Permit Number: DP19-0164
Parcel: 136080310

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - DP19-0164
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2020 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Site Section Manager

PROJECT: Northwest Medical Center Medical Office Building Addition
Development Package (1st Revision)
DP19-0164

TRANSMITTAL DATE: September 25, 2020

DUE DATE: September 23, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. 2-06.4.3 - Provide the Development Package case number, DP20-0, adjacent to the title block on all sheets.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

2. 2-06.4.9.H.5.a - The required number of vehicle parking spaces shown for the Medical Office is not correct, 46,220 / 200 = 231 spaces required.

3. 2-06.4.9.H.5.a - The required number of accessible vehicle parking spaces shown for the Medical Office is not correct and should be 7 with 2 being van accessible.

4. 2-06.4.9.H.5.d - The required number of short-term bicycle parking spaces is not correct and should be 9, see UDC Article 7.4.3.G.

5. 2-06.4.9.R - There are 5 vehicle parking spaces located near the southwest corner of the proposed building. The vehicle parking space are allowed to overhang a proposed sidewalk. This sidewalk is required to be a minimum 6'-6" to allow for a 4' clear sidewalk of wheel stops must be provided.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
09/30/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/30/2020 ANDREW CONNOR LANDSCAPE REVIEW Approved
09/30/2020 SBEASLE1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Approved DP19-0164 / NW Medical / Revision Request is Approved by Pima County Addressing.

Please note the address for the Northwest Medical Center hospital is 2200 S Houghton Rd and the address for the Medical Office Building is 2300 S Houghton Rd.

Robin Freiman, Addressing Official
Pima County Development Services Department
201 N Stone AV – 1st Floor
Tucson, AZ 85701
(520) 724-7570
09/30/2020 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
09/30/2020 GDAURIA1 COT NON-DSD FIRE Completed *
09/30/2020 JANE DUARTE COT NON-DSD PARKS & RECREATION Approved No existing or proposed Tucson Parks and Recreation facilities are affected by these revisions.

Howard B. Dutt, RLA, Landscape Architect
Tucson Parks and Recreation, (520) 837-8040
10/02/2020 SBLOOD1 ENGINEERING REVIEW Reqs Change 1. Sheet C 04.03 - Ensure that all keynote K labels are pointing in the right spots. Bottom left retention/detention area has a few pointing to nothing.

2. Sheet C 04.03 - Entrance at new MOB max bollard spacing is 5’. Update bollard count as needed.

3. Sheet C 04.03 - Clarify that there is sufficient maneuvering space around the accessible entrance on west side of new MOB per ICC A17 code.

4. Provide waste stream calculations on plans per TSM section 8-01.8.0

Stephen Blood
stephen.blood@tucsonaz.gov
Please update the proposed trash enclosure to be constructed according to TSM section 8
10/22/2020 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change DATE: Oct. 22, 2020
REVISION PLAN RETURNED FOR CORRECTIONS NOTICE
- A resubmittal is required

PROJECT DESCRIPTION: SITE/GRADING/SWPPP - Northwest Medical Ctr - Houghton

PERMIT: DP19-0164
Project Manager: Samuel.Rogers@TucsonAz.gov
FEE BALANCE: $0 (zero) Thank you for the payment

VIEW the review comments and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

After the corrections are made, please name your Revision #1, 2nd submittal documents accordingly, for example: REV-1_2_Plan_Set.

YOUR NEXT STEPS: Submit documents to the Filedrop
https://www.tucsonaz.gov/file-upload-pdsd

IMPORTANT: Select the Submission Type "Site Review/CDRC..."

1) Comment Response Letter (your response to the reviewer's Requires changes comments)
2) Plan Set (or individual sheets)
3) Any other items requested by review staff

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov
10/23/2020 SBEASLE1 UTILITIES TUCSON ELECTRIC POWER Approved DP19-0164 / NW Medical / Revision Request is Approved by Pima County Addressing.

Please note the address for the Northwest Medical Center hospital is 2200 S Houghton Rd and the address for the Medical Office Building is 2300 S Houghton Rd.

Thank you,
Robin Freiman, Addressing Official

Pima County Development Services Department
201 N Stone AV – 1st Floor
Tucson, AZ 85701
(520) 724-7570