Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2019 SBEASLE1 START PLANS SUBMITTED Completed
09/10/2019 IMONSHI1 ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Iman Monshizadeh
PDSD Zoning Review Section

PROJECT: Slope Grading Plan
Development Package (1st Review) - 4200 S Harrison Rd
DP19-0200 - SR Zoning

TRANSMITTAL DATE: September 10th, 2019
DUE DATE: September 23rd, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is August 20th, 2020.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS


CONTENT REQUIREMENTS

2-06.4.1 - The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines.

1. COMMENT: 2-06.4.1 - Provide the name of the civil engineer on the first sheet next to their information


2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

2. COMMENT: 2-06.4.3 - Provide the development package case number, DP19-0200, adjacent to the title block on each sheet.

Zoning has reviewed that plans but cannot approve at this time until engineering has reviewed and approved.




***For additional information on the any standard presented in this memo, please refer to the City of Tucson "Unified Development Code" - Administrative Manual Section 2-06 or Technical Standards noted in the comments. https://www.tucsonaz.gov/pdsd/all-codes-plans-determinations


If you have any questions about this transmittal, Contact Iman Monshizadeh at.gov at Iman.Monshizadeh@tucsonaz.gov or leave a message at (520) 791-5550 or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
09/23/2019 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS

4.1 Identification and Descriptive Data

All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

The Development Package will contain the following identification in the lower right corner of each sheet:

Any other relevant case numbers for reviews or modifications that affect the site.

Provide the Case # DP19-0200 on plans.

7.7. NATIVE PLANT PRESERVATION

7.7.3. APPLICABILITY

The provisions of this section apply to all development as listed below.


New Development

All new development proposed in the City of Tucson shall comply with the standards of this section.

Submit NPP plan or Application for Exception for review

Ensure that all Zoning and Engineering comments and concerns are addressed.

Additional comments may apply.
10/01/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP19-0200

1) Project Geotechnical Report section 4.2.3 indicates that benching should be provided on slopes greater than 5H-1V. The report does not indicate the frequency or spacing of the benches. Please clarify if benching is needed and show on plans where these will be provided. Section 4.2.3 says that Area C, A1 and A2 should be benched
2) SWPPP sheet 1. Please update the line weights for the limits of disturbance and sediment wattle. It is not clear where these lines are
3) Show on the SWPPP plan the location of any proposed fueling or fuel storage areas. Reference section 9 "Summary of Potential Pollutant Sources" SWPPP page 32 (PDF page 47)
4) Please add case number DP19-0200 to all relevant documents

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
10/02/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
- A resubmittal is required
Permit/Activity Number: DP19-0200
Project Description: GRADING / SWPPP - 4200 S. Harrison Rd, slope grading, use is closed sand and gravel pit.
Project Manager: John.VanWinkle@TucsonAz.gov, (520) 837-5007
The fee balance is $0 (zero). Thank you for your payment.
To view the review comments: www.tucsonaz.gov/PRO, enter Activity Number.
(If information isn't shown yet, check back later as data uploads to PRO periodically.)
Submit the following items to the PDSD Filedrop: https://www.tucsonaz.gov/file-upload-pdsd.
In the Project Description field, please include the Activity Number.
1) Comment Response Letter (listing your response to the reviewer's comments and the changes that were made)
2) Plan Set (all pages, full set)
3) Any other documents requested by review staff
4) Name your 2nd submittal documents accordingly, for example: 2_Plan_Set

Thank you.