Permit Number: DP19-0267
Parcel: 134264230

Address:
810 S KOLB RD

Review Status: Completed

Review Details: DEV PKG - OK TO SUBMIT

Permit Number - DP19-0267
Review Name: DEV PKG - OK TO SUBMIT
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2019 SBEASLE1 START PLANS SUBMITTED Completed
10/29/2019 SBEASLE1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Passed
10/29/2019 SBEASLE1 WWM REVIEW Passed
10/30/2019 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Section Manager

PROJECT: Villa Del Vista - Covered Parking
Development Package (1st Review)
DP19-0267

TRANSMITTAL DATE: October 30, 2019

DUE DATE: OK to Submit

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

2-06.3.0 FORMAT REQUIREMENTS

1. 2-06.3.7 - A small, project-location map shall be provided in the upper right corner of the cover sheet.

2. 2-06.3.12 - An index of sheets in the development package shall be provided on the first

CONTENT REQUIREMENTS

3. 2-06.4.1 - The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet.

4. 2-06.4.2.D - The page number and the total number of pages in the package (i.e., sheet xx of xx).

5. 2-06.4.3 - Provide the development package case number, DP19-0267, adjacent to the title block on all sheets.

6. 2-06.4.4 - The project-location map to be located on the first sheet of the development package in the upper right corner, shall cover approximately one square mile, be drawn at a minimum scale of three inch equals one mile, and provide the following information.

7. 2-06.4.4.A - Show the subject property approximately centered within the one square mile area;

8. 2-06.4.4.B - Identify major streets and regional watercourses within the square mile area and all streets that abut the subject property; and,

9. 2-06.4.4.C - Section, township, and range; section corners; north arrow; and the scale will be labeled.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

10. 2-06.4.7.A.1 - List as a general note: "Existing zoning is R-3."

11. 2-06.4.7.A.2 - List the gross area of the site/subdivision by square footage and acreage.

12. 2-06.4.7.A.4 - Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

13. 2-06.4.9.F - All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined.

14. 2-06.4.9.Q - Provide the height of the proposed covered parking within the footprint of the structure.

15. Remove the architect/engineers stamp from the plans.


If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
10/31/2019 LOREN MAKUS ENGINEERING REVIEW Reqs Change This proposed shade structure is within a City of Tucson Flood Hazard Area. A floodplain use permit is required.