Permit Number: DP19-0178
Parcel: 13213075A

Address:
3010 S PARK AV

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP19-0178
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2019 SBEASLE1 START PLANS SUBMITTED Completed
07/31/2019 SBEASLE1 UTILITIES SOUTHWEST GAS Passed Review not required. This agency was notified for their information only.
07/31/2019 SBEASLE1 OTHER AGENCIES PIMA ASSN OF GOVTS Passed Review not required. This agency was notified for their information only.
07/31/2019 SBEASLE1 OTHER AGENCIES U. S. POST OFFICE Passed Review not required. This agency was notified for their information only.
08/01/2019 MARTIN BROWN COT NON-DSD FIRE Approved
08/15/2019 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved (The enclosed "TEP facilities map" mentioned here can be viewed on PRO in the "Documents" section)

WR#6282877 August 15, 2019
City of Tucson
Planning and Development Services
Attn: Sharon Beasley, Permit Specialist
201 N. Stone Avenue, First Floor
Tucson, AZ 85701
Dear Ms. Beasley:
SUBJECT: Bridges, Sub-Area, DP19-0178
Tucson Electric Power Company (TEP) has reviewed and approved the development plan submitted July 31, 2019. It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development.
There is a pole line along Park Ave going N to S on the West side of the street. Current plans do not show any conflicts with those poles/lines. Future plans for driveways may/may not be in conflict. Will determine that if/when future plans are drafted up.
Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer.
In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, electrical load, paving off-site improvements and irrigation plans, if available include a CD with the AutoCAD version of the plans.
If easements are required, they will be secured by separate instrument. Your final plans should be sent to:
Tucson Electric Power Company
Attn: Mr. Richard Harrington
New Business Project Manager
P. O. Box 711 (OH 204)
Tucson, AZ 85702
520-917-8726
Should you have any technical questions, please contact the area Designer, Freddy Quintero, at (520) 917-8758.
Sincerely,
Linda Metzer, Office Support Assistant
Design/Build
cc: F. QuinteroTucson Electric Power
08/19/2019 PAUL CAMARENA ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: The BRIDGES, SUB-AREA, B-IV
Development Package (1st Review) 3250 S PARK AV
DP19-0178

TRANSMITTAL DATE: August 16, 2019
DUE DATE: August 28, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is July 29, 2020.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
Section

2-06.3.0 FORMAT REQUIREMENTS


2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

1. COMMENT: Provide the development package case number, DP19-0178, adjacent to the title block on each sheet.


2-06.4.6 - If the project is located within the boundaries of a Planned Area Development (PAD) zone, include a reduced-scale map of the PAD on the first sheet, indicating the location of the portion being developed.

2. COMMENT: Provide a map of the PAD on the cover sheet as noted by the standard above.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes




2-06.4.7.A.4 - Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses.

3. COMMENT: Provide the existing use of the property as noted by the standard above




If you have any questions about this transmittal, Contact Paul Camarena at (520) 791-5550 or by email Paul.Camarena@tucsonaz.gov or contact Steve Shields at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
08/19/2019 PCAMARE1 ZONING HC REVIEW Approved
08/26/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The first floor elevation of the proposed 2-story building is less than 12" above the rim elevation of the next upstream sanitary manhole. Provide a note on the plans requiring the installation of a backwater valve when future plumbing activities take place. Plumbing fixtures located on the second floor of the building shall not discharge through the backwater valve. Reference: Section 714.1, IPC 2018, as amended by the City of Tucson.
08/26/2019 SBEASLE1 COT NON-DSD PARKS & RECREATION Approved Tucson Parks and Recreation recommends approval of this Site/Grading Plan.

Howard B. Dutt, RLA
Landscape Architect
Tucson Parks & Recreation, (520) 837-8040
Howard.Dutt@tucsonaz.gov
08/26/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP19-0178

1) SWPPP plan sheet. Show appropriate controls needed to prevent sediment from entering into the proposed storm drain system and along the boundary of the detention/retention basin
2) Sheet 12. Suggest providing a graded area suitable for future sidewalk along the northern side of the proposed street cross section
3) Roundabout at the western end of the proposed street is a good opportunity for water harvesting. Provide curb cut inlet details and spot grades as needed according to UDC section 7.6.6.C. Also the center landscaped islands in the proposed street can be designed to accept rain water

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
08/27/2019 SBEASLE1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Approved August 27, 2019

RE: DP19-0178 Bridges, Sub-Area, 1st Submittal, Received July 31, 2019

Thank you for the opportunity to comment on DP19-0178, Bridges, Sub-Area; 1st Submittal, a development package application for an approximately 2.0 acre site, located west of the intersection of East Tucson Marketplace Boulevard and South Park Avenue. The property is zoned Planned Area Development 15 (PAD-15) and the proposed development is infrastructure for future commercial development.
The Tucson Airport Authority provided previous comments during the proposed vertical construction portion of the project, DP19-0093. The Tucson Airport Authority is satisfied with the 1st submittal of this project and has no additional comments to provide.
Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811.
Respectfully,
Scott Robidoux, Senior Airport Planner

Cc: Lisa Bowers
08/27/2019 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change The Development Package will contain the following identification in the lower right corner of each sheet:

Any relevant case numbers for reviews or modifications that affect the site.

Provide the development package case number, DP19-0178.

If applicable, indicate graphically, where possible, compliance with conditions of the PAD document.

Provide a map of the PAD on the cover sheet.

Ensure that all Zoning and Engineering comments and concerns are addressed.
08/27/2019 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
08/28/2019 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Passed Building and land use proposal is covered under separate development package review.
08/28/2019 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Passed The buildings are covered under separate development packages.
08/29/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
- A resubmittal is required
Permit/Activity Number: DP19-0178
Description: SITE/GRADING - Bridges, Sub-Area B-4. Initial infrastructure.
Project Manager: Steve.Shields@TucsonAz.gov, (520) 837-4956
Fees Due: $4,554.36
Please pay the total fees (or Review Fees at a minimum):
1. Online
2. In person at the permit counter (Mon-Fri, 8:00 AM to 2:00 PM)
3. By mail - a check payable to City of Tucson, address is shown below, include the Activity Number

NEW: Online payments are now accepted.
1. Visa, MC, Discover, or American Express
2. No cost to the customer
3. All data and transactions are securely encrypted
4. City staff cannot view your online payments

Link to Online Payments:
https://www.tucsonaz.gov/pdsd/online-resources-fees-maps-records
1. Not case-sensitive but a hyphen is needed, e.g.: dp19-0000
2. Simply enter your Permit Nbr. and click the “Continue” tab
3. If any issues, try using the browser Internet Explorer.

To view the review comments: www.tucsonaz.gov/PRO, enter Activity Number.
(If information isn't shown yet, check back later as data flows to PRO periodically throughout the day.)
Submit the following items to the PDSD Filedrop: https://www.tucsonaz.gov/file-upload-pdsd.
In the Project Description field, please include the Activity Number.
1) Comment Response Letter (listing your response to reviewer's comments)
2) Plan Set (all pages, full set)
3) Any other items requested by review staff
Name your 2nd submittal documents accordingly, for example: 2_Plan_Set.
Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
Attn: Permit Counter/Payments
201 N. Stone Avenue, First Floor
Tucson, AZ 85701

Final Status

Task End Date Reviewer's Name Type of Review Description
08/29/2019 SBEASLE1 OUT TO CUSTOMER Completed