Permit Number: DP19-0186
Parcel: 116277720

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP19-0186
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2019 SBEASLE1 START PLANS SUBMITTED Completed
08/27/2019 PAUL CAMARENA ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: COYOTE PASS, LOT 15
Development Package (1st Review) 3167 W TUMAMOC DR
DP19-0186 - R-1 Zoning

TRANSMITTAL DATE: August 26, 2019
DUE DATE: September 05, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is August 05, 2020.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
Section

01. Zoning has reviewed the plan and cannot approve at this time. Please address the following comments.


02. Zoning cannot approve the Development Package until the Engineering Plans reviewer has approved.

Provide a residential plot plan


If you have any questions about this transmittal, Contact Paul Camarena at (520) 791-5550 or by email Paul.Camarena@tucsonaz.gov or contact Steve Shields at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
09/03/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
- A resubmittal is requested
Permit/Activity Number: DP19-0186
Description: GRADING - Coyote Pass, lot 15, SFR.
Fees Due: $903.10
Please pay the total fees (or Review Fees at a minimum):
1. Online
2. In person at the permit counter (Mon-Fri, 8:00 AM to 2:00 PM)
3. By mail - a check payable to City of Tucson, address is shown below, include the Activity Number

Online Payments:
https://www.tucsonaz.gov/pdsd/online-resources-fees-maps-records
1. Not case-sensitive but a hyphen is needed, e.g.: dp19-0000
2. Simply enter your Permit Nbr. and click the “Continue” tab
3. If any issues, try using the browser Internet Explorer.
4. Accepted: Visa, MC, Discover, or American Express
5. No fee to the customer
6. All data and transactions are securely encrypted
7. City staff cannot view your online payments

To view the review comments: www.tucsonaz.gov/PRO, enter Activity Number.
(If information isn't shown yet, check back later as data flows to PRO periodically throughout the day.)
Submit the following items to the PDSD Filedrop: https://www.tucsonaz.gov/file-upload-pdsd.
In the Project Description field, please include the Activity Number.
1) Comment Response Letter (listing your response to reviewer's comments)
2) Plan Set (all pages, full set)
3) Any other items requested by review staff
Name your 2nd submittal documents accordingly, for example: 2_Plan_Set.
Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
Attn: Permit Counter/Payments
201 N. Stone Avenue, First Floor
Tucson, AZ 85701
09/03/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP19-0186

1) Provide Hillside Development Zone Calculations to determine Average Natural Cross Slope. Show calculations on plans. Reference TSM section 9-01
2) Provide maximum allowable grade area based on average cross slope. Reference UDC Table 5.2-1. Show grading extents on plans
3) Reference TSM section 2-01.9.0. It appears that the site retaining wall is running along the property line. Provide the necessary setback from the property line
4) Show on plans any necessary subsurface drainage features, in particular drainage behind the proposed retaining wall shown in detail A on sheet 2

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
09/03/2019 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change The Development Package will contain the following identification in the lower right corner of each sheet:

Any relevant case numbers for reviews or modifications that affect the site.

Provide case # DP19-0184 on each sheet.

The site is within the following Overlay Zone

Add the following notes:

Vegetation Retention and Revegetation
a. Vegetation Retention
(1) Existing viable and transplantable trees with four inch or greater trunk diameter and cacti shall be preserved in their original locations, except for building sites and access and utilities serving building sites.
(2) When retention of the above trees and cacti in their original locations is not possible due to building site location, the trees and cacti shall be salvaged and replanted in areas requiring revegetation, whenever possible.
b. Revegetation
All cut or fill slopes that are no steeper than three horizontal to one vertical and all utility trenches or septic leaching fields that are not located in parking or driveway areas shall be revegetated in compliance with the following standards:
(1) All plants used in revegetation shall be the same as the native vegetation on the site prior to grading or clearing or any adjacent site; and,
(2) Revegetation shall be accomplished with the following minimum standards for plants:
(a) Desert trees, a minimum of 15-gallon size with a minimum trunk diameter of two inches measured at the soil level, or large specimen cactus shall be placed at the same vegetation density found on the site prior to any clearing, grubbing, or grading; and,
(b) Seeds for trees, desert shrubs, and grasses shall be planted with a density adequate to control erosion and may use one of the following methods of planting: Raked into the soil with appropriate mulch materials; hydroseeding; anchored mulches; or established on jute, rolled straw, or similar material. Another method may be approved by PDSD.
(3) A temporary watering system shall be installed until the revegetation materials are established.
3. Slope Stabilization
All slopes steeper than a ratio of three horizontal to one vertical, with the exception of retaining walls, shall be stabilized with properly engineered stone riprapping or sculptured rock as follows:
a. Stone riprapping shall be hand-placed on the slope;
b. The stabilizing material used shall blend with the natural appearance of the site or lot and the surrounding terrain; and,
c. Vegetation retention and revegetation should be used in conjunction with riprapping.


Ensure that all Engineering comments and concerns are addressed.

Additional comments may apply.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/03/2019 SBEASLE1 OUT TO CUSTOMER Completed