Permit Review Detail
Review Status: Completed
Review Details: DEV PKG
Permit Number - DP19-0193
Review Name: DEV PKG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/21/2019 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 09/10/2019 | PAUL CAMARENA | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Iman Monshizadeh PDSD Zoning Review Section PROJECT: O'Rielly Chevrolet Commercial and Fleet Truck center Development Package (1st Review) - 4780 E 22ND ST DP19-0193 - C2 and R2 Zoning TRANSMITTAL DATE: September 6, 2019 DUE DATE: September 19, 2019 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is August 15, 2020. SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS) 2-06.3.0 FORMAT REQUIREMENTS 2-06.3.8 - The north arrow, contour interval, and scale as applicable to each sheet should be placed together in the upper right corner of each sheet. 1. COMMENT: 2-06.3.8 - Provide a north arrow and scale in the upper right hand corner on sheet 3 as noted by the standard above. 2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet. 2. COMMENT: 2-06.4.3 - Provide the development package case number, DP19-0193, adjacent to the title block on each sheet. 2-06.4.7.A.4 - Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses. 3. COMMENT: 2-06.4.7.A.4 - List the UDC sections applicable to the proposed use. Revise General Note 3 to state "The existing & proposed use of the property is vehicle rental and sale with direct vehicular access per UDC section 4.9.9.G.1&.2 2-06.4.7.A.8.a - Floor area for each building; 4. COMMENT: 2-06.4.7.A.8.a - Provide the floor area for the existing building 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes. 2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided. 5. COMMENT: 2-06.4.9.H.5.d - Provide Bicycle parking fully dimensioned as noted by the standard above. Minimum requirements for bicycle parking can be found on table 7.4.8-1 of the UDC 2-06.4.9.Q - Provide the square footage and the height of each commercial, industrial, or business structure and the specific use proposed within the footprint of the building(s). 6. COMMENT: 2-06.4.9.Q - Provide the height of the existing building. The existing structures are not permitted as of September 10th, 2019, the inspections for these structures were never completed and the latest permit is expired. The existing structures will need a C of O (certificate of occupancy) before occupancy. Contact Eric Newcomb for additional information on the C of O process. 2-06.4.9.T - Show refuse collection areas, including locations of dumpsters, screening location and materials, and vehicle maneuverability, fully dimensioned, and access route. If dumpster service is not proposed, indicate type of service. For specific information on refuse collection, refer to Section 8-01.0.0, Solid Waste and Recycle Disposal, Collection, and Storage, of the Technical Standards Manual. Refuse collection on all projects shall be designed based on that section, even if collection is to be contracted to a private firm. 7. COMMENT: 2-06.4.9.T - Provide the dimensions for the refuse collection area based on section 8-01.0.0 of the Technical Standards Manual ***For additional information on the any standard presented in this memo, please refer to the City of Tucson "Unified Development Code" - Administrative Manual Section 2-06 or Technical Standards noted in the comments. https://www.tucsonaz.gov/pdsd/all-codes-plans-determinations If you have any questions about this transmittal, Contact Iman Monshizadeh at (520) 791-5550 or by email Iman.Monshizadeh@tucsonaz.gov or contact Steve Shields at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 09/10/2019 | PCAMARE1 | ZONING HC | REVIEW | Reqs Change | See Zoning Comments |
| 09/18/2019 | ANDREW CONNOR | LANDSCAPE | REVIEW | Reqs Change | ADMINISTRATIVE MANUAL SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS 4.1 Identification and Descriptive Data All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan. The Development Package will contain the following identification in the lower right corner of each sheet: Any other relevant case numbers for reviews or modifications that affect the site. Provide the Case # DP19-0193 on plans. Ensure that all Zoning and Engineering comments and concerns are addressed. Additional comments may apply. |
| 09/19/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 09/27/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | DP19-0193 1) Show on plans the cross slope and running slope for the accessible parking spaces and the accessible pathway to the building and its connection to E 22nd st 2) TSM section 10-01.4.1.A requires a minimum 6' wide sidewalk along collector and arterial streets. Please show a minimum 6' wide sidewalk along E 22nd St 3) It does not appear that the curb access ramp at the northeast corner of the proposd project meets current standards. Please show that this curb access ramp will be update to PAG standard detail 207 4) Provide on plans waste stream calculations per TSM section 8-01.8.0 5) Provide a trash enclosure detail to meet TSM section 8, including onsite service vehicle maneuvering area, or otherwise show how trash service will be provided John Van Winkle, P.E. John.VanWinkle@tucsonaz.gov 520-837-5007 |
| 09/30/2019 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | PLAN RETURNED FOR CORRECTIONS NOTICE - A resubmittal is required Permit/Activity Number: DP19-0193 Project Description: SITE/GRADING - O'Rielly Chevrolet Truck Center. Project Manager: Samuel.Rogers@TucsonAz.gov, (520) 837-6932 Fees Due: $1,899.07 Note: We require payment prior to accepting a resubmittal. Please pay the total fees (or Review Fees at a minimum): 1. Online 2. In person at the permit counter (Mon-Fri, 8:00 AM to 2:00 PM) 3. By mail - a check payable to City of Tucson, address is shown below, include the Activity Number Online Payments (Visa, MC, Discover, American Express) https://www.tucsonaz.gov/pdsd/online-resources-fees-maps-records 1. Total fees due: Payment portal may take 1-2 days to update to the correct total 2. Not case-sensitive but a hyphen is needed, e.g.: dp19-0000 3. Enter your Permit Nbr. and click the “Continue” tab 4. If any issues, try using the browser Internet Explorer. To view the review comments: www.tucsonaz.gov/PRO, enter Activity Number. (If information isn't shown yet, check back later as data uploads to PRO periodically.) Submit the following items to the PDSD Filedrop: https://www.tucsonaz.gov/file-upload-pdsd. In the Project Description field, please include the Activity Number. 1) Comment Response Letter (listing your response to reviewer's comments) 2) Plan Set (all pages, full set) 3) Any other documents requested by review staff 4) Name your 2nd submittal documents accordingly, for example: 2_Plan_Set Thank you. Sharon Beasley, Permit Specialist City of Tucson Planning and Development Services Attn: Permit Counter/Payments 201 N. Stone Avenue, First Floor Tucson, AZ 85701 |
| 10/15/2019 | MASHFOR1 | COT NON-DSD | FIRE | Approved | Confirmation from Luis was provided on 1,400 sqft property in B use, This has been approved Please also verify with TFD (Fire) if Fire Sprinklers/Alarms will be necessary for this project.Limited information provided so please provide all information on plan sets moving forward. |
| 10/15/2019 | MASHFOR1 | COT NON-DSD | FIRE | Approved | Confirmation from Luis was provided on 1,400 sqft property in B use, This has been approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/30/2019 | SBEASLE1 | OUT TO CUSTOMER | Completed |