Permit Number: DP19-0224
Parcel: 132131020

Address:
2995 S KINO PW

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP19-0224
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/26/2019 SBEASLE1 START PLANS SUBMITTED Completed
09/26/2019 SBEASLE1 UTILITIES SOUTHWEST GAS Passed Review not required. This agency was notified for their information only.
09/26/2019 SBEASLE1 OTHER AGENCIES PIMA ASSN OF GOVTS Passed Review not required. This agency was notified for their information only.
09/26/2019 SBEASLE1 OTHER AGENCIES U. S. POST OFFICE Passed Review not required. This agency was notified for their information only.
10/03/2019 MASHFOR1 COT NON-DSD FIRE Approved
10/07/2019 IMONSHI1 ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Iman Monshizadeh
PDSD Zoning Review Section

PROJECT: Dutch Bros at The Bridges - New Food Service
Development Package (1st Review) - PAD 15
DP19-0224 - 2995 s Kino PW

TRANSMITTAL DATE: October 7th, 2019
DUE DATE: October 24th, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is September 23rd, 2020.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)


2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

1. COMMENT: 2-06.4.3 - Provide the development package case number, DP19-0224, adjacent to the title block on each sheet.


2-06.4.6 - If the project is located within the boundaries of a Planned Area Development (PAD) zone, include a reduced-scale map of the PAD on the first sheet, indicating the location of the portion being developed.

2. COMMENT: 2-06.4.6 - Provide a reduced scale map of PAD-15 on the first sheet, indicate the site location within the PAD map as noted by the standard above.


2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.


2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided.

3. COMMENT: 2-06.4.9.H.5.d - under "Parking Requirements for Food Service", Revise Long term bicycle requirements to 0. UDC standard (7.4.8.B.1.a-1) states that no long term bicycle parking is required for sites with less than 2,500 sf GFA. Add a note citing this standard under bicycle parking calculations


***For additional information on the any standard presented in this memo, please refer to the City of Tucson "Unified Development Code" - Administrative Manual Section 2-06 or Technical Standards noted in the comments. https://www.tucsonaz.gov/pdsd/all-codes-plans-determinations


If you have any questions about this transmittal, Contact Iman Monshizadeh at (520) 837-4082 or at Iman.Monshizadeh@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
10/07/2019 IMONSHI1 ZONING HC REVIEW Reqs Change
10/21/2019 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
10/22/2019 SBEASLE1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Reqs Change October 21, 2019
RE: DP19-0224 Dutch Bros at The Bridges, drive-thru coffee shop / 1st Submittal, Received September 26, 2019

Thank you for the opportunity to comment on DP19-0224, Dutch Bros at The Bridges, drive-thru coffee shop; 1st Submittal, a development package application for an approximately 0.69 acre site, located southwest of the intersection of South Campbell Avenue and East Cochise Vista. The property is zoned Planned Area Development 15 (PAD-15) with the proposed development being a commercial use as a food service.
This site is within the Tucson International Airport avigation easement requirements and public disclosure area, FAA traffic pattern airspace, and FAA Part 77 airspace.

The Tucson Airport Authority recognizes that the Avigation Easement was recording in a previous submittal; DP17-0204.

The Tucson Airport Authority conditionally approves the subject request contingent upon the following conditions of approval, as noted below. These conditions shall be identified in the general notes of the revised development plan.
Conditions of Approval:
1. "According to the Federal Aviation Administration (FAA) Notice Criteria Tool, this project area is located in proximity to a navigation facility and could impact navigation signal reception. The project applicant shall file FAA Form 7460 with the FAA at least 45 days before construction activities begin unless FAA staff, with the Obstruction Evaluation / Airport Airspace Analysis (OE/AAA), provides the project applicant with written communication that filing FAA Form 7460 is not required. It is highly recommended that the applicant file earlier than 45 days to provide the applicant with sufficient time to respond to any concerns which are identified by the FAA. Any cranes which are used must also be identified with Form 7460. Please file Form 7460 at https://oeaaa.faa.gov/oeaaa/external/portal.jsp"

Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811.
Respectfully,
Scott Robidoux, Senior Airport Planner

cc: Lisa Bowers
10/22/2019 SBEASLE1 COT NON-DSD PARKS & RECREATION Approved No existing or proposed Tucson Parks and Recreation facilities are affected by this development.

Howard B. Dutt, RLA
Landscape Architect
Tucson Parks & Recreation, (520) 837-8040
Howard.Dutt@tucsonaz.gov
10/23/2019 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS

4.1 Identification and Descriptive Data

All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

The Development Package will contain the following identification in the lower right corner of each sheet:

Any relevant case numbers for reviews or modifications that affect the site.

