Permit Review Detail
Review Status: Completed
Review Details: TENTATIVE PLAT REVIEW
Permit Number - DP19-0216
Review Name: TENTATIVE PLAT REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/11/2019 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 09/11/2019 | SBEASLE1 | UTILITIES | SOUTHWEST GAS | Passed | Review not required. This agency was notified for their information only. |
| 09/11/2019 | SBEASLE1 | OTHER AGENCIES | U. S. POST OFFICE | Passed | Review not required. This agency was notified for their information only. |
| 09/11/2019 | SBEASLE1 | OTHER AGENCIES | PIMA ASSN OF GOVTS | Passed | Review not required. This agency was notified for their information only. |
| 09/19/2019 | ZELIN CANCHOLA | COT NON-DSD | TRAFFIC | Reqs Change | September 19, 2019 ACTIVITY NUMBER: DP19-0216 PROJECT NAME: Trinity Subd PROJECT ADDRESS: 505 W Calle Alvord PROJECT REVIEWER: Zelin Canchola TDOT Resubmittal Required: The following items must be revised and added to the Development plan. 1. Show improvements within right of way according to PAG Standard details, not PC/COT (including sidewalk and ramps) 2. Key note 8 reference PAG standard details ramp should be PAG 207 Type 1 not type 2 as shown. Connect sidewalk to ramp. 3. Show existing street light pole along 12th Ave. A minimum distance of 5 feet must be maintained from new driveway If you have any questions, I can be reached at 520 837 6659 or zelin.canchola@tucsonaz.gov |
| 09/26/2019 | SROGERS2 | H/C SITE | REVIEW | Reqs Change | See zoning comments |
| 09/26/2019 | SAMUEL ROGERS | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Samuel Rogers PDSD Zoning Review Section PROJECT: Trinity Subdivision Lot 1-16 - an FLD Project Development Package (1st Review) DP19-0216 TRANSMITTAL DATE: 9/26/2019 DUE DATE: 10/9/2019 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is September 11 , 2020. SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS) Section CONTENT REQUIREMENTS 1. COMMENT: 2-06.4.2.D - There are two Sheet 6's and Sheets 7-9 indicate 8 total sheets. Revise on next submittal. 2. COMMENT: 2-06.4.3 - Provide the development package case number, DP19-0216, adjacent to the title block on each sheet. 3. COMMENT: 2-06.4.4.B - Add 6th Ave. to the project-location map. 4. COMMENT: 2-06.4.4.C - Add the southern bordering section numbers (14, 13) at the bottom of the location map. 2-06.4.7 - General Notes The following general notes are required. Additional notes specific to each plan are required where applicable. 2-06.4.7.A - Zoning and Land Use Notes 5. COMMENT: 2-06.4.7.A.4 - Amend Zoning and Land Use Note 5 to remove listed use specific standard and replace it with FLD UDC 8.7.3 6. COMMENT: 2-06.4.7.A.6 - Add the Median Sea Level of the property and the Northwest end of the 11L runway (per COT UDC section 5.6.11.A.1 the MSL for NW runway 11L is 2,575 feet.) 7. COMMENT: 2-06.4.7.A.7 - Include the subdivision plat case numbers when available. 2-06.4.8 - Existing Site Conditions 8. COMMENT: 2-06.4.8.C - Provide the recordation data for South 12th Ave. and Calle Alvord to the site plan. 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes. 9. COMMENT: 2-06.4.9.L - Provide dimensions for all utility easements. 2-06.5.0 FLEXIBLE LOT DEVELOPMENT (FLD - ADDITIONAL REQUIREMENTS) 10. COMMENT: 2-06.5.2.A - Provide the developable area calculation for the entire FLD 2-06.5.2.B - Show the maximum developable area of each lot (i.e., building footprint). 11. COMMENT: 2-06.5.2.B - Show the maximum developable area for each lot as a note. 2-06.5.3 Additional Information The following are required in addition to the requirements of the tentative plat or site plan, whichever is applicable: 2-06.5.3.A. Reduced Perimeter Yards Street perimeter yards along interior street rights-of-way and perimeter yards between interior lots may be modified in accordance with Section 8.7.3.L, Perimeter Yards on Interior Lots, of the UDC. Applicants requesting a perimeter yard reduction must indicate what the required and reduced perimeter yards are and their locations. Applicants requesting a reduced street perimeter yard must provide a written description of how the reduced yard will enhance the architectural design or the vehicular circulation in the FLD and submit a transportation statement, or if required by the Department of Transportation, a traffic impact analysis; 12. COMMENT: 2-06.5.3.A. - The interior setback should be revised to reflect the setback as 21' from the nearest edge of travel lane. 13. COMMENT: 2-06.5.3.C - Per UDC 8.7.3.F.1.g projects may be exempt from functional open space requirements if the project is 60 lots or fewer located within one-quarter of a mile of a City community park of at least 15 acres which does not require crossing an arterial roadway to reach the park. Access to the park from the site requires crossing 12th Avenue, an arterial roadway. Functional open space must be provided onsite if this project plan on continuing as an FLD. 14. COMMENT: 2-06.5.3.G.1 - Provide copies of the CC&R's on the next submittal. If you have any questions about this transmittal, Samuel Rogers at (520) 791-6932 or by email Samuel.Rogers@tucsonaz.gov or contact Steve Shields at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 09/30/2019 | ALEXANDRA HINES | DESIGN PROFESSIONAL | REVIEW | Passed | Design review per UDC 8.7.3.M from design professional not applicable. |
| 10/01/2019 | MASHFOR1 | COT NON-DSD | FIRE | Approved | |
