: Strike out non-applicable pages from street index.


CONTENT REQUIREMENTS

1. The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines.

COMMENT: Add the names and email addresses of the owner and architect to the "Project Contact Info" section.

2. The title block shall include the following information and be provided on each sheet: The proposed name of the project, or if there is no name, the proposed tenant's name. A brief legal description is to be provided. The page number and the total number of pages in the package (i.e., sheet xx of xx). The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

COMMENT: Add the following to the title block: A brief legal description is to be provided. The page number and the total number of pages in the package (i.e., sheet xx of xx). The administrative street address and relevant case numbers. Add the DP case number "DP19-0287" adjacent to the title block.

GENERAL NOTES
The following general notes are required. Additional notes specific to each plan are required where applicable.


3. Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses.

COMMENT: Add note on Sheet 2.1 that the use will be Retail Use - Water Kiosk



INFORMATION OF PROPOSED DEVELOPMENT:
The following information on the proposed project shall be shown on the drawing or added as notes.

2. Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

COMMENT: Are there any parking spaces that are proposed to be removed. If so, how many spaces are to be eliminated?


6. All applicable building setback lines, such as erosion hazard, floodplain detention/retention basins, and zoning, including sight visibility triangles, will be shown.

COMMENT: Dimension all applicable setback lines to the water kiosk on the site plan (Sheet 2.1). Provide dimension for the PAAL between the water kiosk and the parking spaces.

7. Provide the square footage and the height of each commercial, industrial, or business structure and the specific use proposed within the footprint of the building(s).

COMMENT: Provide the dimensions of the water kiosk.

8. Show on-site pedestrian circulation and refuge utilizing location and the design criteria in Section 7-01.0.0, Pedestrian Access, of the Technical Standards Manual.

COMMENT: The portion of sidewalk adjacent to the parking space must be concrete cement and physically separated from the vehicular use areas/parking spaces. Physically separated may include a raised sidewalk, extruded curb, or bollards no more than five feet apart on center, etc.. From what direction will customers access the kiosk from? Add a note indicating access location direction.

11. Indicate the locations and types of proposed signs (wall, free-standing, pedestal) to assure there are no conflicts with other requirements and that minimal locational requirements can be met. Indicate if there are any existing billboards on site. Compliance to the Sign Code, Chapter 3 of the Tucson Code, is required.

COMMENT: Add a note to Sheet 2.1 indicating that all new signage will be permitted under a separate permit application.


If you have any questions about this transmittal, Contact Iman Monshizadeh at (520) 837-4082 or at Iman.Monshizadeh@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
12/10/2019 SROGERS2 ZONING HC REVIEW Reqs Change See zoning comments
12/12/2019 MASHFOR1 COT NON-DSD FIRE Approved
12/27/2019 LOREN MAKUS ENGINEERING REVIEW Approved
12/31/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the site drawing to include the following existing utility information:
a. The location and size of sanitary sewers including the pipe diameter and the invert and rim elevations of all manholes and cleanouts; along with the Pima County Wastewater Management Department (PCWMD) reference number.
b. The points of connection to existing public sewers.
c. The first floor elevation for the building
Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2018

Final Status

Task End Date Reviewer's Name Type of Review Description
01/02/2020 SBEASLE1 OUT TO CUSTOMER Completed