Permit Number: DP19-0164
Parcel: 136080310

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP19-0164
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2019 SBEASLE1 START PLANS SUBMITTED Completed
10/21/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a note on the civil utility plans requiring the installation of a backwater valve for the building drain from the powerhouse. [Initial comment: The FFE for the powerhouse is less than 12" above the rim elevation of manhole MH-4. Provide a backwater valve for the building drain from the powerhouse. Reference: Section 714.1, IPC 2018 as amended by the City of Tucson.]
10/21/2019 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Approved DP19-0164 / NW Medical / 2nd submittal is being Approved by Pima County Addressing.
Thank you,
Robin Freiman, Addressing Official
Pima County Development Services Department
201 N Stone AV – 4th Floor Tucson, AZ 85701
(520) 724-7570
10/21/2019 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved Both design engineers, Kimley Horn and Psomas, should closely coordinate their projects so the new SR1J Houghton Rd, 22nd St to Irvington Rd segment roadway improvements (planned contractor bidding January 2021, Construction start April 2021) will dovetail right into the new NW Medical Center improvements
10/22/2019 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

4.1 Identification and Descriptive Data

All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

Remove any clouded sections on all sheets prior to approval of Development Package.

Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.


Additional comments may apply upon subsequent reviews.
10/24/2019 SROGERS2 ZONING HC REVIEW Reqs Change See zoning comments
10/24/2019 SAMUEL ROGERS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Samuel Rogers - Planner
PDSD Zoning Review Section

PROJECT: Northwest Medical Center - Houghton
2200 S Houghton Rd
Development Package (2nd Review)
DP19-0164

TRANSMITTAL DATE: 10/24/2019
DUE DATE: 10/22/2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is June, 6th 2020.

2-06.3.8 - Add the contour interval in the upper right corner of the grading sheets.


2-06.4.2.C - Lot split must be approved prior to development package approval. New lot configuration should be shown on cover sheet. Lost split application S19-046 is in "RFC" (Return for Corrections) status, lot split must be in "Final" status before approval of the DP.


2-06.4.7.A.4 - List all UDC sections applicable to the proposed uses. Proposed use is Commercial: Medical Service - Major. Add proposed based on the PAD-25 (Medical Service - Major) use to the General Notes section.


2-06.4.7.A.8.a - Add information as a general note with the floor area for each building. It is acknowledged this information has been provided in a table on sheet 9 of 33.


2-06.4.8.C - Show current and future curb dimensions and locations on Old Spanish Trail


\2-06.4.9.B - This comment appears to not have been addressed. Comment response state information is on sheet C01.00, however the information was not present on that sheet. Identify each block or lot by number within the PAD and include the approximate square footage of each.


2-06.4.9.H.2 - Confirm with engineering that the future and existing sight visibility triangles are correct.


2-06.4.9.I - Clarify if dedication process has been approved/submitted. When will dedication occur?


2-06.4.9.L - Is the 15' Water Easement on the East side of the property existing or proposed? The easement must be recorded prior to the approval of the DP.


2-06.4.9.S - Show future sidewalk along Old Spanish Trail if required by TDOT.



44. General comment - per the Minor Amendment letter dated 11/28/18 and the letter dated 2/22/19, an updated

45. COMMENT: Remove all deltas and clouds from the plan sheets.



If you have any questions about this transmittal, Contact Samuel Rogers at (520) 837-6932 or by email Samuel.Rogers@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
10/25/2019 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Approved
10/28/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP19-0164

1) Previous comment 2. This comment was not addressed. Please update contact information on cover sheet for both Engineering/Stormwater and the Building Department
2) Previous comment 4. This comment was not addressed. Detectable warnings are required at all curb access ramps and transitions. Reference ICC A117.1 section 406.6

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
10/30/2019 MARTIN BROWN COT NON-DSD FIRE Approved
10/30/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
- A resubmittal is required.
Permit/Activity Number: DP19-0164
Project Description: SITE/GRADING/SWPPP - Northwest Medical Ctr - Houghton, hospital, parking, associated infrastructure.

Fees Due: $ 82.50
Note: We require a payment prior to accepting a resubmittal.
Please pay:
1. Online Payment
2. In person at the City of Tucson Permit Counter (Mon-Fri, 8:00 AM to 2:00 PM)
3. By mail - a check payable to City of Tucson (address below), include the Permit Number

Online Payment (Visa, MC, Discover, American Express)
https://www.tucsonaz.gov/pdsd/online-resources-fees-maps-records
1. Total fees due: Payment portal may take 1-2 days to update and be viewable
2. Not case-sensitive but a hyphen is needed, e.g.: dp19-0000
3. Enter your Permit Nbr. and click the “Continue” tab
4. Ignore the line request for Business/Individual Name
5. If any issues, try using the browser Internet Explorer.

View the reviewer's comments: www.tucsonaz.gov/pro
(If information is not available, check back later as data transfers to PRO periodically.)
- Home page, left side, “Activity Search”, enter the Activity Number
- “Permits” section, click on blue tab
- "Reviews" section, click on "Review Details"
Submit the following items to the Filedrop. Before uploading, please enter the Activity Number in the Project Description field.
PDSD Filedrop: https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter (your response to the reviewer's “Requires changes” comments)
2) Plan Set (all pages, full set)
3) Any other documents requested by review staff
4) Name your 3rd submittal documents accordingly, for example: 3_Plan_Set

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
Attn: Permit Counter/Payments
201 N. Stone Avenue, First Floor
Tucson, AZ 85701

Final Status

Task End Date Reviewer's Name Type of Review Description
10/30/2019 SBEASLE1 OUT TO CUSTOMER Completed