Permit Number: DP19-0235
Parcel: 123122010

Address:
1000 E GRANT RD

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP19-0235
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/08/2020 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP19-0235

Previous Comment 3. Sheet 7. Provide typical dimensions for the site visibility triangles. Reference City of Tucson Technical Standards Manual section 10-01.5.0. Provide dimensioned site visbility triangles so that they can be verified

Engineering can conduct an expedited review after the above comment has been addressed

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
01/08/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
NOTE: A resubmittal with a Comment Response Letter is required.
Permit/Activity Number: DP19-0235
Please include this number on all future correspondence.

Description: SITE/GRADING/SWPPP/NPZ - Jefferson Park, COT, new Health & Heritage Park.

Manager: Alexandra.Hines@Tucsonaz.gov or (520) 837-6975
Fee Balance: $0 (zero)
View documents and reviewer's comments on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, left side, Activity Search, enter the Activity Number
- Permits section, click on blue tab
- Documents section, click on blue icon to the right of each document
- Reviews section, click on Review Details

YOUR NEXT STEPS: Submit the following items to the Filedrop - https://www.tucsonaz.gov/file-upload-pdsd
- In the Project Description field, enter the Activity Number
- Name your 3rd submittal documents accordingly, for example: 3_Plan_Set
1) Comment Response Letter (your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set)
3) Any other documents requested by review staff

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
Attn: Permit Counter/Payments
201 N. Stone Avenue, 2nd Floor
Tucson, AZ 85701
email: COTDSDPermits@TucsonAz.gov
12/04/2019 SBEASLE1 START PLANS SUBMITTED Completed
12/18/2019 IMONSHI1 ZONING REVIEW Approved
12/18/2019 IMONSHI1 ZONING HC REVIEW Approved
12/26/2019 ANDREW CONNOR LANDSCAPE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/08/2020 SBEASLE1 OUT TO CUSTOMER Completed