Permit Review Detail
Review Status: Completed
Review Details: DEV PKG
Permit Number - DP19-0214
Review Name: DEV PKG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/11/2019 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 09/11/2019 | SBEASLE1 | UTILITIES | SOUTHWEST GAS | Passed | Review not required. This agency was notified for their information only. |
| 09/11/2019 | SBEASLE1 | OTHER AGENCIES | PIMA ASSN OF GOVTS | Passed | Review not required. This agency was notified for their information only. |
| 09/11/2019 | SBEASLE1 | OTHER AGENCIES | U. S. POST OFFICE | Passed | Review not required. This agency was notified for their information only. |
| 09/17/2019 | SAMUEL ROGERS | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Samuel Rogers PDSD Zoning Review Section PROJECT: The Bridges Sub-Area B-III Development Package (1st Review) DP19-0214 TRANSMITTAL DATE: 9/17/2019 DUE DATE: 10/09/2019 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is September 6, 2020 SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS) Section CONTENT REQUIREMENTS 2-06.4.1 - The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines. 1. COMMENT: Provide the name, mailing and email addresses, and phone number of the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents on the right half of the cover sheet 2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet. 2. COMMENT: Provide the development package case number, DP19-0214, adjacent to the title block on each sheet. 2-06.4.7 - General Notes The following general notes are required. Additional notes specific to each plan are required where applicable. 2-06.4.7.A.6 - If a plan or plat is prepared in conjunction with other applications or overlays or the parcel being developed is subject to conditions of an application processed previously, additional information must be added to the plan. Such applications and overlays include, but are not limited to: annexations; rezonings; special exceptions; Board of Adjustment variances; Design Development Options; Technical Standard Modification Request; overlays (Airport Environs Zone, Environmental Resource Zone, Gateway Corridor Zone, Hillside Development Zone, Historic Preservation Zone, Major Streets and Routes, Rio Nuevo District, Scenic Corridor Zone, WASH); Modification of Development Regulations through the Downtown Area Infill Incentive District or Rio Nuevo District; Downtown Heritage Incentive Zone; or, Design Review Board. Provide the following information on the plan. 3. COMMENT: Add any applicable conditions from other applications. 2-06.4.8 - Existing Site Conditions 2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks. COMMENT: Provide the dimensioned paving, curbs, curb cuts, and sidewalks of all existing public or private ROW. 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes. 2-06.4.9.R - Show on-site pedestrian circulation and refuge utilizing location and the design criteria in Section 7-01.0.0, Pedestrian Access, of the Technical Standards Manual. 4. COMMENT: Why are there sidewalks proposed on only one side of the private street? If you have any questions about this transmittal, Contact Samuel Rogers at (520) 837-6932 or by email samuel.rogers@tucsonaz.gov or contact Steve Shields at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 09/17/2019 | SROGERS2 | ZONING HC | REVIEW | Reqs Change | See zoning comments |
| 09/19/2019 | ZELIN CANCHOLA | COT NON-DSD | TRAFFIC | Approved | |
| 10/01/2019 | MASHFOR1 | COT NON-DSD | FIRE | Approved | |
| 10/07/2019 | ANDREW CONNOR | LANDSCAPE | REVIEW | Reqs Change | ADMINISTRATIVE MANUAL All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan. The Devlopment Package will contain the following identification in the lower right corner of each sheet: Any relevant case numbers for reviews or modifications that affect the site. Provide Case # DP19-0214 on each sheet. Indicate graphically, where possible, compliance with conditions of PAD-15 document. Specifically: C. Development Standards. 3. Landscape and Screening Requirements. f. Landscape and Screening along Kino Parkway. Ensure that all Zoning comments and concerns are addressed. Additional comments may apply. |
| 10/07/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 10/08/2019 | ALEXANDRA HINES | OTHER AGENCIES | TUCSON AIRPORT AUTHORITY | Reqs Change | October 8, 2019 RE: DP19-0214 Bridges, B-3, Site & Grading / 1st Submittal, Received September 11, 2019 Thank you for the opportunity to comment on DP19-0214, Bridges, B-3, Site & Grading; 1st Submittal, a development package application for an approximately 11.56 acre site, located southwest of the intersection of East Tucson Marketplace Boulevard and Kino Parkway. The property is zoned Planned Area Development 15 (PAD-15) and the proposed use would be future development. This site is within the Tucson International Airport avigation easement requirements and public disclosure area, and FAA traffic pattern airspace. The Tucson Airport Authority approves the proposed project. Although this project does not propose a change in plan designation or zoning the Tucson Airport Authority highly recommends the applicant add the following note into the general notes of the revised development plan. This project is located approximately 3 ½ miles north of Tucson International Airport and is within FAA traffic pattern airspace, an area which would be subject to aircraft overflight and noise due to being in close proximity to Tucson International Airport. The proposed note would provide a means of assuring that future owners and tenants of the property are aware they are in proximity an airport and further assures the continued right of the City of Tucson, Tucson Airport Authority, and all persons lawfully utilizing the Tucson International Airport the right to utilize the airspace above or near the property. This would be accomplished through the property owner recording the Avigation Easement. The Tucson Airport Authority believes the proposed note helps to support the City of Tucson Airport Environs Overlay Zone and supports Plan Tucson - Regional and Global Positioning policy 4 (RG-4). 