Add Case # DP19-0224.

Indicate graphically, where possible, compliance with conditions of PAD 15 document.

Refer to section C.2.2.C.3.f of the PAD for landscape and screening.

Screening for parking along Kino Parkway and Park Ave. shall be accomplished with a low wall.

The following information must be provided on the plans.

Screening

a. Location of screening elements;
b. Height of screening material and reference point for measurement;
c. Nature of screening material (e.g., permanent or temporary as in phased development); and,
d. Type of screening material (e.g., masonry wall, wood fence, species of plant material).

Identify screening elements on landscape plans.

Ensure that all Zoning and Engineering comments and concerns are addressed.

Additional comments may apply.
10/23/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify the address of this activity.
2. Provide the rim elevation of the next upstream sanitary manhole (it appears to be 8177-01). Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.
10/28/2019 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Completed
10/29/2019 SBEASLE1 UTILITIES TUCSON ELECTRIC POWER Approved (The "TEP facilities map" mentioned below can be viewed on: www.TucsonAz.gov/pro. See the "Documents" section)

WR#6288131 October 29, 2019
SUBJECT: Dutch Bros. at the Bridges, DP19-0224

Tucson Electric Power Company (TEP) has reviewed and approved the development plan submitted October 29, 2019. It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development.
Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer.
In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, electrical load, paving off-site improvements and irrigation plans, if available include a CD with the AutoCAD version of the plans.
If easements are required, they will be secured by separate instrument. Your final plans should be sent to:
Tucson Electric Power Company
Attn: Mr. Richard Harrington
New Business Project Manager
P. O. Box 711 (DB101)
Tucson, AZ 85702
520-917-8726
Should you have any technical questions, please contact the area Designer, Martin Rodriguez, at (520) 917-8787.
Sincerely,
Patty Lopez, Office Support Assistant, Design/Build
10/29/2019 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved Regional Traffic Engineering has no comments on this submittal and supports is acceptance. The development will have no impact to the I-10/Kino area. thank you.

Tom J. Martinez
10/30/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP19-0224

1) Sheet 1, General Note 16. Please update note to reflect that adoption of the 2018 IBC
2) Provide a pedestrian circulation connection from the proposed building to S Campbell Av. Reference TSM section 7-01.4.1.D
3) This project is part of an overall development that is greater than 1 acre. As such a SWPPP plan is required. Provide a SWPPP plan and manual on next submittal. If there is a pre-existing SWPPP that is being used, please indicate the SWPPP number on the cover sheet

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
10/30/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
- A resubmittal is required.
Permit/Activity Number: DP19-0224
Project Description: SITE/GRADING - Dutch Bros at The Bridges, drive-thru coffee shop.
Project Manager: Nicholas.Ross@TucsonAz.gov, (520) 837-4029

Fees Due: $ 2,165.71
Note: We require a payment prior to accepting a resubmittal.
Please pay the total fees (or Review Fees at a minimum):
1. Online Payment
2. In person at the City of Tucson Permit Counter (Mon-Fri, 8:00 AM to 2:00 PM)
3. By mail - a check payable to City of Tucson (address below), include the Permit Number

Online Payment (Visa, MC, Discover, American Express)
https://www.tucsonaz.gov/pdsd/online-resources-fees-maps-records
1. Total fees due: Payment portal may take 1-2 days to update and be viewable
2. Not case-sensitive but a hyphen is needed, e.g.: dp19-0000
3. Enter your Permit Nbr. and click the “Continue” tab
4. Ignore the line request for Business/Individual Name
5. If any issues, try using the browser Internet Explorer.

View the reviewer's comments: www.tucsonaz.gov/pro
(If information is not available, check back later as data transfers to PRO periodically.)
- Home page, left side, “Activity Search”, enter the Activity Number
- “Permits” section, click on blue tab
- "Reviews" section, click on "Review Details"

Submit the following items to the Filedrop. Before uploading, please enter the Activity Number in the Project Description field.
PDSD Filedrop: https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter (your response to the reviewer's “Requires changes” comments)
2) Plan Set (all pages, full set)
3) Any other documents requested by review staff
4) Name your 2nd submittal documents accordingly, for example: 2_Plan_Set

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
Attn: Permit Counter/Payments
201 N. Stone Avenue, First Floor
Tucson, AZ 85701

Final Status

Task End Date Reviewer's Name Type of Review Description
10/30/2019 SBEASLE1 OUT TO CUSTOMER Completed