Permit Number: DP19-0173
Parcel: 12419022B

Address:
1635 E 18TH ST

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP19-0173
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2019 SBEASLE1 START PLANS SUBMITTED Completed
11/05/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the site drawing to include the following existing utility information:
a. The rim elevations of the upstream and downstream manholes along with the Pima County Wastewater Management Department (PCWMD) reference numbers.
b. The first floor elevation for the building
Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2018.
11/05/2019 ANDREW CONNOR LANDSCAPE REVIEW Approved
11/06/2019 STEVE SHIELDS ZONING REVIEW Approved
11/06/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP19-0173

1) Previous Comment 6. Show on plans ADA compliant parking spaces and connection to the existing building through which access is provided to the proposed expansion. Show all applicable details for cross slope and running slope showing that the pathway and parking spaces meet ICC A117. Show on plans the cross slope and running slope for all accessible pathways and parking spaces
2) The new additional accessible parking space requires ADA signage. Show on plans a standard accessible parking space signage detail. Note that minimum clearance from finished grade to lowest sign is 84". Reference City of Tucson (COT) Technical Standards Manual (TSM) section 7-01.4.3
3) TSM section 7-01.4.1.F. Sidewalks or pedestrian refuge areas cannot be located between any motor vehicle parking space and the Parking Area Access Lane (PAAL) providing access to that space. In previous discussions, the 2 parking spaces below Keynote 20 were going to be removed in order to eliminate this conflict. Relocate/remove the 2 parking spaces or reconfigure the hatched pathway running north south which joins the new concrete sidewalk to the east-west running pedestrian path such that it does not run behind any parking spaces
4) The new proposed ramp identified in keynote 19. The keynote says that the ramp is flanked by 8" tall curbs. Clarify the height of the ramp. Maximum ramp height can be 6" only without a handrail being required

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
11/06/2019 SSHIELD1 ZONING HC REVIEW Approved
11/07/2019 SBEASLE1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Reqs Change November 6, 2019

RE: DP19-0173 Imarx Investments, cleanroom addition to existing building / 2nd Submittal, Received November 5, 2019

Thank you for the opportunity to comment on DP19-0173, Imarx Investments, cleanroom addition to existing building; 2nd Submittal, a development package application for an approximately 1.37 acre site, with the proposed expansion of the new structure being approximately 1,400 sq ft, which is located northwest of the intersection of South Warren Avenue and East 18th Street. The property is zoned Industrial Zone 1 (I-1) with the proposed development being the expansion of an existing industrial building.
This site is within the Tucson International Airport avigation easement requirements and public disclosure area, FAA traffic pattern airspace, and FAA Part 77 airspace.
The Tucson Airport Authority acknowledges that the Avigation Easement has been recorded for this project under sequence 20192970696.
The Tucson Airport Authority conditionally approves the subject request contingent upon the following conditions of approval, as noted below. This condition of approval shall be identified in the general notes of the revised development plan unless FAA staff, with the Obstruction Evaluation / Airport Airspace Analysis (OE/AAA), provides the project applicant with written communication that filing FAA Form 7460 is not required.

Condition of approval:
1. "According to the Federal Aviation Administration (FAA) Notice Criteria Tool, this project area is located in proximity to a navigation facility and could impact navigation signal reception. The project applicant shall file FAA Form 7460 with the FAA at least 45 days before construction activities begin unless FAA staff, with the Obstruction Evaluation / Airport Airspace Analysis (OE/AAA), provides the project applicant with written communication that filing FAA Form 7460 is not required. It is highly recommended that the applicant file earlier than 45 days to provide the applicant with sufficient time to respond to any concerns which are identified by the FAA. Any cranes which are used must also be identified with Form 7460. Please file Form 7460 at https://oeaaa.faa.gov/oeaaa/external/portal.jsp"

Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811.
Respectfully,
Scott Robidoux, Senior Airport Planner

cc: LeoJMiller@msn.com
11/07/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
- A resubmittal is required.
Permit/Activity Number: DP19-0173 Please include this number on all future correspondence.
Project Description: SITE - Imarx Investments, cleanroom addition to existing building.

Fee Balance: $0 (zero). Thank you for the payment.
View the documents and the reviewer's comments: www.tucsonaz.gov/pro
(If information is not available, check back later as data transfers to PRO periodically.)
- Home page, left side, “Activity Search”, enter the Activity Number
- “Permits” section, click on blue tab
- “Documents” section, click on blue icon to the right of each document
- "Reviews" section, click on "Review Details"

Submit the following items to the Filedrop. In the Project Description field, enter the Activity Number.
PDSD Filedrop: https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter (your response to the reviewer's “Requires changes” comments)
2) Plan Set (all pages, full set)
3) Any other documents requested by review staff
4) Name your 3rd submittal documents accordingly, for example: 3_Plan_Set

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
Attn: Permit Counter/Payments
201 N. Stone Avenue, First Floor
Tucson, AZ 85701

Final Status

Task End Date Reviewer's Name Type of Review Description
11/07/2019 SBEASLE1 OUT TO CUSTOMER Completed