1. "That prior to the City's approval of the development package, the property owner shall record the Avigation Easement which discloses the existence, and operational characteristics of the Tucson International Airport to future owners or tenants of the property and further conveys the right to the public to lawfully use the airspace above the property. The Avigation Easement shall be recorded in a manner with the Pima County recorder which shall document it as having title liability. The content of such documents shall be according to the form and instructions provided. The current property owner or person authorized to sign on behalf of the current property owner shall complete, sign, and record the Avigation Easement. Please record the Avigation Easement with the Pima County Recorder's Office. Once the Avigation Easement is recorded please send a complete copy of the recorded easement document to Tucson Airport Authority by either email (send to srobidoux@flytucson.com) or to the mailing address provided below. Scott Robidoux Senior Airport Planner Tucson Airport Authority 7250 South Tucson Boulevard Suite 300 Tucson, AZ 85756" Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811. Respectfully, Scott Robidoux, Senior Airport Planner Cc: Lisa Bowers |
| 10/08/2019 | SBEASLE1 | COT NON-DSD | PARKS & RECREATION | Approved | No existing or proposed Tucson Parks and Recreation facilities are affected by this development. Howard B. Dutt, RLA, Landscape Architect Tucson Parks & Recreation, (520) 837-8040 Howard.Dutt@tucsonaz.gov |
| 10/10/2019 | SBEASLE1 | UTILITIES | TUCSON ELECTRIC POWER | Reqs Change | **Attachment is viewable in documents table on PRO.** 4350 E. Irvington Road Post Office Box 711, Tucson, AZ 85702 WR# 6286724 October 7, 2019 City of Tucson Planning and Development Services Attn: Sharon Beasley, Permit Specialist 201 N. Stone Avenue, First Floor Tucson, AZ 85701 Dear Beasley SUBJECT: Bridges, B-3, site & grading DP19-0214 Tucson Electric Power Company (TEP) has reviewed the development plan submitted September 11, 2019. TEP is unable to approve the plan at this time. Not all TEP facilities are shown the on plans. In order for TEP to approve the plan, our facilities and easements must be depicted on the plans. Enclosed is a copy of a TEP facility map showing the approximate location of the existing facilities. All costs associated with the relocation of the facilities in conflict will be billable to the developer. Please revise and resubmit to the City of Tucson for TEP's review. Should you have any technical questions, please contact the area Designer, Sylvia Morales, at (520) 918-8708 should you have any questions. Sincerely, Linda Metzer, Office Support Assistant, Design/Build cc: Sharon Beasley, City of Tucson Planning and Development Services S. Morales, Tucson Electric Power |
| 10/15/2019 | TOM MARTINEZ | OTHER AGENCIES | AZ DEPT TRANSPORTATION | Approved | Regional Traffic Engineering has no comment on this submittal and supports the site and grading of the roadway plan's acceptance. Thank you. Tom J. Martinez TMartinez@Azdot.gov |
| 10/18/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | DP19-0214 1) Sheet 8. Pima County Regional Flood Control requires that the storm drain outlet be constructed within the project boundaries and not within Pima County maintained property 2) Sheet 4. Show a minimum 6' wide sidewalk along S Kino PW. Reference TSM section 10-01.4.1.A.1.a 3) Sheet 8. Cross-Section A-A shows a 5' sidewalk along both sides of the new proposed street. A sidewalk is only shown as being on the southside of the street. Clarify and update as needed. Show the sidewalk, which will not be constructed as "Future Sidewalk" 4) The drainage report and plans show 3 storm drain systems, 1 of which is to be constructed as part of this development package. The one being constructed has its inlets placed outside of the road. How will the runoff from the road be conveyed? 5) The drainage reports shows a series of curb openings along the northside of the proposed road. Clarify why they are not being constructed as part of this plan. Update the drainage report to address the proposed development in lieu of a future development which will occur under a separate plan 6) SWPPP site plan. How is sediment from the northern side of the proposed road going to be controlled? It appears that runoff generally flows south-west until it hits the proposed road. Update/add fiber roll as needed John Van Winkle, P.E. John.VanWinkle@tucsonaz.gov 520-837-5007 |
| 10/18/2019 | JOHN BEALL | COT NON-DSD | COMMUNITY PLANNING | Passed | |
| 10/21/2019 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | PLAN RETURNED FOR CORRECTIONS NOTICE - A resubmittal is required Permit/Activity Number: DP19-0214 Project Description: SITE/GRADING/SWPPP - Bridges, SubArea B-3. Fees Due: $3,505.58 Note: We require payment prior to accepting a resubmittal. Please pay the total fees (or Review Fees at a minimum): 1. Online 2. In person at the permit counter (Mon-Fri, 8:00 AM to 2:00 PM) 3. By mail - a check payable to City of Tucson, address is shown below, include the Activity Number Online Payments (Visa, MC, Discover, American Express) https://www.tucsonaz.gov/pdsd/online-resources-fees-maps-records 1. Total fees due: Payment portal may take 1-2 days to become viewable and payable 2. Not case-sensitive but a hyphen is needed, e.g.: dp19-0000 3. Enter your Permit Nbr. and click the “Continue” tab 4. Ignore the line request for Business/Individual Name 5. If any issues, try using the browser Internet Explorer. To view the review comments: www.tucsonaz.gov/PRO, enter the Permit/Activity Number. (If information isn't shown yet, check back later as data uploads to PRO periodically.) Submit the following items to the PDSD Filedrop: https://www.tucsonaz.gov/file-upload-pdsd. In the Project Description field, please include the Activity Number. 1) Comment Response Letter (your response to the reviewer's “Requires changes” comments) 2) Plan Set (all pages, full set) 3) Any other documents requested by review staff 4) Name your 2nd submittal documents accordingly, for example: 2_Plan_Set Thank you. Sharon Beasley, Permit Specialist City of Tucson Planning and Development Services Attn: Permit Counter/Payments 201 N. Stone Avenue, First Floor Tucson, AZ 85701 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/21/2019 | SBEASLE1 | OUT TO CUSTOMER | Completed |