| 10/03/2019 | ALEXANDRA HINES | UTILITIES | TUCSON ELECTRIC POWER | Reqs Change | **See attachments in documents table on PRO.** Tucson Electric Power Co., (TEP) has reviewed the development package submitted on September 11, 2019, and is unable to approve at this time. Please identify pole locations within the overhead electric lines along W. Calle Alvord and S. 12th Avenue. Electric facilities also need to be shown on the adjacent parcel to the south. TEP is proceeding with an equipment placement for this project which should be completed within the next few weeks. If you have any questions, please contact me at 520-917-8744. Thank you, Mary Burke Senior Right of Way Agent Tucson Electric Power Co. Land Resources – RC 131 3950 E. Irvington Road Tucson, AZ 85714-2114 Office - 520-917-8744 Cell - 520-401-9895 mburke@tep.com |
| 10/08/2019 | SBEASLE1 | COT NON-DSD | PARKS & RECREATION | Approved | No existing or proposed Tucson Parks and Recreation facilities are affected by this development. Howard B. Dutt, RLA Landscape Architect Tucson Parks & Recreation, (520) 837-8040 Howard.Dutt@tucsonaz.gov |
| 10/08/2019 | ANDREW CONNOR | LANDSCAPE | REVIEW | Reqs Change | ADMINISTRATIVE MANUAL 4.1 Identification and Descriptive Data All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan. The Development Package will contain the following identification. Any relevant case numbers for reviews or modifications that affect the site. Indicate Case # DP19-0216 in the lower right corner of each sheet: 8.7.3. FLEXIBLE LOT DEVELOPMENT (FLD) Landscaping, Screening and Wall Requirements 1. FLD projects shall comply with Section 7.6, Landscaping and Screening Standards, except as otherwise provided by this section. 2. Landscape plans shall incorporate water-conserving design as defined in Section 7.6.6, Use of Water, and as described in the Technical Standards Manual. 3. Water harvesting techniques shall be incorporated as part of the landscape design based on the Water Harvesting Guidance Manual prepared for the City of Tucson Transportation Department Stormwater Section. 4. Mechanical equipment, utility boxes, irrigation equipment and similar elements shall be screened from adjacent streets exterior to the project and from adjacent existing residential development. Screening shall be architecturally integrated with the overall design of the FLD. 5. If a perimeter wall is proposed along an existing public right-of-way, it shall be constructed of, or painted with, graffiti-resistant materials. The wall shall incorporate one or more of the following decorative materials: a. Tile; b. Stone; c. Brick; d. Adobe; e. A textured material such as stucco or plaster; or, f. Metal. Ensure that all Zoning and Engineering comments are addressed. Additional comments may apply. |
| 10/10/2019 | SBEASLE1 | PIMA COUNTY | ADDRESSING | Reqs Change | (The "attached plan" mentioned below can be viewed on PRO in the "Documents" section) DP19-0216 /1st Subm. for review / Trinity is being returned for corrections. Please see the attached plan for comments. Thank you Nicholas Jordan, Addressing Specialist Pima County Development Services Department 201 N Stone AV, Tucson, AZ 85701, (520) 724-9623 |
| 10/14/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 10/21/2019 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | 1. Retention and detention basins are not permitted on individual residential lots and water harvesting on individual lots cannot be credited against subdivision detention/retention requirements. (Drainage Manual 14.2.1,Stormwater Detention/Retention Manual Section 1.4, Water Harvesting Manual Appendix A) 2. With a density between 3 and 6 units per acre, 2-year threshold retention is required. 3. Since the site is within balanced basins, detention is required. 4. Consider omitting the sidewalk along the south side of the entry road with a TSMR. (TS 10-01.3.3.C.2) |
| 10/22/2019 | SBEASLE1 | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Reqs Change | The Applicant is responsible for obtaining a Water Availability Letter from Tucson Water (or Ray Water Company, if applicable). Provide the Letter in resubmittal. Mayor & Council cannot approve until water is assured. |
| 10/22/2019 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | PLAN RETURNED FOR CORRECTIONS NOTICE - A resubmittal is required Permit/Activity Number: DP19-0216 Project Description: TENTATIVE PLAT / FLD - Trinity Subd, lots 1-16. Project Manager: Elisa.Hamblin@TucsonAz.gov, (520) 837-4966 The fee balance is $0 (zero). Thank you for the payment. To view the review comments: www.tucsonaz.gov/PRO, enter the Permit/Activity Number. (If information isn't shown yet, check back later as data uploads to PRO periodically.) Submit the following items to the PDSD Filedrop: https://www.tucsonaz.gov/file-upload-pdsd. In the Project Description field, please include the Activity Number. 1) Comment Response Letter (your response to the reviewer's “Requires changes” comments) 2) Plan Set (all pages, full set) 3) Any other documents requested by review staff 4) Name your 2nd submittal documents accordingly, for example: 2_Plan_Set Thank you. Sharon Beasley, Permit Specialist City of Tucson Planning and Development Services Attn: Permit Counter/Payments 201 N. Stone Avenue, First Floor Tucson, AZ 85701 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/22/2019 | SBEASLE1 | OUT TO CUSTOMER | Completed |